Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Providing installing testing commissioning and handing over of Central Air Conditioning System HVAC for Punjab and Haryana Civil Secretariat Building Level 5 to 9 Sector 1 Chandigarh
Report Missing Document

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Minimum COP should be 5.4 as per latest ECBC code 2017 of Govt of India (ECBC Guideline) for water cooled screw chillers. The IPLV of VFD chiller should not be more than 0.4KW/TR as per CPWD norm. The IKW/TR should not be more than 0.68 KW/TR.

-

-

-

... More
mono/ twin screw type semi hermetic compressor complete with automatic capacity control, safety switches, speed increasing gears forced feed lubrication system etc. complete as per specifications as required.

-

-

-

... More
The semi hermetic compressor should be mono / twin type. Capacity control range of compressor shall be from 25% to 100% instead of 20% to 100% as per CPWD Specifications.

-

-

-

... More
Suitable Nos & suitable capacity squirrel cage induction motor with class 'F' insulation suitable for operation on 415 volts ±10% , 50 Hz, A.C. supply.

-

-

-

... More
Suitable capacity of VFD starter suitable for compressor motor complete with ammeter with CTs, over load protection, under voltage protection, protection against phase reversal & independent single phase preventors etc complete as required with Active Harmonic Filters to achieve THDI & THDV not to exceed 5% at source.

-

-

-

... More
Necessary drive arrangement

-

-

-

... More
Suitable No. of Lubrication device consisting of automatic electric oil pump, oil cooler, head tank, oil strainer, automatic pressure regulating valve, oil heater, oil heater thermal switch etc. as per specifications.

-

-

-

... More
Matching shell and tube water cooled condenser of M.S. shell and integrally finned copper tubes having max. two passes - as per OEM.

-

-

-

... More
Matching shell & tube flooded type chiller for screw type units of MS shell and copper tubes having max. two passes - as per OEM.

-

-

-

... More
Refrigerant piping fittings, valves, Expansion valves and accessories to inter connect compressor, condenser, chiller and expansion valve etc. complete as per specification as required.

-

-

-

... More
Microprocessor based control panel comprising of Controls including sensors, factory manufactured and tested. All Control function including start up and shut down leaving chilled water temperature Control, Compressor and Electronic Expansion Valve modulation, anti re-cycle logic, automatic Compressor load limiting. it shall also be equipped with the following protection and monitoring devices - 1 Set.

-

-

-

... More
The Microprocessor shall have a simple keyboard access input system and HMI shall be of touch screen display.

-

-

-

... More
Microprocessor based control panel shall have suitable hardware & software so that it can be integrated directly to with standard communication open protocol using backnet / Modbus as well as open IP.

-

-

-

... More
Refrigerant line accessories comprising of safety valves, angle valve, liquid line indication, liquid level control etc. complete as per specifications as required.

-

-

-

... More
Water flow switches at inlet of condenser & chiller, water drain & air purge valves wherever required as per specifications.Chiller shall be complete with necessary vibration isolation arrangement and flexible pipe joint (rubber bellow).

-

-

-

... More
Suction line and chiller insulation with minimum 19 mm thick polyvinyl nitrile rubber insulation finished with 0.63 mm thick G.S.S. cladding complete as per specifications as required.

-

-

-

... More
Frame work for mounting the above condenser, chiller, compressor and motor with base plate complete with antivibration pads/ springs etc. complete as per specifications as required.

-

-

-

... More
Initial/ first charge of refrigerant gas & compressor oil complete as per specifications as required.

-

-

-

... More
Custom duty, port clearing, any other incidental charges, Loading, Local transportation, insurance upto handing over and all other incidental charges upto delivery at site to be included.

-

-

-

... More
The evaporator & condensor shall have ASME stamping only.

-

-

-

... More
The chiller shall be AHRI certified

-

-

-

... More
The make of the compressor and the water chilling machine shall be the same.

