Postgraduate Institute Of Medical And Education And Research Tender

View complete overview of Chandigarh PGIMER Tender

Postgraduate Institute Of Medical And Education And Research - PGIMER Tender

Electrical and Maintenance Works
Eprocure
Opening Date11 Aug 2021
Closing DateCancelled
Tender Amount₹ 5,63,00,000 
Notes
Download

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Centrifugal type compressor open-type / semi-hermetic complete with automatic capacity control, safety switches, speed increasing gears, forced feed lubrication system etc. as per specifications.

-

-

-

... More
1 No.- Suitable capacity squirrel cage induction motor with class 'F' insulation suitable for operation on 415±10% volts, 3-phase, 50Hz A.C. supply. The open type Motor shall be rated for minimum 110% of rated compressor BHP consumption.

-

-

-

... More
1 NO. - Close transition type air / liquid cooled VFD suitable for compressor motor , complete with CTs, OLP,Under voltage protection,Phase reversal protection,independent SPPR,timer controls & automatic tripping systems with integrated circuits and sensing elements (field devices) such as HP/LP/Anti-freeze protection. The VFD shall be floor mounted / unit mounted type with minimum IP-54 enclosure. Machine mounted VFD shall have IP23/ NEMA-1 enclosure.Active Harmonic Filters. THDI & THDV not exceeding 5% at source

-

-

-

... More
Necessary drive arrangement

-

-

-

... More
1 Set- Lubrication device consisting of automatic electric oil pump, oil cooler, head tank, oil strainer, automatic pressure regulating valve, oil heater, oil heater thermal switch etc. as per specificaitons.

-

-

-

... More
1 No.- Matching shell and tube water cooled condenser of M.S. shell and integrally finned copper tubes.

-

-

-

... More
1 No.-Optimally paired MS shell and tube type factory insulated evaporator (flooded type, shell insulated with a minimum of 32 mm thick (19 mm + 13 mm) nitrile rubber) , complete with the safety devices, drain and purge valves and integrally finned copper tubes.

-

-

-

... More
1 Lot- Inter-connecting refrigerant piping (factory assembled and tested), including and not restricted to safety valves,angle valves, isolation valves liquid line indication,liquid level controllers etc.

-

-

-

... More
1 Set- Micro-processor based control panel, as described in the intent of specification. This panel will at a minimum display the following field information in english language: Supply voltage,electric frequency,load current,chilled water inlet and outlet temperature, cooling water inlet and outlet temperature,operating pressures in the system etc.

-

-

-

... More
Lot- Refrigerant line accessories comprising of safety valves, angle valve,Isolation valves, liquid line indications, liquid level control etc.

-

-

-

... More
Lot- Water flow switches at inlet and outlet of condenser & chiller, water drain & air purge valves wherever required.

-

-

-

... More
Lot- Suction line and chiller insulation with minimum 19mm thick polvinyl nitrile rubber insulation finished with 0.63mm thick Aluminium cladding complete as required.

-

-

-

... More
Lot- Frame work (including victaulic couplings at the inlet & outlet of cooler & condenser; & painting of all components) for mounting the above condenser, chiller compressor and motor with base plate complete with antivibration pads/ springs.

-

-

-

... More
Lot- Initial / first charge of refrigerant gas & compressor oil

-

-

-

... More
Lot-anti vibratory mounts over the sub-structural (MS)foundation provided by others for the chilling unit.

-

-

-

... More
Refrigerant piping shall be factory assembled as per the specifications.

-

-

-

... More
Additional Safety Devices shall include Internal Thermostat for Compressor Motor, Fusible Plug, Discharge Gas Thermostat, Operation Hour-Meter etc.

-

-

-

... More
Chillers should be compatible to hook up with any BMS System, including any integrator/ software etc.

-

-

-

... More
An automatic voltage correcter for the control circuit of microprosessor panel shall be supplied with the chiller.

-

-

-

... More
COP of chiller shall not be less than 6.3, full load Ikw/TR not more than 0.64 at AHRI conditions

-

-

-

... More
Machine Opreating Parameters

-

-

-

... More
Tonnage - 400 TR

-

-

-

... More
Full Load IKW/TR - 0.64

-

-

-

... More
NPLV Not more then - 0.39

-

-

-

... More
Evaporator

-

-

-

... More
Chilled water in - 54 deg.F

-

-

-

... More
Chilled Out - 44 deg.F

-

-

-

... More
Fouling Factor - 0.0005 hr.sq.ft.-deg.F/BTU

-

-

-

... More
Maximum pressure drop - 7 meter

-

-

-

... More
Condenser

-

-

-

... More
Chilled water in - 90.0 deg.F

-

-

-

... More
Chilled Out - 97.5 deg.F

-

-

-

... More
Fouling Factor - 0.001 hr.sq.ft.-deg.F/BTU

-

-

-

... More
Maximum pressure drop - 9 meter

-

-

-

... More
Due to limitation in plant room the evaporator and condensor connections shall be on same side.

-

-

-

... More
Conformity and Selection criteria:

-

-

-

... More
THE CHILLER SHALL CONFIRM TO AHRI AND BID SHALL ACOMPANY THE COMPUTERSIED SELECTION SHEET AS ALSO MENTIONED IN THE SPECIFICATIONS.Chiller to conform to ARI 550/590 conditions as pre-requisite, but to be also tested for the constatnt and reducing condenser inlet and outlet temperature (site conditions : 90 Deg F inlet and 97.5 Deg F outlet) , as mentioned in this chapter.Chiller shall have a microprocessor control panel, which is compatible with BAS , and is communicable on an open protocol.

-

-

-

... More
Factory type test ( for one chiller ) as mentioned above, at 25% , 50% load, 75% load and 100% load, to establish the COP, at ARI 550/590-1998, and specified duty conditions of 90 Deg F (IN) and 97.5 Deg F (OUT) condenser water temperature (CONSTANT & REDUCING), based on AHRI relief.

