Delhi Development Authority Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Delhi Development Authority - DDA Tender
Eprocure
Opening Date18 Nov 2020
Closing Date25 Nov 2020
Tender AmountRefer Documents
Costs
EMD
₹ 47,285Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2020_DDA_597760_1Bid Award Id
ViewTender No
42/EE/ELD-3/DDA/2020-21Tender Authority
Delhi Development Authority ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used
where 3 phase outlets are required.)
a) 12 way (4 + 36), Double door (DSR-2018)
1
-
9828
... More
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (DSR-2018)
a) 40A
4
-
339
... More
b) 63A
4
-
385
... More
Providing and fixing following rating and breaking capacity and pole MCCB with thermom0agnetic release and terminal spreaders in existing cubicle panel board including0 drilling holes in cubicle panel, making connections, etc. as required.
a) 100 A, 16 KA,TPMCCB (DSR-2018)
6
-
3726
... More
Supply and replacement of LED Floodlight of system wattage 120 watt and replacement of 250 watt MH Light Fitting. Floodlight should have IP65 Pressure die-cast aluminum housing for effective thermal management. The power of LED should not be more than 120 watt and total system lumen should no be less than 14400 lumen Cool day Light(5000K to 6000K), Lumen Efficacy120 Lm/W, Power factor0.95, CRI70. Complete with Mounting Brackets & accessories as required with connections. Rebate of old material is included in this estimate.
12
-
7329
... More
Supply and replacement of LED Floodlight of system wattage 200 and replacement of 400 watt MH light fitting. Floodlight should have IP65 Pressure die-cast aluminium housing for effective thermal management. The power of LED should not be more than 200 watt and total system lumen should no be less than 24000 lumen Cool day Light (5000K to 6000K), Lumen Efficacy120 Lm/W, Power factor0.95, CRI70. Complete with Mounting Brackets & accessories as required with connections. Rebate of old material is included in this estimate.
60
-
13658
... More
Supply and replacement of 3 mtr GI Octagonal Pole having top dia 70mm bottom dia 130mm sheet thickness 3mm with base plate 200x200x12mm of 3 mtr Octagonal pole and SOH GO bracket of 500mm made out of which 48 mm dia pipe 3.2 thickness with a canopy (i/c Deduction Cost of Replaced item)
31
-
5663
... More
Supply and Replacement of Non LED 70 watt with LED post top fitting 50 watt Power coated aluminum die cast and spun aluminum with clear opal diffuser. Suitable for Landscape Lighting. Available in 5700K IP65. The system luminous efficacy≥85 Lumens (including deduction of cost for replaced items)
31
-
9394
... More
Supply and replacement of aesthetically designed tripod style inverted pyramid bollard 8 watt LED made up of aluminum casting with acrylic diffuser for soft illumination effect, the bollard trunk is of black powder coated with silver white finish for tripod stand with color temperature 5000K,voltage 150-260 Volt, rating IP-65 ,surge 4.5KV etc as required (i/c deduction of cost of replaced item
28
-
3998
... More
9 watt LED Spike light with tough and glass suitable for round mounting IP 65 (Color of light as per required at site).The system luminous efficacy ≥100 Lumens.
6
-
3664
... More
Supply and replacement of lighting panel with 160A MCCB & 5hp DOL starter feeder IP-54,(outdoor type) of suitable size made out of 2mm thick MS CRCA sheet i/c connection inter connection of the following accessories mounted there on with suitable size of copper wire/strip with thimble/lugs, earthing the body of the feeder pillar and duly phosphate painted as per technical specification attached. (including deduction of cost for replaced item)
INCOMER
a) 160A FP fixed type MCCB 35KA TMR (Adj. O/L & Adj. S/C Protection), Spreader, 1No C/O Aux. Cont., 1No C/O Trip Cont. & ROM qty-1 b) Digital AMP Meter with Selector Switch class 1.0 qty-1
c) Digital VOLT Meter with Selector Switch 0-500 V qty-1 d) Current Transformer 160/5A, Class 1.0 qty-3
e) Phase Indication R,Y,B qty-3 f) ON/OFF/TRIP Indication qty-3
g) Aux. Contact 2NO. +2NC qty-1 h) Control MCB 2A SP 10KA qty-3
OUTGOING FEEDER
a) 63A FP fixed type MCCB 25KA TMR (Adj. O/L & Adj. S/C Protection), Spreader & ROM qty-1