-

-

-

... More
Chiller shall be with VFD & AHF

-

-

-

... More
300 TR Actual Capacity at above conditions

2

-

5606983

-

-

-

... More
a) The work shall include pre shipping inspection / testing of works at factory, Freight, Insurance, Port clearance, loading / unloading, Installation, testing and commissioning as per specifications.

-

-

-

... More
b) Necessary RCC foundation also to be provided by contractor in the quoted rate.

-

-

-

... More
c) One no chiller out of two shall be got tested at AHRI certified test bed in OEM factory for 4 load points at (100%, 75%, 50% & 25%) the cost of the agency / firm. The machine shall be accompanied with the 4 point test report duly certified by the OEM. No payment shall be released without the same.

-

-

-

... More
CONDENSER PUMPS

-

-

-

... More
Supply installation balancing and commissioning of the following;

-

-

-

... More
Vertical Split Casing pump set with CED/Epoxy Coated Cast Iron casing, Bronze impellers with stainless steel shaft & with integral reinforced flanged rubber bellows at suction and discharge side. Pump connected to suitable capacity TEFC ventilated induction motor, IE-3 with class 'F' insulation, 1450 RPM, suitable for 415 volts ± 10%, 3 phase, 50 Hz A.C. supply.

-

-

-

... More
2 Nos. - 125 mm dia dial type pressure gauges. With stainless steel binders & vibration dampers.

-

-

-

... More
Mounting frame work with vibration isolation arrangement, coupling guard, foundation bolts and all other accessories.

-

-

-

... More
Integral reinforced flanged rubber bellows at suction and discharge side.

-

-

-

... More
Min. pump efficiency at duty conditions shall be 75%

-

-

-

... More
RCC/CC Foundation to be provided by contractor.complete in all respect as per EIC

-

-

-

... More
Flow Rate : 1240 GPM

-

-

-

... More
Head : 23 Metre WC

-

-

-

... More
Pump set complete with pumps

3

-

339495

... More
CHILLED WATER PRIMARY PUMPS

-

-

-

... More
Supplying, erection, testing and commissioning of Vertical Split Casing primary chilled water pump set capable of delivering 744 GPM of water against a head 12 Mtr. each pump shall comprise the following as required as per specifications.

-

-

-

... More
1 No. - Vertical Split Casing type pump with bronze impeller, S.S Shaft, C.I body and mechanical seal with integral reinforced flanged rubber bellows at suction and discharge side.

-

-

-

... More
2 Nos. - 125 mm dia dial type pressure gauges. With stainless steel binders & vibration dampers.

-

-

-

... More
Duly insulated with 80 kg/cum density resin bonded fibre glass duly cladded with aluminium sheets of 0.5mm thickness and properly clamped to pump in two semi-circular sections as per specifications.

-

-

-

... More
1 No.- Suitable HP, TEFC squirrel cage induction motor, IE-3 with class 'F' insulation, IP -55 Protection, 1450 RPM , operating on 415 volts ± 10%, 3 phase, 50 Hz A.C. supply. (3 Working + 1 Stand By)

-

-

-

... More
Pump set shall be complete with necessary vibration isolation arrangement, MS base plate, coupling guard, flexible connections, foundation bolts and all other accessories.

-

-

-

... More
Min. pump efficiency at duty conditions shall be 75%

-

-

-

... More
RCC/CC Foundation to be provided by contractor.complete in all respect as per EIC

-

-

-

... More
Pump as above

3

-

269965

... More
CHILLED WATER SECONDARY PUMPS (VARIABLE PUMPING SYSTEM)

-

-

-

... More
Supplying, erection, testing and commissioning of variable speed secondary chilled water pumping system with VFD and all pump system controller, comprising of:

-

-

-

... More
Vertical Split Casing pump set with CED/Epoxy Coated Cast Iron casing, Bronze impellers with stainless steel shaft & with integral reinforced flanged rubber bellows at suction and discharge side. Pump connected to suitable capacity TEFC ventilated induction motor, IE-3 with class 'F' insulation, 1450 RPM, suitable for 415 volts ± 10%, 3 phase, 50 Hz A.C. supply.