-

-

-

... More
Refrigerant and efficiency criteria:

-

-

-

... More
Chiller shall have open protocol modbus communication card to replicate all chiller parameter over BMS terminal.

-

-

-

... More
Chilling machine as described above, with a capacity of 400 TR at above prescribed site conditions.

-

-

-

... More
CIF site, Including Customs duty, CVD, Auxiliary duty, Clearing, port handling and other incidental charges, Clearing, port handling and other incidental charges, Installation, testing and commissioning.

2

-

11492882

... More
Supplying, installing, testing and commissioning of CENTRIFUGAL VERTICAL INLINE PUMPS, factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system.  Vertical split case design, in cast iron bronze fitted construction specifically designed for quiet operation for chilled water cooling systems as shown in the drawings. All pumps shall be provided with mechanical seal and aligned properly as required.All Inline pumps shall be complete with SS multi-spring outside balanced type seal. The pump motor shall be suitable for 415 + 10% volts, 50 cycles, 3 phase power supply. Secondary chilled water pumps shall be suitable for operation on Adjustable frequency drives. Pumps with performance characteristics as given below:

-

-

-

... More
Primary Chilled Water pumps

-

-

-

... More
1 No. Vertical Inline Split Coupled centrifugal pump.

-

-

-

... More
1 No. suitable HP TEFC induction motor with class `F' insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply.( 4 pole, 1500 RPM,syn)

-

-

-

... More
Suction guide to be supplied by pump manufacturer for unit responsibility.

-

-

-

... More
2 nos. - dial type pressure gauges.

-

-

-

... More
Lot - Mounting frame with Anti vibration pads.

-

-

-

... More
Lot - RCC/cement concrete foundation for the pump unit.

-

-

-

... More
Operating parameters

-

-

-

... More
Water flow rate = 960 USGPM

-

-

-

... More
Head = 39.3 Ft. of water /12 M

-

-

-

... More
Motor HP = 15 HP (Suggested)

-

-

-

... More
The pump efficiency shall not be less than 70 %.

-

-

-

... More
Quantity indicated includes one standby

3

-

298138

... More
SECONDARY PUMP FOR APC BLOCK :Supply, installing, testing and commissioning of Secondary Variable Speed Pumping System consisting of adjustable frequency drive (AFD) for each pump. 1 No. microprocessor based pump controller & sensor less control as per the site requirement. The entire system along with secondary pumps must be sourced from pumping system supplier only, for unit responsibility. Secondary chilled water pumps comprising of the following

3

-

809352

... More
The system shall be complete in all respects and suitable for following ratings. The secondary pump efficiency shall not be less than 70 %.

-

-

-

... More
1 Nos. Vertical in line Split Coupled centrifugal pumps complete with suitable HP, 4 Pole 1500 RPM,syn, TEFC induction motor with class ‘F’ insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply for each pump. Parallel pump controller to operate the set of the pump stated in a parallel pump operation.

-

-

-

... More
1 Nos. adjustable Frequency drives integrated with pump motor, BMS Compatible

-

-

-

... More
DPT (Sensors ) Supplied by pump Manufacturers or Sensor less Controls in Pump

-

-

-

... More
Suction guide to be supplied by pump manufacturer for unit responsibility.

-

-

-

... More
2 nos. - Pressure gauges.

-

-

-

... More
Lot - Mounting frame with Anti vibration pads.

-

-

-

... More
Lot - RCC/cement concrete foundation for the pump unit.

-

-

-

... More
1 Lot Microprocessor based BMS compatible, variable frequency speed controller complete with necessary fittings and wiring

-

-

-

... More
Water flow rate for each pump : 960 USGPM

-

-

-

... More
Head : 78 feet / 24 M

-

-

-

... More
Motor HP : 25 HP (suggested)  

-

-

-

... More
Note: All, pumps, Motors, VFD, controller and software etc are to be sourced from the same vendor. This shall be of similar make/ type as being installed for the main plant and the logic controller shall be shared.

-

-

-

... More
All VFD shall have separate controller. The VFD shall not behave in master and slave format.

-

-

-

... More
Supplying, installing, testing and commissioning of VERTICAL SPLIT CASING PUMPS, factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system.  Split case design, in cast iron bronze fitted construction specifically designed for quiet operation for chilled water cooling systems as shown in the drawings. All pumps shall be provided with mechanical seal and aligned properly as required. The pump motor shall be suitable for 415 + 10% volts, 50 cycles, 3 phase power supply. Secondary chilled water pumps shall be suitable for operation on Adjustable frequency drives. Pumps with performance characteristics as given below:

-

-

-

... More
Condenser water pumps

-

-

-

... More
1 No. Vertical Split Casing pump.

-

-

-

... More
1 No. suitable HP TEFC induction motor with class `F' insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply.( 4 pole 1500 RPM,syn)

-

-

-

... More
2 nos. - dial type pressure gauges.

-

-

-

... More
Lot - Mounting frame with Anti vibration pads.

-

-

-

... More
Lot - RCC/cement concrete foundation for the pump unit.

-

-

-

... More
Operating parameters

-

-

-

... More
Water flow rate = 1600 USGPM

-

-

-

... More
Head = 95 Ft. of water /29 M

-

-

-

... More
Motor HP = 60 HP (Suggested)

-

-

-

... More
The pump efficiency shall not be less than 70 %.

-

-

-

... More
Quantity

1

-

476084

... More
AIR HANDLING UNITS

-

-

-

... More
Suppy, Installation ,Testing and commissioning of sectionalised construction double skin AHU with Thermal Break complete with Pre filters, chilled water coils of copper tube and aluminum fins construction , squirrel cage induction motor , DIDW BACKWARD CURVE centrifugal fan , V-belt drive package and vibration isolation. The AHU shall have 25+/- 3 mm thick panels made out of 0.8 mm thick external preplasticide GI sheet and internal GSS sheets of thickness 0.8 mm, with PUF 40 kG/CuM density . The blower shall be AMCA certified-210 and AMCA 300. Entire unit vibration level as per ISO 2372/3945. The AHU assembly shall be complete with electrically inter-locked fan guard, access doors with nylon hinges, nylon door locks handles, port holes in fan section, sealed screw end caps , internal light and limit switches , SS drain pan etc.

