Chandigarh Administration Tender
View complete overview of Chandigarh Chandigarh Administration Tender
Chandigarh Administration Tender
Civil And Construction
Building Construction
Eprocure
Opening Date11 Dec 2023
Closing Date12 Jan 2024
Tender Amount₹ 8,65,966
Costs
EMD
₹ 17,320Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_CHD_78251_1Bid Award Id
ViewTender No
OP1/23/2023-24Tender Authority
Chandigarh Administration ViewPurchaser Address
-Website
http://http://chandigarh.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply and Erection of 11KV 400Amp. Triple pole, outdoor, vertical mounted gang operated switch single vertical break three, insulator per pole, tilting type blade with copper flexible connecting links and arcing horns etc. with 32mm nominal dia round type pipe as face coupler G.I. pipe, MS box channel 75x40mm two angle iron pieces each not less than 1850mm in length and made out of MS angle iron of size 50x50x5mm. It shall be completed with gang operated handle workable from 1.20 Mtrs from ground level with pad locking arrangement both in “OFF” and “ON” positions. The female contacts shall be of box spring type. 11KV G.O. switches i.e. 11 KV post insulators, G.I. Pipe, MS channel, Brass Male/ Female contacts & Arcing Horns shall comply with the Indian Standard Specification IS:2544, IS:5340 (Part-III) and IS:9921( Part Ito V)
3
19203
6401
... More
Supply and Erection of Lightening Arrestor set of ISI mark 5KA station class gapless surge arrestor suitable for 11KV O/H line confirming to IS:3070 (Part-III) IEC 99.4 (1991) with latest version thereof on four pole structure duly supported with M.S. Flat 50x6mm clamps with required size of nuts & bolts. The lightening arrestor shall be earthed properly with existing earth 7/10 SWG. The lightening arrestor shall be connected on one side with HT line and other side with main earth line. The L.A. should be earthed separately with main earth of all parts of lightening arrestor should be loop earthed with 7/10 SWG wire. Complete Job in all respect.
3
11602
3867.5
... More
Supply and Erection of stay set for HT line / structure comprising of following items w.r.t. each stay set as per standard design of the department:-
8.1 Supply and Erection of Anchor made of M.S. Channel 100 x 50 x 6mm 2ft long.=1No. 8.2 Supply and Erection of G.I. Thimbles of suitable size =2Nos.
8.3 Supply and Erection of M.S. Round 16mm dia. (31") long having threading on one side 30cm and hook on other side as per standard design of the department. =1No. 8.4 Supply and Erection of M.S clamps made of M.S Flat 50 x 6mm =1No.
8.5 Supply and Erection of M.S. Nut & Bolt for stay wire =2Nos
8.6 Supply and Erection of M.S elbow of M.S. round 19/20mm dia., 1.8mtr long welded with M.S. Flat iron of size 50x6mm=300mm long. =1No.
8.7 Supply and Erection of M.S. Stay Wire 7/10SWG of 12mtr length =12Kg
8.8 Supply and Erection of 11KV disc insulator of 45KN capacity. alongwith fitting. =1No.
8.9 Supply and Erection of M.S. Channel of size 75x40x6mm x 6'long=1No.
12
42156
3513
... More
Earthing of structure/ Transformer body /Neutral Point /LA etc complete as under:-
a). Supply & Erection of Pipe earthing for 315KVA T/F including excavation of pit 4.5 Mts. Deep and surrounded by 65 kg charcoal Kerry and 5kg salt mixed and laid in alternate layer including supply & erection of GI Pipe 50mm dia medium class, drilling of 23 nos. 12mm holes on GI pipe for adding watering as per Drawing attached at Page no.37 of DNIT.
b). Supply & Erection stay wire 7/10 SWG duly crimped with thimble on one side to GI pipe and other side to T/F neutral through GI pipe medium class, 50mm dia. (Total length=4.73meter of GI pipe 50mm dia medium class) in ground and conduit pipe of size 20mm x 4.5 mtr along the structure and complete in all respect.
c) Supply & Erection of GSL 8 SWG wire for loop earthing of insulators pins/LA/GO switch Handle etc. complete as required including connections with thimbles etc.
15
43305
2887
... More
S/E of G.I Pipe 'B' class pipe 100MM dia fixed with existing pole with M.S. clamps made out of MS flat 50x6mm with appropriate size of nuts and bolts.
42
32508
774
... More
Low tension Shunt capacitor 37.5 KVAR:- Supply, installation, testing and commissioning of low tension shunt capacitor 37.5 KVAR, 440 volt, 50Hz, three phase internally delta connected metalized polypropylene type (MRP) with inert gas impregnated conforming to IS: 13340-/1993 ( re-affirmed 1998) ISS-13340-41, IS-12672/1989 and IS 13341/1992 Standards with latest amendments upto date should be installed in iron clad minimum 16 SWG steel sheet all weather proof enclosure with conopy with locking arrangement suitable to 37.5 KVAR Shunt Capacitor with MCB on panel on pole mounting S/Stn. including making inter connections with 10 mm2 PVC 3/c 25mm2 AL armoured cable between MCB to T/F with incoming side of LT ACB AL link and other side with LT shunt capacitor through TP MCB 63 Amp. with S/E of lugs, nuts and bolts complete in all respect LT ACB shunt Capacitor as required at site as per.
Note :- :- Make of LT Shunt capacitor 37.5 KVAR should be L&T/ Siemens/ Schneider /ABB and Havel’s.
3
29600
9866.94
... More
Laying of HT 3 x 300mm2 XLPE cable through supply and erection of HDPE pipe 6kg. pressure having outer dia 110 mm in road.
550
211128
383.87
... More
Erection of 11 KV 3 x 300mm2 XLPE cable along the pole through GI pipe 100mm dia, excluding cost of GI pipe & Along the pole.
40
668
16.7
... More
S/E of 11 KV 3 x 50mm2 XLPE Cable end joint O/D type, the joint should be heat shrinkable type. The joint should be ISI marked. The make of joint should be 3M/ Denson/Raychem.
4
68664
17166