b) 32A FP fixed type MCCB 25KA TMR (Adj. O/L & Adj. S/C Protection), Spreader & ROM qty-1
LIGHTING FEEDER
a) 32A TP MCB 10KA qty-1 b) On Indicating Lamp LED Type qty-1
c) 40A Power Contactor qty-1 d) Astronomical Timer qty-1
e) Auto/Manual Selector Switch qty-1 f) Start/Stop Push Button qty-2
g) Control MCB 2A SP 10 KA qty-3
5 HP DOL STARTER FEEDER
a) 32A FP MCB 10KA qty-1 b) 25A TP Power Contactor qty-1 c) Thermal over load 9-15A qty-1
d) Single Phase Preventor qty-1 e) ON/OFF Indication qty-2
f) ON/OFF Push Button qty-2g) Aux. Contactor 2NO+NC qty-1
h) Control MCB 2A SP 10 KA qty-3
1
-
174760
... More
Supply and replacement of lighting panel with 200A MCCB &5hp DOL starter feeder IP-54,(outdoor type) of suitable size made out of 2mm thick MS CRCA sheet i/c connection inter connection of the following accessories mounted there on with suitable size of copper wire/strip with thimble/lugs, earthing the body of the feeder pillar and duly phosphate painted as per technical specification attached. (including deduction of cost for replaced item)
INCOMER
a) 200A FP fixed type MCCB 35KA TMR (Adj. O/L & Adj. S/C Protection), Spreader, 1No C/O Aux. Cont., 1No C/O Trip Cont. & ROM. Qty-1 b) Digital AMP Meter with Selector Switch class 1.0. qty-1
c) Digital VOLT Meter with Selector Switch 0-500 V qty-1 d) Current Transformer 160/5A, Class 1.0. qty-3
e) Phase Indication R,Y,B qty-3 f) ON/OFF/TRIP Indication qty-3
g) Aux. Contact 2NO. +2NC qty-1 h) Control MCB 2A SP 10KA qty-3
OUTGOING FEEDER
a) 63A FP fixed type MCB 10KA TMR (Adj. O/L & Adj. S/C Protection), Spreader & ROM qty-1
b) b) 32A FP fixed type MCB 10KA TMR (Adj. O/L & Adj. S/C Protection), Spreader & ROM. Qty-1
c) 63A DP fixed type MCB 10KA qty-1
LIGHTING FEEDER
a) 32A DP MCB 10KA qty-1 b) On Indicating Lamp LED Type qty-1
c) 40A Power Contactor qty-1 d) Astronomical Timer qty-1 e) Auto/Manual Selector Switch qty-1
f) Start/Stop Push Button qty-2 g) Control MCB 2A SP 10 KA qty-3
5 HP DOL STARTER
a) 32A FP MCB 10KA qty-1 b) 25A TP Power Contactor qty-1
c) Thermal over load 9-15A qty-1 d) Single Phase Preventor qty-1 e) ON/OFF Indication qty-2 f) ON/OFF Push Button qty-2
g) Aux. Contactor 2NO+NC qty-1 h) Control MCB 2A SP 10 KA qty-3
2
-
125681
... More
Supply and replacement of lighting panel with 250A MCCB &5hp DOL starter feeder IP-54,(outdoor type) of suitable size made out of 2mm thick MS CRCA sheet i/c connection inter connection of the following accessories mounted there on with suitable size of copper wire/strip with thimble/lugs, earthing the body of the feeder pillar and duly phosphate painted as per technical specification attached. (including deduction of cost for replaced item)
INCOMER a) 200A FP fixed type MCCB 35KA TMR (Adj. O/L & Adj. S/C Protection), Spreader, 1No C/O Aux. Cont., 1No C/O Trip Cont. & ROM. Qty-1 b) Digital AMP Meter with Selector Switch class 1.0. qty-1
c) Digital VOLT Meter with Selector Switch 0-500 V qty-1 d) Current Transformer 160/5A, Class 1.0. qty-3
e) Phase Indication R,Y,B qty-3 f) ON/OFF/TRIP Indication qty-3 g) Aux. Contact 2NO. +2NC qty-1
h) Control MCB 2A SP 10KA qty-4
OUTGOING FEEDER a) 63A FP fixed type MCB 10KA TMR (Adj. O/L & Adj. S/C Protection), Spreader & ROM Digital VOLT Meter with Selector Switch 0-500 V qty-3 b) 40A FP MCB 10K qty-1 c) 40A DP MCB 10K qty-1
LIGHTING FEEDER a) 32A TP MCB 10KA qty-1 b) On Indicating Lamp LED Type qty-1 c) 40A Power Contactor qty-1
d) Astronomical Timer qty-1 e) Auto/Manual Selector Switch qty-1
f) Start/Stop Push Button qty-2 g) Control MCB 2A SP 10 KA qty-3
5 HP DOL STARTER a) 32A FP MCB 10KA qty-1 b) 25A TP Power Contactor qty-1
c) Thermal over load 9-15A qty-1 d) Single Phase Preventor qty-1
e) ON/OFF Indication qty-2 f) ON/OFF Push Button qty-2
g) Aux. Contactor 2NO+NC qty-1 h) Control MCB 2A SP 10 KA qty-3
1
-
176037
... More
Supplying (including deduction of cost for replaced item) of following sizes of multicore aluminum conductor XLPE insulated armoured cable 1.1 KV grade confirming to IS:7098 (Part-I) complete with all amendments etc as required:-
a) 2x10 sq. mm
250
-
166
... More
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) DSR-2018
7
-
131