-

-

-

... More
The AHU coil Frame sould be of SS with SS drain pan of minimum thickness 1.25 mm and shall be insulated.

-

-

-

... More
Floor mounted AHU motor shall be three phase motor suitable for VFD drive. Motor shall be EFF-1/ IE-2

-

-

-

... More
All AHU's should be compatible to hook up with any BMS System

-

-

-

... More
The installation shall include all civil works to create entry of the equipments into the AHU room.

-

-

-

... More
Cooling coil - For 6 row - Coil shall be 3R +3R & with 300 mm gap between the two coils, including the access door (either from top or from side) between the two coils.

-

-

-

... More
All AHU's shall be supplied with thermal break profile.

-

-

-

... More
Floor mounted AHU

-

-

-

... More
12700 CFM / 33.0 TR, DIDW fan backward curved centrifugal fan, 65 mm SP WG 6 row deep chilled water coil , pre filter, MERV-13 FILTER, with three phase motor (VFD Compatible) , Thermal break profile.

2

-

325880

... More
11500 CFM / 29.0 TR, DIDW fan backward curved centrifugal fan, 65 mm SP WG 6 row deep chilled water coil , pre filter, MERV-13 FILTER, with three phase motor (VFD Compatible) , Thermal break profile.

3

-

300894

... More
9500 CFM / 25.0 TR, DIDW fan backward curved centrifugal fan, 65 mm SP WG 6 row deep chilled water coil , pre filter, MERV-13 FILTER, with three phase motor (VFD Compatible) , Thermal break profile.

1

-

260472

... More
7700 CFM / 20.0 TR, DIDW fan backward curved centrifugal fan, 65 mm SP WG 6 row deep chilled water coil , pre filter, MERV-13 FILTER, with three phase motor (VFD Compatible) , Thermal break profile.

2

-

214938

... More
7000 CFM / 20.0 TR, DIDW fan backward curved centrifugal fan, 65 mm SP WG 6 row deep chilled water coil , pre filter, MERV-13 FILTER, with three phase motor (VFD Compatible) , Thermal break profile.

3

-

214648

... More
3400 CFM / 12.0 TR, DIDW fan backward curved centrifugal fan, 110 mm SP WG 6 row deep chilled water coil , 4 row DX VRV coil, Mixing Box , pre filter, MERV-13 FILTER, HEPA FILTERS, with three phase motor (VFD Compatible) , Thermal break profile.

4

-

256806

... More
Vertical floor mounted 5000 CFM / 14.0 TR, DIDW fan forward curved centrifugal fan, 40 mm SP WG 4 row deep chilled water coil , pre filter, MERV-8 FILTER, with three phase motor , Thermal break profile.

8

-

154739.8

... More
Vertical floor mounted 4500 CFM / 12.0 TR, DIDW fan forward curved centrifugal fan, 40 mm SP WG 4 row deep chilled water coil , pre filter, MERV-9 FILTER, with three phase motor , Thermal break profile.

5

-

142777.38

... More
Vertical floor mounted 3000 CFM / 8.0 TR, DIDW fan forward curved centrifugal fan, 40 mm SP WG 4 row deep chilled water coil , pre filter, MERV-9 FILTER, with three phase motor , Thermal break profile.

1

-

101294.76

... More
Ceiling suspended AHU of following capacity with forward curved blower with 60 mm Total pressure. The AHU shall have thermal break profile and shall ccomprise of following sections.

-

-

-

... More
2500 CFM / 10 TR/ 60 mm static DIDW fan backward curved centrifugal fan, 65 mm SP WG 4 row deep chilled water coil , pre filter, MERV-13 FILTER, with three phase motor , Thermal break profile.

1

-

96857.08

... More
Supplying, installation, testing and commissioning of electrical HW generator equipped with sufficient number of electrical immersion heaters. The pressure vessel shall be constructed and insulated on all sides with 100 mm thick fiber glass and cladded with 0.80 mm aluminum sheet in a neat and clean manner. The generator shall be equipped with all automatic and safety controls such as manual reset high temperature water outlet, step controller and recycling relay, 'ON' 'OFF' switch thermostats, pilot light, low water cutoff and other controls as per manufacturers recommendations. All controls and terminals shall be located in an integral control cabinet factory wired and tested. The generator shall be suitable for 415 (+)/(-) 10% volts, 50 cycle, 3 phase power supply. The entire generator shall be factory assembled and tested at 350 PSI pressure. The Hot Water Generator shall be of following capacity made of 8mm MS sheet and dish end made of 10mm MS having 16 gauge stainless steel lining with heaters arranged in banks and controlled by electronic Controller and Thermostats so that hot water is generated at 55 Deg C with nominal variation including necessary controls including inlet and outlet connections for water as per specifications complete with pressure release valve, low level cut-out. Autovent sight-glass, foundation for HWG as per specifications complete as required.

-

-

-

... More
300 KW

1

-

445826

... More
Supply, installation, testing and commissioning of an insulated roof mounted chilled water expansion tank of PVC construction. The tank shall be complete with necessary connection for piping. Insulation shall be 50 mm thick expanded polystyrene covered with sand cement plaster. Each tank shall be of capacity minimum 1000 liters.

