Delhi Transport Corporation Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Delhi Transport Corporation - DTC Tender
Civil And Construction
Building Construction
Electrical and Electronics
Electrical Works
Eprocure
Opening Date6 Feb 2024
Closing Date15 Feb 2024
Tender Amount₹ 15,47,189
Costs
EMD
₹ 30,944Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_DTC_253270_1Bid Award Id
ViewTender No
Dy.CGM (Civil)CED/Elect. /2023-2024/28Tender Authority
Delhi Transport Corporation ViewPurchaser Address
-Website
http://http://www.dtc.nic.in/home/delhi-transport-corporation-dtc
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
200
33600
168
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
-
-
-
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
250
34250
137
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
280
47040
168
Supplying and drawing following pair 0.5 sq mm FR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
-
-
-
2 Pair
180
3420
19
Supplying and fixing of following sizes of PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required:
-
-
-
20 mm
150
8550
57
25 mm
510
35190
69
32 mm
40
3560
89
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
-
-
-
Telephone socket outlet
18
1728
96
Bell push
4
456
114
Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
63
18144
288
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
25
600
24
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.
-
-
-
1 or 2 Module (75mmX75mm)
36
6300
175
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
70
21910
313
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
72
29232
406
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
63
8316
132
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
-
-
-
Upto 450 mm sweep
12
2688
224
Supplying and drawing of UTP 4 pair CAT 6E LAN Cable in the existing surface/ recessed steel/ PVC conduit as required.
-
-
-
1 run of cable
180
6120
34
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
-
-
-
Group C
147
61005
415
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)
-
-
-
8 way (4 + 24), Double door
6
19026
3171
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
-
-
-
Single pole
144
24912
173
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
20
140
7
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
-
-
-
63 A
18
40356
2242
Supplying and fixing DP sheet steel enclosure on surface/ recess
along with 25/32 A 240 V "C" curve DP MCB complete with
connections, testing and commissioning etc. as required.( for ac point)
6
5880
980
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required
6
894
149
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
-
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
15
5220
348
150 mm width X 50 mm depth X 1.6 mm thickness
5
1965
393
Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
-
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
1
604
604
150 mm width X 50 mm depth X 1.6 mm thickness
1
714
714
Supplying and installing following size of perforated pre-painted M.S. cable trays reducers with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
-
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
1
683
683
150 mm width X 50 mm depth X 1.6 mm thickness
1
812
812
Supplying and installing following size of perforated pre-painted M.S. cable trays Tee's with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
-
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
1
683
683
150 mm width X 50 mm depth X 1.6 mm thickness
1
812
812
Supplying and installing following size of perforated pre-painted M.S. cable trays cross members with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
-
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
3
1983
661
150 mm width X 50 mm depth X 1.6 mm thickness
4
3096
774
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
2
7344
3672
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
3
12981
4327
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
1
8289
8289
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
75
2100
28
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe FRLSom earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
15
13080
872
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
30
10530
351
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
15
2010
134
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
10
6980
698
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
30
3870
129
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
20
740
37
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
-
-
-
Above 35 sq. mm and upto 95 sq. mm
25
5350
214
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
-
-
-
Above 35 sq. mm and upto 95 sq. mm
80
2240
28
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
-
-
-
Above 35 sq. mm and upto 95 sq. mm
20
440
22
Laying and fixing of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 kV grade of following size
on wall surface as required
-
-
-
Upto 35 sq. mm (clamped with 1mm thick saddle)
250
6250
25
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
10
2690
269
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-
3½ X 70 sq. mm (38mm)
2
788
394
4 X 25 sq. mm (28mm)
12
3096
258
Supplying and fixing following rating, four pole, 415 MCB DB complete with connections, testing and commissioning etc. as required.
-
-
-
63 amps
6
13290
2215
Supply of XPLE insulated PVC sheathed AL conductor cable 1.1 KV grade conforming to IS-7098 of size 3.5Core X 70 sq. mm.
100
61900
619
Supply of XPLE insulated PVC sheathed AL conductor cable 1.1 KV grade conforming to IS-7098 of size 4X25 sq. mm.
250
77000
308
Supply, installation, testing and commissioning of pre-wired, LED fitting of all types, complete with all accessories and lamp etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
-
-
-
36 w 2x2 Recess Mounted LED
35
107800
3080
10 w LED Ceiling for corridor area
165
94710
574
15W LED surface (1X1) type light for Stairecase
16
10624
664
12 w LED Ceiling for toilet
36
24624
684
Ceiling Fan 1200mm sweep complete erected in position with all accessories.
63
128583
2041
Exhaust fan for toilet
12
36120
3010
L.T Panel, for Admin block
Design, manufacture, supply, installation, testing and commissioning of following Utility panels suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 2mm thick CRCA sheet steel for Load bearing members and 1.6 mm thick for non-load bearing members, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber (form-3b Construction). The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.
Important Notes: Common for all Switchboard:
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
Fault current wherever mentioned shall be Ics value. (Ics = 100% Icu).
All MCCB shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, continious variable thermal magnetic O/C and S/C releases. All rating MCCB's shall be thermalmagnetic type.
Incoming MCCBs shall be provided with O/C, S/C, and Earth fault protection releases. Outgoing MCCBs shall be provided with O/C, short circuit protection.
All feeder doors shall have pad locking arrangement.
All TP feeders shall have solid isolable neutral link.
All MCCB used in starter feeder shall be suitable for motor duty application.
All power contactors including NIC shall be of AC3 duty.
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All meters are digital type.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
Bus bar chamber shall be kept at top of the all panels.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm. All Lift Panels transport section should not be more then 1000 mm.
In soft starter Vender should supply power contactor with aux. Contactor & All necessary accessories required etc. (As per BOQ & specification )
All indicating light shall be LED type .
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Client approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
Two (2) Nos. 400 A FP MCCB One (1) No. digital multifunction meter for measurement of voltage and currents with selector push buttons (ELF-3259 of conzerv or equivalent) and one set of CTs of ratio 400A /5A, CL 1.0, 15 VA.
3 Nos. phase indication lamps and 3 Nos. status indication lamps for ON/OFF/ Trip with control SP MCB.
Busbar :
800A TPN Al. Busbar of short circuit withstand capacity 35kA. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.
Outgoing :
All MCCB outgoing feeders shall be of 35 kA breaking capacity and shall be provided with ON/OFF / Trip indication lamps with back up SP MCB.
Four (4) Nos. 125A FP MCCB
Four (4) Nos. 100A FP MCCB
-
-
-
MDB described as above.
1
261750
261750
Rate (DSR-2016 + Add prevailling cost index @ 22.69% On DSR-2016 rate)
658163
149337
0.23
Rate -@9.5% below on DSR-2016+Add prevailling cost index @ 22.69%
807500.18
-76712
0.1