-

-

-

... More
Duly insulated with 80 kg/cum density resin bonded fibre glass duly cladded with aluminium sheets of 0.5mm thickness and properly clamped to pump in two semi-circular sections as per specifications.

-

-

-

... More
Renewable wear ring of bronze shall be furnished on the casing.

-

-

-

... More
Variable speed drive Panel should have a dedicated programmable logic controller with individual drive for each pump and with required no. of sensors and the entire unit has to be procured from the Pump manufacturer to ensure the smooth operation of the system. The Programmable logic controller shall be able to control minimum 1 Pump and maximum of 4.6 Pumps, Automatic cascade control of pumps, automatic sequence change, Friction loss compensation, pump status shall be there. Display shall be graphical type with minimum 320 pixels X 240 Pixels VGA display with backlight. Drive should have rated input frequency 50 Hz and output frequency range of 0.5 to 132 Hz. An IP41/IP55 Nema Standard powder coated steel enclosure for Basement, with sufficient capacity of cooling fan shall house all the electrical control components.

-

-

-

... More
Microprocessor based control panel shall have suitable hardware & software so that it can be integrated directly to BMS with standard communication protocol using backnet / Modbus /any open Protocol.

-

-

-

... More
(All the Pump set will have their control panel with respect to the motor rating & should be suitable for chilled water circulation).

-

-

-

... More
All pumps to be provided with separate variable frequency drives. Control panel with respect to motor rating and should also consist of cooling fan, enclosoures etc. as required.

-

-

-

... More
Mounting frame work with vibration isolation arrangement, flexible connections, , coupling guard, foundation bolts and all other accessories.

-

-

-

... More
Electronic Differential Pressure Transmitters as required.

-

-

-

... More
Integral reinforced flanged rubber bellows at suction and discharge side.

-

-

-

... More
Complete system to be mounted on a common MS base frame structure with base plate of pump and shall have following duty and characteristic:

-

-

-

... More
Min. pump efficiency at duty conditions shall be 75%

-

-

-

... More
RCC/CC Foundation to be provided by contractor.complete in all respect as per EIC

-

-

-

... More
Flow Rate : 744 GPM

-

-

-

... More
Head : 35 Metre WC

-

-

-

... More
Pump set complete

3

-

561267

... More
Pump VFD - The lot shall include 3 Nos VFD's, differential pressure transmitters, all housed in factory built control panel as described above)

1

-

924933

... More
COOLING TOWER

-

-

-

... More
Supply, installation, testing and commissioning of multi cell square type Induced draft FRP Cooling tower of suitable for 1323000 Kcal/hr. heat rejection capacity (suitable for chiller with actual capacity of 350TR) with PVC fillings with integral louvers and drift eliminators open pan suitable for water distribution complete with hot FRP water basin either fitted with spray nozzles or having self rotating sprinklers, statically and dynamically balanced though required nos of axial flow type fan-direct driven or driven through special bevelled reduction gear box with TEFC induction motor with IP-55 protection, IE-3, suction screen, make up and quick fill arrangement, overflow and drain connections and suitable inspection ladder, access arrangement for cooling tower interior, anti vibration mountings etc. complete as per specifications and as required.