1

-

11543

... More
Supply, installation, testing and commissioning of 2-way motorized valves suitable for Chilled water as well as hot water application complete with Electrical / Electronic actuator, necessary wiring and required accessories for proper operation and control of valves of following sizes. (Vendor to submit the Selection sheets of the Control Valves for all sizes individually)

-

-

-

... More
65 mm dia valve

3

-

32345

... More
50 mm dia valve

3

-

19696

... More
40 mm dia valve

20

-

17269

... More
32 mm dia valve

4

-

15000

... More
Supply, installation, testing and commissioning of cooling / heating thermostats for various Air Handling Units as per specifications including all accessories, mountings, wiring between thermostat & unit, terminations etc., complete in all respect as required and as per specifications.

-

-

-

... More
Proportional thermostats for Air Handling Units

30

-

4868

... More
Supply, installation, testing and commissioning of Humidistat for various Air Handling Units as per specifications including all accessories, mountings, wiring between Humidistat & unit, terminations etc., complete in all respect as required and as per specifications.

4

-

2261

... More
Supplying, installing, testing and commissioning of Fan coil unit, each complete with 3 rows deep chilled water coil, centrifugal fans, cleanable fabric filters, main condensate drain pans, auxiliary drain pan, as described in specifications, casing, coil piping connections, through copper pipes, condensate drain connections, wiring, control wiring in conduit upto thermostat boxes. All fan coil units shall be suitable for 220 + 6% volts, 50 cycles, single phase power supply. Fan Coil Units shall be of following refrigeration capacities as listed.

-

-

-

... More
2.0 TR nominal capacity

25

-

11577

... More
1.5 TR nominal capacity

81

-

10543

... More
1.0 TR nominal capacity

4

-

9613

... More
Fan Coil Unit Controls

-

-

-

... More
Supply, installation, testing and commissioning of controls for fan coil units consisting of 2-way motorized spring return valves, Snap acting type heating/cooling thermostat with fan speed switch, wiring etc.

-

-

-

... More
25 mm dia valve

25

-

3439

... More
20 mm dia valve

85

-

3217

... More
Exhaust fan unit with filters

-

-

-

... More
Supply, installation, testing and commissioning of Double skin Exhaust unit with DIDW blower, pre-filter and fine filter(EU-13). The unit shall have direct driven fan with high efficency motor complete with power efficiency

-

-

-

... More
Air Quantity 150 CFM Static 25 mm

14

-

26993

... More
Air Quantity 500 CFM Static 25 mm

6

-

26993

... More
Inline Fans

-

-

-

... More
Supply, installation, testing and commissioning of inline ducted Fans as shown in drawings. Fan motor shall be suitable for single phase, 50 Hz AC supply. The capacity of the fan given as under:-

-

-

-

... More
Air Quantity 100 - 150 CFM Static 10 mm

65

-

3185

... More
Propeller Fans

-

-

-

... More
Supply, installation, testing and commissioning of direct driven Propeller fans for exhaust air as shown on drawings and as per specifications. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan capacities and Electrical characteristics shall be as follows:

-

-

-

... More
225 mm dia 1400 RPM fan suitable for 220 +/- 10% volts, 50 Cycles, Single Phase AC Supply (with bird screen)

83

-

1862

... More
Variable Refrigerant Volume System

-

-

-

... More
Supply, Installation Testing and Commissioning of Variable Refrigerant Volume type multi unit air-conditioning system (HEAT PUMP TYPE) complete with indoor and outdoor units with central individual controller etc as per details Below. The units shall be cooling only as per specifications.

-

-

-

... More
Outdoor Unit

-

-

-

... More
Supply , Installation Testing and Commissioning Including vacumising, Gas charging of Modular type outdoor units equipped with highly efficient scroll/ Rotary compressors, with all Inverter Scroll/ rotary type compressor(s), special acryl pre-coated heat exchanger, low noise condenser fan, auto check function for connection error etc, centralize controller for individual control complete as per OEM specifications of Following Capacity. ( Refrigerant R-410A)

-

-

-

... More
20 HP Capacity (HEAT PUMP)

4

-

328300

... More
Each ODU shall have minimum 2 compressors

-

-

-

... More
Supply Installation Testing and Commissioning of Required AHU kit for connecting the Cooling coils with the VRF Outdoor unit complete with expansion valve, Sensors, wired remote controller and PCB etc. as required.

-

-

-

... More
20 HP each

4

-

28941

... More
Supply of HVAC dedicated VFDs with IP 55 enclosures with Mains disconnect, complying with the tender specifications and having:

-

-

-

... More
1. Built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the VFD.

-

-

-

... More
2. Built-in EMC Filters (electromagnetic compatibility filters) for VFDs for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 3.

-

-

-

... More
3. Three-feedback PID controller having capability to simultaneously accept 3 feedback signals from temperature sensors or pressure sensors for process optimization and accordingly regulate the speed of the AHUs.

-

-

-

... More
4. Additional 3 PID controllers to control external devices such as chilled water modulating valve, fresh air damper, etc. thus reducing the number of I/Os in DDC Controllers & improving system reliability.

-

-

-

... More
5. Automatic Energy Optimization / Load dependent flux optimization functionality for maximum energy savings.

-

-

-

... More
6. MODBUS RTU as the communication protocol between BMS & VFDs.

-

-

-

... More
7. VFDs not meeting above requirements shall provide external disconnect, external harmonic filters, additional external EMC Filters to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 3, external PLCs / DDCs to achieve 3 Feedback PID Controller functionality and external devices controlling capabilities.

-

-

-

... More
8. The VFD cost shall include suitable PID controller for regulating the flow of air by controlling the frequency of VFD.

-

-

-

4

-

38257

... More
PIPING

-

-

-

... More
MS Chilled / Hot Water Pipe ( Insulated) within Building

-

-

-

... More
Supply, fixing in position, testing and commissioning of the following over ground MS class ‘C’ pipes of following diameter cut to required lengths and installed with all welded joints, complete with the necessary fittings like elbows, tees and reducers, sockets etc. excluding valves for Chilled / Hot water lines but including insulation as per specifications.

