Postgraduate Institute Of Medical And Education And Research Tender
View complete overview of Chandigarh PGIMER Tender
Postgraduate Institute Of Medical And Education And Research - PGIMER Tender
Civil And Construction
Eprocure
Opening Date22 Jan 2021
Closing Date1 Feb 2021
Tender AmountRefer Documents
Costs
EMD
₹ 55,040Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_PGIME_610442_1Bid Award Id
ViewTender No
PGI/Engg/RAC/2021/91Tender Authority
Postgraduate Institute Of Medical And Education And Research ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
VRF/VRV Split Units
-
-
-
Supply, installation , testing and commissioning of following minimum capacity VRV/ VRF High wall type Indoor unit equipped with washable synthetic me diaper-filter, fan section with low noise fan / dynamically balanced blower, multi speed motor, coil section with DX copper coil ,electronic expansion valve, outer cabinet ,cordless remote control ,drain pan ,necessary accessories etc., suitable for operation on 230V±10%,50Hz, single phase AC supply ,complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS system. The cooling capacity of indoor unit will be at airinlet conditions of 27Degree C DB and 19 Degree C WB temperature
-
-
-
2 TR split units
9
-
22100
1.65 TR split units
6
-
21746
VRF/VRV Tee/ Y joints for indoor & outdoor units Supply, Installation, Testing and commissioning of Imported fittings (Ref Net) Y-joints etc as per specifications.
15
-
4684
Part B
-
-
-
Copper Refrigerant Piping
-
-
-
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for VRV/VRF system , complete with fittings , with suitable adjustable ring type hanger supports ,jointing / brazing including accessories , insulated with XPLE Class-O tubular insulation /with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines , all accessories as per specifications etc. as required
-
-
-
34.9mm dia (OD) (Hard drawn) with tube thickness1.62mm with19 mm thick insulation
40
-
1230
28.58 mm dia (OD) (Hard drawn) with tube thickness1.2mm with19 mm thick insulation
40
-
1108
19mm dia (OD) (Hard drawn) with tube thickness1.2mm with19mm thick insulation
40
-
707
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with19mm thick insulation
170
-
588
12.7 mm dia (OD) (Soft drawn) with tube thickness1.2mm with19mm thick insulation
40
-
466
9.5mm dia (OD) (Soft drawn) with tube thickness1.2mm with19mmthick insulation
150
-
331
6.4mm dia (OD) (Soft drawn) with tube thickness1.2mm with19mm thick insulation
40
-
245
Control & Transmission Wiring
-
-
-
Providing & fixing control cum transmission wiring of 3 core x 1.5 sq. mm. copper in PVC conduits between indoor and outdoor unit with earthling.
200
-
70
Providing & fixing control cum transmission wiring of 3 core x 2.5 sq. mm. copper in PVC conduits between indoor and outdoor unit and from electrical panel to inline fan for toilet Exhaust with earthling.
200
-
114
P/F electrical inter connecting control wiring 3 core 6 sqmm copper conductor PVC insulated PVC sheathed unarmoured cable between indoor and outdoor units, with double earthing , clamped on surface including end terminations and as per site requirement as desired by Engineer-In-Charge
200
-
245
P/F PVC insulated PVC sheathed armoured copper cabling 4 core 10 sqmm from electrical panel to blower units with GI double earthing clamped on surface etc.
100
-
532
Condensate Drain Piping:
-
-
-
Supply and installation of 40 mm dia UPVC piping for condensate water drainage upto nearest floor trap.
100
-
161
Supply and installation of 32 mm dia UPVC pipingf for condensate water drainage upto nearest floor trap
100
-
130
Supply and installation of 25 mm dia UPVC piping for condensate water drainage upto nearest floor trap
100
-
105
Supply and Installation of 65 mm static 5000 cfm Blower Section for Exhaust Air in Toilet. having SISW Centrifugal Backward Curve blower with energy efficent motor and Horizontal floor mounted
2
-
122498
SITC of INLINE Fans 1000 CFM @ 13 mm WG From Each Toilet to Duct
10
-
25408
Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required :-
-
-
-
0.80 mm
110
-
1104
0.63 mm
60
-
942
Supplying & fixing of powder coated extruded aluminum Supply Air Grills with aluminum volume control dampers as per specifications
4
-
8480
Supplying, fixing, testing, commissioning of Supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
4
-
11363
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required
20
-
5507
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
10
-
7559
P/F Flexible double canvas connection between blower and supply air duct.
2
-
2218
Supply installation testing and commissioning of free floor / wall mounted Electric Panel for HVAC system of radiotheraphy and adjoining Toilet Exhaust made of 16/14 SWG thickness, CRCA sheet duly powder coated complete with solid interconnection Voltmeter, Ammeter, Indicating lights, selector switch incoming /outgoing isolator, single phase preventer complete with Aluminium bus bar and soild copper interconnection as per site requriment and specification attached sepeartaely.
1
-
337531
SITC of hot dipped galvanized Cable tray
-
-
-
MS perforated cable tray hot dipped galvanized 100 x 50 x1.6 mm
50
-
239
MS perforated cable tray hot dipped galvanized 150 x 50 x1.6 mm
50
-
268
MS perforated cable tray hot dipped galvanized 300 x 50 x1.6 mm
80
-
429
Dismantling work which includes dismantling of old ducting, frames, grills, panel, cables etc. complete in all respect and shifting the scrap material up to scrap yard
1
-
15000
Minor civil work (wall openings for fixing of plenum & replasting the wall including Brick work). It also includes foundation work for exhaust blower installation.
1
-
10000
Buy Back Item
-
-
-
Buy back cost of old dismatled material which include old ducting,exhaust inline fan, frames, grills, electrical panel,cables etc.complete in all respect (-)
1
-
20000
Evaluation Notes How It Works ?