-

-

-

... More
Water Leaving Temperature : 32.2 Deg C

-

-

-

... More
Water Entering Temperature : 36.4 Deg C

-

-

-

... More
Water Flow Rate : 1240 GPM

-

-

-

... More
Ambient Wet Bulb Temperature : 26.6 Deg C

3

-

551517

... More
SUBHEAD 'B' AHU'S & Etc

-

-

-

... More
CEILING SUSPENDED AIR HANDLING UNITS

-

-

-

... More
Supplying, installing, testing and commissioning of factory built Ceiling Suspended double skin type air handling units made of 25 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6 mm outside layer and plane GI of 0.6mm inside layer with polyurethene foam (PUF) insulation of density 32 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower DIDW forward curved centrifugal fan with required static pressure, 6 row deep cooling coil, section with aluminium finned copper tubes (tube thickness not less than 0.5mm), filter section with 50 mm thick metal viscous/ washable synthetic type Pre filter (MERV 8 - 90% down to 10 microns), belt drive package with TEFC drive motor (IE-3) suitable for 415 ± 10% volts, 50 Hz, 3 phase, A.C supply, complete, drain connections with drain valve, stainless steel drain pan, necessary vibration isolation arrangement etc, complete as per specifications of following capacities:

-

-

-

... More
1000 cfm, 2.5TR with 35mm SP

6

-

43243

... More
1500 cfm, 3.5TR with 35mm SP

10

-

40213

... More
2100 cfm, 3.5TR with 35mm SP

8

-

61008

... More
2500 cfm, 5.5TR with 35mm SP

2

-

67894

... More
3000 cfm, 5.0TR with 35mm SP

9

-

78360

... More
3400 cfm, 6.0TR with 35mm SP

5

-

82078

... More
3900 cfm, 7.5TR with 35mm SP

8

-

92820

... More
4500 cfm, 8.0TR with 40mm SP

4

-

109071

... More
5000 cfm, 8.5TR with 40mm SP

2

-

113615

... More
5500 cfm, 10.0TR with 40mm SP

2

-

121740

... More
6000 cfm, 15.0TR with 40mm SP

1

-

126285

... More
6300 cfm, 12.0TR with 40mm SP

1

-

139230

... More
Supply, installation, testing and commissioning of ceiling suspended Normal static type FCU's each complete with 3 row deep cooling coil of copper tubes aluminium fins construction, centrifugal fan, 3 speed motor, washable filters, insulated drain pan, coil piping connections, condensate drain connection, complete as required, thermostats and electrical wiring, manual air vent valve etc. as required as per specification & drawings with the following capacities:-

-

-

-

... More
800 CFM , 2.0 TR

2

-

14328

... More
1000 CFM , 2.5 TR

1

-

15420

... More
1600 CFM, 4.0 TR

1

-

27155

... More
TREATED FRESH AIR UNIT

-

-

-

... More
Supplying, installing, testing and commissioning of factory built Ceiling Suspended double skin type treated fresh air units made of 25 mm thick panels consisting of pre plasticized GI casing of 0.6 mm thickness outside layer and plane GI of 0.6 mm thick inside layer with polyurethene foam (PUF) insulation of density 32 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower DIDW forward curved centrifugal fan, 8 row deep cooling coil section only with aluminium finned copper tubes (tube thickness not less than 0.5mm), filter sections with 50 mm thick washable synthetic type Pre filters having efficiency 90% down to 10 micron with belt drive package with TEFC drive motor suitable for 415 ± 10% volts, 50 Hz, 3 phase, A.C supply, complete with drain connections with drain valve, stainless steel drain pan, necessary vibration isolation arrangement etc, complete as per specifications of following capacities:

-

-

-

... More
350 CFM, 2.0 TR with 40mmSP

3

-

40764

... More
600 CFM, 3.0 TR with 40mmSP

3

-

43793

... More
850 CFM, 4.5 TR with 40mmSP

6

-

46823

... More
1100 CFM, 5.5 TR with 40mmSP

15

-

52607

... More
1400 CFM, 7.0 TR with 40mmSP

2

-

56326

... More
1800 CFM, 7.0 TR with 40mmSP

1

-

63862

... More
CHILLED WATER CASSETTE

-

-

-

... More
Supply, installation, testing & commissioning of Chilled water Cassette type indoor units with compact cooling coil, multispeed fan motor, the blower shall be dynamicaly balanced and designed for silent operation, the filters shall be washable synthetic media type arranged for convenient cleaning and replacement and inbuilt drain pump, wireless/ wired remote as required with following capacity.