-

-

-

... More
Pipe insulation Inside the building shall be done with Expanded Polystyrene(24 kg/cum)and covered with Starbond/Equilant UV protective coating as specified

-

-

-

... More
Pipes shall confirm to IS 3589 for sizes 200 mm and above and IS 1239 for sizes upto 150 mm

-

-

-

... More
300 mm dia MS pipes 75 mm thick Insulation

110

-

6186

... More
250 mm dia MS pipes 75 mm thick insulation

230

-

5205

... More
200 mm dia MS pipes 75 mm thick insulation

120

-

4324

... More
150 mm dia MS pipes 75 mm thick insulation

90

-

2952

... More
125 mm dia MS pipes 50 mm thick Insulation

135

-

2598

... More
100 mm dia MS pipes 50 mm thick Insulation

135

-

2410

... More
80 mm dia MS pipes 50 mm thick insulation

155

-

1934

... More
65 mm dia MS pipes 50 mm thick insulation

160

-

1725

... More
50 mm dia MS pipes 50 mm thick insulation

180

-

1535

... More
40 mm dia MS pipes 50 mm thick insulation

150

-

1341

... More
32 mm dia MS pipes 50 mm thick insulation

275

-

1273

... More
25 mm dia MS pipes 50 mm thick insulation

280

-

1184

... More
20 mm dia MS pipes 50 mm thick insulation

280

-

1068

... More
Providing and fixing in position the following Butterfly Valves duly insulated as per specifications.

-

-

-

... More
300 mm dia Valves.

2

-

19817

... More
200 mm dia Valves. Motorised valve

4

-

70510

... More
200 mm dia Valves.

12

-

8698

... More
150 mm dia Valves

2

-

5335

... More
125 mm dia Valves

20

-

4703

... More
80 mm dia Valves

6

-

2996

... More
65 mm dia valves

6

-

2875

... More
50 mm dia Valves

40

-

2621

... More
40 mm dia valves

8

-

2457

... More
Providing and fixing in position following Balancing Valves duly insulated as per specifications.

-

-

-

... More
200 mm dia Valves.

10

-

53988

... More
125 mm dia Valves

2

-

20251

... More
80 mm dia Valves

3

-

11068

... More
65 mm dia valves

3

-

9977

... More
50 mm dia Valves

20

-

8885

... More
40 mm dia valves

4

-

6886

... More
Providing and fixing in position following Balancing Valves duly insulated as per specifications.

-

-

-

... More
200 mm dia valves

6

-

19541

... More
Providing and fixing in position following Balancing Valves duly insulated as per specifications.

-

-

-

... More
200 mm dia

10

-

23306

... More
125 mm dia

2

-

13806

... More
80 mm dia

3

-

7461

... More
65 mm dia

3

-

5050

... More
50 mm dia

20

-

4590

... More
40 mm dia

4

-

4153

... More
MS Chilled / Hot Water Pipe ( Insulated) outside Building in Trench/ Hume Pipe

-

-

-

... More
Supply, fixing in position, testing and commissioning of the following over ground / underground MS class ‘C’ pipes of following diameter cut to required lengths and installed with all welded joints, complete with the necessary fittings like elbows, tees and reducers, sockets etc. excluding valves for Chilled / Hot water lines but including insulation as per specifications.

-

-

-

... More
Pipe insulation Inside the building shall be done with Expanded Polystyrene and covered with 2 layers of Tarfelt finished with Sand Cement Plaster.

-

-

-

... More
150 mm dia MS pipes 75 mm thick insulation

80

-

3142

... More
125 mm dia MS pipes 50 mm thick Insulation

10

-

2774

... More
100 mm dia MS pipes 50 mm thick Insulation

70

-

2410

... More
80 mm dia MS pipes 50 mm thick insulation

65

-

1934

... More
65 mm dia MS pipes 50 mm thick insulation

55

-

1725

... More
Auto air Vent 15 mm

23

-

1883

... More
CONDENSER WATER PIPING &VALVES

-

-

-

... More
Supply, fixing in position, testing and commissioning of the following over ground MS class ‘C’ pipes of following diameter cut to required lengths and installed with all welded joints, complete with the necessary fittings like elbows, tees and reducers, sockets etc. excluding valves for condenser water lines as per specifications.

-

-

-

... More
300 mm dia

110

-

5188

... More
250 mm dia

80

-

4383

... More
Providing and fixing in position the following Butterfly Valves as per specifications.

-

-

-

... More
300 mm dia

2

-

21126

... More
250 mm dia

4

-

16482

... More
Providing and fixing in position following Balancing Valves as per specifications.

-

-

-

... More
250 mm dia

2

-

101178

... More
Providing and fixing in position following Check Valves as per specifications.

-

-

-

... More
300 mm dia

1

-

34524

... More
Providing and fixing in position following Y-Strainer duly insulated as per specifications.

-

-

-

... More
300 mm dia

2

-

50328

... More
250 mm dia

4

-

34967

... More
Thermometers

56

-

957

... More
Pressure Gauges

78

-

1094

... More
Flow switches

4

-

2031

... More
SITC of Ball Valve set for FCUS

-

-

-

... More
25 mm dia

25

-

1925

... More
20 mm dia

85

-

1109

... More
Insulated pvc DRAIN 10 Kg/Cm2 plus 6 mm insulation piping with fittings etc.

-

-

-

80

-

300

120

-

233

185

-

198

375

-

165

... More
Refrigerant Piping for VRV units

-

-

-

... More
Supply, Installation, testing and commissioning of Interconnecting refrigerant pipe work with (19 mm / 13mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger and all external piping shall run in covered cable tray as per specifications.

-

-

-

... More
31.8 mm O.D.(insulation : 19 mm)

100

-

1170

... More
19.1 mm O.D.(insulation : 13 mm)

100

-

707

... More
AIR SIDE DISTRIBUTION

-

-

-

... More
Supply, installation, balancing and commissioning of Factory Fabricated GSS Rectangular ducting complete with neoprene gaskets, elbows , splitter dampers , vanes , hangers,supports, etc. as per approved drawings and specifications of following sheet thickness complete as required.

-

-

-

... More
0-750 mm 24 G GSS

300

-

983

... More
751-1500 mm 22G GSS

300

-

1154

... More
1501-2200 mm 20G GSS

300

-

1273

... More
2201 mm and above 18G GSS

80

-

1677

... More
Supply, installation, balancing and commissioning of Fabricated at site GSS Rectangular ducting complete with neoprene gaskets, elbows , splitter dampers , vanes , hangers,supports, etc. as per approved drawings and specifications of following sheet thickness complete as required.

-

-

-

... More
0-750 mm 24 G GSS

100

-

942

... More
751-1500 mm 22G GSS

100

-

1104

... More
1501-2200 mm 20G GSS

100

-

1458

... More
2201 mm and above 18G GSS

80

-

1615

... More
SITE FABRICATED DUCT -ALUMINIUM DUCT

-

-

-

... More
Supply, Fabrication , Installation and testing of sheet metal ducts in accordance with the approved shop floor drawings and specifications , and shall also confirm to the BIS specifications. The hardware shall be chrome plated or of stainless steel.All lateral and transverse joints shall be sealed with silicon based mastic sealant.

-

-

-

... More
Aluminum Sheet thickness - 0.80 mm

250

-

986

... More
Aluminum Sheet thickness - 1.00 mm

100

-

1220

... More
MOTORIZED FIRE AND SMOKE DAMPERS

-

-

-

... More
Supplying, fixing, testing and commissioning of fire dampers incombination in supply air duct/ main branch and return air path as and where required of required sizes i/c control wiring , the damper shall be motorized & spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored . The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.

-

-

-

... More
Motorised Fire & Smoke dampers should be compatible to hook up with any BMS System & shall release open protocol (BACnet / MODBUS)

-

-

-

... More
1 Lot - Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers. With fire alarm panel.

-

-

-

... More
1 Lot - Sealing the openings around the sleeve of the fire dampers with approved fire sealant, as per the recommendations of the manufacturer and specifications.

-

-

-

... More
a) Bare Fire Dampers with 500 mm sleeve . For supply air Fire dampers to be provided with factory fabricated TDC flanges

24

-

9883

... More
b) Control panel actuator, including Electrical spring type actuator, remote indication of the fire damper position.

50

-

9212

... More
COLLAR DAMPERS

-

-

-

... More
Supplying, fixing, testing and commissioning of multiblade type Collar / louver damper of aluminium sheet, provided with suitable links, levers and quadrants for manual control of volume of air flow and for proper balancing of air distribution as per approved shop floor drawings and specifications.

28

-

4987

... More
Supply, Installation Testing & commissioning of G.I. multiblade volume control duct damper complete with neoprene gasket , nuts bolts, screws, linkages, flanges etc. as per specifications.

25

-

6500

... More
Supplying & fixing of powder coated extruded aluminium section grills (Fixed Bar) with louvers but without volume control dampers complete as required and of approved shade and colour. & as per specifications

75

-

5507

... More
Supplying, fixing, testing commissioning of supply air diffusers of powder coated aluminium equipped with removable core and aluminium volume control dampers with anti smudge ring & removable core of approved colour and shade. & as per specifications

-

-

-

... More
Powder coated extruded aluminium supply air diffuser of approved colour and shade.

20

-

11363

... More
Supplying, fixing, testing commissioning of Return air diffusers of powder coated aluminium equipped with removable core and aluminium volume control dampers with anti smudge ring & removable core of approved colour and shade. & as per specifications

-

-

-

... More
Powder coated extruded aluminium return air diffuser of approved colour and shade.

20

-

7559

... More
Supply, Installation and Testing of air transfer grilles of approved make and colour. & as per specifications

-

-

-

... More
Powder coated extruded aluminium air Intake Louvers

10

-

7833

... More
CANVASS CONNECTIONS

-

-

-

... More
Supply, Installation and Testing of Double layer fire proof Canvass connection wuth 1/2 Hr fire rating as per specification

40

-

985

... More
Insulation

-

-

-

... More
DUCT LINE THERMAL INSULATION

-

-

-

... More
Supplying and fixing of Thermal insulation of ducts cold insulation using anti microbial closed cell Nitrile rubber (class "O") aluminium foil faced with density 55 kg/cum miniumum duct insulation as specified , insulation in slab sections stuck to the duct & fixtures using manufacturer approved cold adhesive on both surface of the duct and inner face of the insulation slab section. The joints shall sealed with 50mm wide and 3 mm thick self adhesive nitrile rubber aluminium faced tape insulation

-

-

-

... More
19 mm thick

400

-

697

... More
13 mm thick

600

-

623.1

... More
ELECTRICAL WORKS

-

-

-

... More
Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall undergo seven tank process before painting as per standards with 2 coats of red oxide primer and final approved shade of enamel paint. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness.

-

-

-

... More
The panel shall be complete with DOL / SD starter as per kW rating of the serviced motor, Terminal block for power distribution, Contactor, over load relay with built in single phasing protection , Phase indicating lights and indicating light for ON status,Digital voltmeter and digital ammeter with selector switches, Time delay relay for delayed automatic restart of air handling unit motor, Wiring for microswitch for stopping the fan when fire damper closes, For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation , All starters shall be provided with suitable potential free contract for connections to the Building Automation System , 220 / 24 V Transformer (if required for the performance of the system) ..All panels shall be suitable to receive and process the signal from the PLC panel and fire zonel panel/ zonal fire control module (as the case may be) Potential free NO-NC contact shall be provided in each panel. Inter connecting and looping shall also be done accordingly. The panel as described above shall be either wall mounted or floor mounted.