-

-

-

... More
0.9 TR

9

-

35186

... More
1.1 TR

25

-

36825

... More
1.2 TR

61

-

36825

... More
1.7 TR

94

-

39814

... More
2.0 TR

115

-

39814

... More
2.7 TR

57

-

48104

... More
3.2 TR

14

-

49357

... More
3.7 TR

4

-

49357

... More
HI WALL UNITS CHILLED WATER TYPE

-

-

-

... More
Supply, installation, testing & commissioning of Hi Wall split air-conditioning units with compact cooling coil, multispeed fan motor, the blower shall be dynamicaly balanced and designed for silent operation, the filters shall be washable synthetic media type arranged for convenient cleaning and replacement and inbuilt 2-way control valve & wireless remote as required with following capacity.

-

-

-

5

-

34367

5

-

37596

1

-

37596

... More
SPLIT UNITS

-

-

-

... More
Supply, installation, testing & commissioning of Invertor Type Hi Wall split air-conditioning unit for cooling option, unit suitable to operate from 230±10% volt, 50 Hz, 1 phase power supply, with air-cooled evaporator with coil, fan, and fan motor, air-cooled condenser with hermetically sealed rotery / scroll compressor condenser coil, propeller fans controls, control panel, Including control wiring, necessary power cable, M.S. frame duly painted to locate Outdoor Unit etc. The Refrigerant pipe size and gas quantity should suit to the copper pipe length as per actual requirement.

-

-

-

... More
1.0TR, 380 cfm (Approx)

1

-

44594

... More
1.5TR, 480 cfm (Approx)

2

-

51120

... More
Supply, installation, Testing & commissioning of pair of copper refrigerant pipe as per unit tonnage (Soft Pipe) & work insulated with 13 mm thick elastomeric nitrile rubber tubular insulation, complete with  refrigerant topping  for split units

-

-

-

15

-

892

15

-

1207

... More
DRAIN PIPE

-

-

-

... More
Supply, installation, testing and commisisoning of insulated PVC drain water piping with bends reducers tees, supports etc. The insulation shall be with pipe sections of nitrile rubber of 6/9mm thick as per specifications and drawings.

-

-

-

... More
20 mm dia with 6 mm thick insulation

225

-

118

... More
25 mm dia with 6 mm thick insulation

710

-

163

... More
32 mm dia with 6 mm thick insulation

1650

-

211

... More
40 mm dia with 9 mm thick insulation

1325

-

274

... More
STEAM TYPE HUMIDIFIER

-

-

-

... More
Supply, installation, testing and commissioning of steam Type Humidifier package (to be fitted within AHU cahmber or in AHU rooms) of following capacities. (The humidifier shall be interlocked with thermostat of RH sensor ). The unit shall be complete with all necessary electric equipment, like incoming MCCB, contractors, Thermostats etc. as required.

-

-

-

... More
1.5 kg./hr.

5

-

39249

... More
3.0 kg./hr.

1

-

39249

... More
2.0 kg./hr.

2

-

39249

... More
SUBHEAD 'C' VENTILATION EQUIPMENT

-

-

-

... More
Supplying, installting, testing and commissioning of Inline fan for fresh/ exhaust air with centrifugal blower and motor encased in sheet metal casing, as per specifications. The motor shall be suitable for 220 voltage, 1 phase, 50 cycle AC cycle.

-

-

-

... More
800 cfm with 15mmSp

1

-

11123

... More
1100 cfm with 15mmSp

6

-

15065

... More
1400 cfm with 15mmSp

2

-

12407

... More
1800 cfm with 15mmSp

1

-

19900

... More
SUB HEAD 'D' - PIPING WORKS

-

-

-

... More
CHILLED WATER PIPING

-

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, supports, hangers, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elestomeric nitrile rubber of minimum 45 kg/cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive confirming to standard specifications and applied by suitable adhesive confirming to standard specifications and finally applying Glass Cloth (UV protective as and where required ) over the nitrile rubber insulation with chemical coating as per specification and as required complete in all respect. Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.