-

-

-

... More
All panel shall have 300 mA EL MCB on out going

-

-

-

... More
The panel drawing shall be approved before taking up the fabrication.

-

-

-

... More
MAIN PANEL

-

-

-

... More
Incoming:

-

-

-

... More
2 no. 1600 amp MDO-ACB of 50 kA Breaking capacity with 1 bus coupler, (1 # 4 POLE 1600 amp MDO-ACB) with magneto thermal release, CT's and 6 NO + 6NC auxiliary contacts and 18 way secondary isolating contacts. With U/V release and shunt trip.With necessary mechanical and electrical interlocking between incomer & bus coupler. Releases will be provided in both incomer alongwith NO/NC contact.

-

-

-

... More
Metering for incoming:

-

-

-

... More
1 Nos. Voltmeter of range 0-500V, selector switch and 2 Amps SP MCB back up . (2 set )

-

-

-

... More
1 Nos. Ammeter of range 0-1600A, selector switch and 3 Nos. of associated CT's of ratio 1600/5 A. (2 set )

-

-

-

... More
Bus Bars:

-

-

-

... More
Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 2000amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints.

-

-

-

... More
The bus bar sizing calculations shall be submitted for approval, considering all derating factors.

-

-

-

... More
Outgoing (All MCB/MCCB/MPCB shall be suitable for motor duty & with heavy duty detachable solid neutral link):

-

-

-

... More
1 Nos. 1000 A TP MDO ACB of 50kA breaking capacity for for centrifugal chiller

-

-

-

... More
2 Nos. 800 A TP MCCB of 50 kA breaking capacity for chiller

-

-

-

... More
3 Nos. 160 A TP MCCB of 35kA breaking capacity with suitable rating, with STAR DELTA STARTER, Suitable for 37.0 KW motor with ON / OFF indication lamps, with one Set of Red, Green & Amber Indicating Lamps, Start/Stop Push buttons with remote control start/stop arrangement, Auto/Manual/Off selector switch. for Condenser Water Pumps

-

-

-

... More
3 Nos. 63A TP MCCB of 35kA breaking capacity with Single Phase Preventor of suitable rating, with STAR DELTA STARTER, Suitable for 11.0 KW motor with ON / OFF indication lamps, with one Set of Red, Green & Amber Indicating Lamps, Start/Stop Push buttons with remote control start/stop arrangement, Auto/Manual/Off selector switch. - for Primary Chilled Water Pumps

-

-

-

... More
3 Nos. 80A TP MCCB of 35kA breaking capacity with suitable rating, with STAR DELTA STARTER, Suitable for 22.0 KW motor with ON / OFF indication lamps, with one Set of Red, Green & Amber Indicating Lamps, Start/Stop Push buttons with remote control start/stop arrangement, Auto/Manual/Off selector switch. - for Secondary Chilled Water Pumps.

-

-

-

... More
4 Nos. 63A TP MCCB of 35kA breaking capacity with suitable rating, with VSD, Suitable for 11 KW motor with ON / OFF indication lamps, with one Set of Red, Green & Amber Indicating Lamps, Start/Stop Push buttons with remote control start/stop arrangement, Auto/Manual/Off selector switch. - for Cooling tower

-

-

-

... More
4 Nos. 63 A TPN, indication lamp with MCB for ‘ON’ status of equipment. Overload and under voltage protection device, ELCB of minimum 300 mA current sensitivity, Time delay relay, Single phase preventer, phase reversal protection.

-

-

-

... More
1 Nos. 630 A TP MCCB of 50kA breaking capacity for HWG

-

-

-

... More
3 Nos. Spare Space

-

-

-

... More
The panel shall have necessary contactors / ancillaries for BMS operation.

-

-

-

... More
Panel as described as above and complete in all respects

1

-

2127142

... More
AHU Panel Type 1 (Wall mounted)

-

-

-

... More
Incoming

-

-

-

... More
Phase indicating lights with control fuses.

-

-

-

... More
Breaker ON/OFF/TRIP indicating lights.

-

-

-

... More
Metering for incoming:

-

-

-

... More
1 No. Voltmeter of range 0-500V, selector switch and 2 Amps SP MCB back up.

-

-

-

... More
One Nos. Ammeter of range 0-63A, selector switch and 3 Nos. of associated CT's of ratio 63/5 A.

-

-

-

... More
1 set of phase indicating lamps RYB with 2A,SP, MCB backup.

-

-

-

... More
Outgoings

-

-

-

... More
1 nos TP MPCB, suitable capacity upto 7.5 HP motor with DOL starter and VFD bypass

-

-

-

... More
1 No. 10 amps DP MCB (single Phase) with step down transformer 220V to 24V (AC)

-

-

-

... More
Each outgoing shall have auto/manual selector switch, indication lamps with control MCB's, ON/OFF push buttons, necessary internal control and power wiring in all respect. .The panel shall have necessary contactors / ancillaries for BMS operation and fire signal.

-

-

-

... More
Panel as described above and in drawings.

24

-

22752

... More
AHU Panel Type 2 (Wall mounted)

-

-

-

... More
Incoming

-

-

-

... More
Phase indicating lights with control fuses.

-

-

-

... More
Breaker ON/OFF/TRIP indicating lights.

-

-

-

... More
Metering for incoming:

-

-

-

... More
1 No. Voltmeter of range 0-500V, selector switch and 2 Amps SP MCB back up.

-

-

-

... More
One Nos. Ammeter of range 0-63A, selector switch and 3 Nos. of associated CT's of ratio 63/5 A.

-

-

-

... More
1 set of phase indicating lamps RYB with 2A,SP, MCB backup.

-

-

-

... More
Outgoings

-

-

-

... More
1 nos TP MPCB, 40 amp with DOL with space for VSD along with by-pass arrangement).

-

-

-

... More
1 No. 10 amps DP MCB (single Phase) with step down transformer 220V to 24V (AC)

-

-

-

... More
Each outgoing shall have auto/manual selector switch, indication lamps with control MCB's, ON/OFF push buttons, space for VFD and suitable ventilation for VFD, necessary internal control and power wiring in all respect. .The panel shall have necessary contactors / ancillaries for BMS operation and fire signal.

-

-

-

... More
Panel as described above.

4

-

27458

... More
AHU Panel Type 3 (Wall mounted)

-

-

-

... More
Incoming

-

-

-

... More
Metering for incoming:

-

-

-

... More
1 No. Voltmeter of range 0-500V, selector switch and 2 Amps SP MCB back up.

-

-

-

... More
One Nos. Ammeter of range 0-63A, selector switch and 3 Nos. of associated CT's of ratio 63/5 A.

-

-

-

... More
1 set of phase indicating lamps RYB with 2A,SP, MCB backup.

-

-

-

... More
Outgoings

-

-

-

... More
1 nos TP MPCB, suitable capacity upto 7.5 HP motor with ASD starter and VFD bypass

-

-

-

... More
1 No. 10 amps DP MCB (single Phase) with step down transformer 220V to 24V (AC)

-

-

-

... More
Each outgoing shall have auto/manual selector switch, indication lamps with control MCB's, ON/OFF push buttons, necessary internal control and power wiring in all respect. .The panel shall have necessary contactors / ancillaries for BMS operation and fire signal.

-

-

-

... More
Panel as described above and in drawings.

2

-

27458

... More
Supply installation testing & commissioning of Control indication cume annunciation control desk in plant room for remote start stop & run status of all AHU's in APC and SPH the control panel shall have hooter to indicate fault level. Total no. of equipements :- AHU's - 52 , Pumps-9 , HWG-2 , Cooling tower-4 , Chillers-3 , VRV ODU's-4 , Fan units-20 .

1

-

469858

... More
Supplying of complete cable work using 1.1kV grade XLPE insulated PVC sheathed steel tape/wire armoured underground stranded cables as per IS-7098 (Part-1) of following sizes of electric supply from main panels in AC plant room, to various loads including interconnections (terminations) from starters to motors on connections on both sides as per specifications and as required.

-

-

-

... More
3.5Cx300 Sqmm aluminum armoured

150

-

1069

... More
3Cx120 Sqmm aluminum armoured

150

-

396

... More
3Cx35 Sqmm aluminum armoured

400

-

157

... More
3Cx10 Sqmm Aluminum armoured

600

-

92

... More
4Cx06 Sqmm aluminium armoured

100

-

82

... More
4Cx25 Sqmm Copper armoured

400

-

871

... More
3Cx2.5 Sqmm Copper armoured

1000

-

97

... More
4C x 2.5 Sqmm copper armoured (Control Cable)

800

-

120

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

-

-

-

... More
Upto 35 sq. mm (clamped with 1mm thick saddle)

3300

-

33

... More
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)

150

-

93

... More
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)

150

-

150

... More
Cable Trays

-

-

-

... More
Supplying and installing following size of performated pre-painted MS cable trays cross members with perforation not more than 17.5% joined with connectors, suspended from the ceilling with MS suspenders including nuts , bolts, bends , reducers etc. painted suspenders etc. as required.

-

-

-

... More
150mm (W) x 50mm (D) x 1.6mm thickness

300

-

531

... More
300mm (W) x 50mm (D) x 1.6mm thickness

150

-

621

... More
450mm (W) x 50mm (D) x 2.0mm thickness

50

-

700

... More
600mm (W) x 50mm (D) x 2.0mm thickness

50

-

765

... More
Local MCB Isolator box for VRV ODUs

-

-

-

... More
Supplying, installation, testing and commissioning of Following MCB isolator in weather proof, 16SWG CRCA sheet steel enclosure Powder coated

-

-

-

... More
63 amp MCB TP

4

-

2777

... More
Supplying, of control cabling with insulated PVC sheathed wire/cable as per IS-7098 (Part-1) of following sizes including terminations on suitable cable trays / uPVC pipe with supports, as required including connections on both sides as per specifications and as required.

-

-

-

... More
2 core x 1.5 sq. mm.

430

-

42

... More
3 core x 1.5 sq. mm.

600

-

52

... More
4 core x 1.5 sq. mm.

900

-

65

... More
6 core x 1.5 sq. mm.

250

-

91

... More
8 core x 1.5 sq. mm.

240

-

120

... More
12 core x 1.5 sq. mm.

300

-

170

... More
16 core x 1.5 sq. mm.

170

-

223

... More
24 core x 1.5 sq. mm.

300

-

332

... More
30 core x 1.5 sq. mm.

200

-

425

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

-

-

-

... More
Upto 35 sq. mm (clamped with 1mm thick saddle)

3390

-

33

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.

-

-

-

... More
3.5Cx300 Sqmm aluminum armoured

8

-

936

... More
3Cx120 Sqmm aluminum armoured

12

-

480

... More
3Cx35 Sqmm aluminum armoured

18

-

283

... More
3Cx10 Sqmm Aluminum armoured

20

-

211

... More
4Cx06 Sqmm aluminium armoured

60

-

219

... More
4Cx25 Sqmm Copper armoured

8

-

250

... More
3Cx2.5 Sqmm Copper armoured

40

-

211

... More
4C x 2.5 Sqmm copper armoured (Control Cable)

200

-

219

... More
MISC CIVIL WORK

-

-

-

... More
Dismantling of Existing AC syustem at APC comprising of chiller, Pumps, pipings, Ducting, AHU, Grilles etc.

1

-

125000

... More
Misc civil work including road cutting, hume pipe

1

-

125000

... More
Buy back for 2 no Old Reciprocating 80 TR chillers , 1 no VAM 250 TR , Pumps, Pipes, Panel, AHUs, FCUs, piping, Valves Ducting grilles etc.

1

-

2200000



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.