-

-

-

... More
400mm dia. (32 mm insulation)

60

-

6126

... More
300mm dia.(32 mm insulation)

40

-

2879

... More
200mm dia.(32 mm insulation)

50

-

1928

... More
150mm dia. (32 mm insulation)

10

-

1158

... More
125mm dia.(32 mm insulation)

60

-

978

... More
100mm dia. (32 mm insulation)

1196

-

796

... More
80mm dia. (32 mm insulation)

792

-

521

... More
65mm dia. (32 mm insulation)

192

-

439

... More
50mm dia.(32 mm insulation)

420

-

332

... More
40mm dia. (32 mm insulation)

744

-

223

... More
32mm dia. (19 mm insulation)

864

-

219

... More
25mm dia. (19 mm insulation)

2604

-

170

... More
Supply, installation, testing and commissioning of following valves, strainers, gauges, in the chilled water plumbing duly insulated to the same specification as the connected piping and adequately supported as per specifications.

-

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile rubber sheet & O - ring & PN 16 pressure rating for chilled water/hot water circulation as specified.

-

-

-

... More
200mm dia.

18

-

11870

... More
50mm dia.

4

-

2006

... More
40mm dia.

30

-

1681

... More
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled water / hot water circulation as specified.

-

-

-

... More
200mm dia.

3

-

46490

... More
NON - RETURN VALVE WITH dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.

-

-

-

... More
200mm dia.

6

-

13692

... More
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.

-

-

-

... More
200mm dia.

6

-

26270

... More
50mm dia.

2

-

3177

... More
40mm dia.

15

-

2443

... More
PRESSURE INDEPENDENT BALANCING CUM CONTROL VALVE / HIGH RANGEABILITY CONTROL VALVE

-

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. Valves should have pressure rating of 25 Bar minimum.

-

-

-

... More
50mm dia. - 60 GPM

2

-

38403

... More
40mm dia. - 40 GPM

15

-

37547

... More
32mm dia. - 20 GPM

60

-

13772

... More
25mm dia. - 10 GPM

11

-

10903

... More
Supply, installation, testing & commissioning of BALL VALVE WITH STRAINER complete in all respect.

-

-

-

... More
32mm dia.

64

-

2588

... More
25mm dia.

386

-

1713

... More
Supply, installation, testing & commissioning of BALL VALVE WITHOUT STRAINER complete in all respect.

-

-

-

... More
32mm dia.

64

-

1790

... More
25mm dia.

386

-

1018

... More
TWO WAY VALVES

-

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way On/ OFF valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. . Valves should have pressure rating of 25 Bar minimum.

-

-

-

... More
25mm dia.

386

-

5770

... More
32mm dia.

64

-

8134

... More
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required

200

-

1264

... More
Providing & fixing in position the mercury in glass industrial type thermometres.

178

-

744

... More
Providing and fixing of Auto Air - purge valve of 15mm dia (Air Vent will be fitted with an isolating ball valve ) & complete as per specifications.

91

-

716

... More
CONDENSER WATER PIPE

-

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc..but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.

-

-

-

... More
Note:-The Pipes size 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.

-

-

-

... More
500mm dia.

25

-

8207

... More
200mm dia.

50

-

2172

... More
150mm dia.

40

-

1348

... More
65mm dia.

30

-

502

... More
50mm dia.

40

-

398

... More
40mm dia.

60

-

278

... More
Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.

-

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile rubber sheet & O - ring & PN 16 pressure rating for chilled water/hot water circulation as specified.

-

-

-

... More
200mm dia.

21

-

11531

... More
65mm dia.

3

-

2198

... More
50mm dia.

3

-

1948

... More
NON - RETURN VALVE with dual plate of C I body SS plates PN 16 pressure rating as specified.

-

-

-

... More
200mm dia.

3

-

13301

... More
BALANCING VALVE with built in measuring facility with C I body flanged construction with EPDM Coated disc with long pitch with protded out pipe insulation & PN 16 pressure rating as specified.

-

-

-

... More
200mm dia.

6

-

45161

... More
Y - STRAINER of Ductile CI Body flanged ends stainless steel strainer.

-

-

-

... More
200mm dia.

3

-

25519

... More
Providing and fixing in position of approved make Flow Switch complete with copper control wiring at condenser outlet of each machine.

3

-

1498

... More
SUB-HEAD 'E' - AIR DISTRIBUTION

-

-

-

... More
Supply, installation, balancing and commissioning of site/ factory fabricated at site GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.

-

-

-

... More
24 Gauge ( Thickness 0.63mm)

2950

-

682

... More
22 Gauge (Thickness 0.8mm)

285

-

806

... More
20 Gauge (Thickness 1.0mm)

50

-

950

... More
Supply, installation, testing and commissioning of GI Volume control duct damper complete with neoprene rubber gasket, nuts, bolts, screw linkages, flanges etc., as per specifications.

16

-

5949

... More
Supplying & fixing of powder coated extruded aluminium Supply / Exhaust Air Grills with aluminium volume control dampers as per specifications.

17

-

8428

... More
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.

25

-

4298

... More
Supplying, fixing testing commissioning of Supply Air Diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.

19

-

10285

... More
Supplying, fixing testing commissioning of Return Air Diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.

19

-

6610

... More
Supply, installation, testing and commissioning of Exhaust / Fresh air intake section comprising of powder coated extruded Aluminium louvers with bird screen as required.

19

-

5584

... More
Supply, installation, testing and commissioning of single duct VAV Terminal unit with automatic motorized volume control dampers, sensor, controller & actuator assembly, 24V transformer, ON/OFF switch, hanger along with room cordless thermostat 2 x 1.5 sqmm control wiring & thermostat conduiting complete in all respect.

-

-

-

... More
1750 CFM (Forest Minister at B3- 5th)

1

-

22681

... More
1400 CFM(Chief Parliamentry Scretary at B5- 6th Floor)

1

-

22681

... More
1250 CFM (Finance Minister at B5- 5th & Transport Minister B3-8th Floor)

2

-

19361

... More
1100 CFM(Chief Parliamentry Scretary at B5- 6th Floor)

1

-

19361

... More
SUB-HEAD 'F' - INSULATION

-

-

-

... More
Supply and fixing of acoustic lining of supply air duct and plenum with 15 mm thick open cell Nitrile Rubber (class-1) having density of 180 kg/m³, fire retardent BS 476 Part 7A & 7C. The joint cell be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.

166

-

595

... More
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish, closed cell Nitrile Rubber (Class “O”) insulation on duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.

-

-

-

... More
19mm (on supply air duct)

1245

-

317

... More
13mm (on return air duct)

1850

-

238

... More
SUB HEAD 'G' - ELECTRICAL PANELS

-

-

-

... More
CHILLER PANEL Ics = 50KA

-

-

-

... More
Supply, installation, Testing and Commissioning of dust, damp and vermin proof free floor /wall mounted, Indoor type factory built sheet steel enclosed modular construction(each bay shall be modular and shall be bolted together to form the panel board) extendable compartmentalized cubicle panel board, suitable for operation on 415 ±10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized structural sections and covered with CRCA sheet steel /GI sheet of 2mm thick for framework and covers, 3mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade (or other approved superior process), complete with Aluminium bus bars, inter-connection with copper conductor wires / aluminium strips, neutral links, earth bus etc. including control wiring with 1.5sqmm. & 2.5sqmm. PVC insulated FRLS copper conductor single core cable for voltage & current respectively, cable alleys, cable gland plates in two half etc. necessary metering protections & indications and mounted with the following switch gears etc. complete as required. The panel board shall be IEC- 61439- Part-1 & 2 compliant type tested.

-

-

-

... More
Incomers:- One number1 (1x2500A, 4P EDO ACB)

-

-

-

... More
1 No Incomer of 2500A 4P EDO ACB with microprocessor based over current, short circuit & earth fault release. ACB releases shall have over current different time settings, short ckt. release with variable setting, short time delay, instantaneous current setting, earth fault release, earth fault time delay, 3 Nos. phase indicating lamps to show the incoming power with control MCB, 1 no. ON/OFF/TRIP indication,1 no. digital multifunction meter and matching cast resin CT's. This incomer breaker shall operated from remote push button and necessary arrangements shall be made in ACB.

-

-

-

... More
Bus Bar Section-01

-

-

-

... More
A set of TPN Aluminium bus bar rated for 3000A (after considering all necessary deratings) 3 phase 4wire, 50Hz. A minimum derating factor of 0.8 must be taken for calculation of bus bar sizes. The bus bar size after derating shall be equal to the ampere given in the BOQ. current density of bus-bars shall not be more than 1 Amps/sq.mm for Aluminium and earth bus size shall be suitable of system fault level.

-

-

-

... More
The outgoing feeders are as follows :

-

-

-

... More
Outgoing Section-01

-

-

-

... More
3 No.630 A feeder having one no. 630A TPN EDO ACB with microprocessor based releases for O/C, S/C along with time delay for all protections,1no. ON/OFF/TRIP indications. 1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup protection.and Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH etc. along with current transformers of 630/5A ratio, 15 VA Class 1.0 metering.

-

-

-

... More
3 No. star delta starter feeder suitable for condenser water pumps with DM type MCCB with isolable neutral, 3 nos TP contactor, 1 no timer, 1no over load relay, 1 no ON/OFF indication and other switchgear rating as per type II coordination alongwith 1no. digital ammeter with matching cast resin CT's and 1 no auto manual selector switch.

-

-

-

... More
3 No. star delta starter feeder suitable for primary chilled water pump with DM type MCCB with isolable neutral, 3 nos TP contactor, 1no timer , 1no overload relay, 1 no. ON/OFF indication and other switchgear rating as per type II coordination alongwith 1no. digital ammeter with matching cast resin CT's and 1 no auto manual selector switch.

-

-

-

... More
3 No. star delta starter feeder suitable for secondary chilled water pump with DM type MCCB,1no. ON/OFF/TRIP indications. 1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup protection.and Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH etc. along with current transformers of 125/5A ratio, 15 VA Class 1.0 metering.

-

-

-

... More
6 No. DOL starter feeder suitable for cooling tower motor with DM type MCCB with isolable neutral, 3 nos TP contactor, 1 no timer, 1no over load relay, 1 no ON/OFF indication and other switchgear rating as per type II coordination alongwith 1no. digital ammeter with matching cast resin CT's and 1 no auto manual selector switch.

-

-

-

... More
3 Nos. 125Amps 4P MCCB feeders each having one number 125 Amps 4P MCCB.

-

-

-

... More
1 No. spare 63 A TP MCCB along with S/D starter type feeders.(Space only)

-

-

-

... More
1 No. spare 100 A TP MCB along with S/D starter type feeders.(Space only)

-

-

-

... More
1 set of complete wiring

-

-

-

... More
Necessary electrical Interlocking through advance contacts / contactors in MCCB/ ACB's (Incomers & Bus couplers) should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidentally approaching three supplies at bus sections as per single line diagram enclosed & as required.

-

-

-

... More
CHILLER PANEL as describe above and shown in SLD.

1

-

2501698

... More
SUB HEAD 'H' - ELECTRICAL WIRING Etc

-

-

-

... More
SUB HEAD-H (SUPPLY AND LAYING OF LT CABLE)

-

-

-

... More
Supplying and laying of following 1100 volt grade PVC insulated sheathed copper conductor armoured cables in trenches, on walls clamped to wall with suitable clamps, saddles, and fixing bolts, or laying in ground including cost of digging brick and sand protection, and including jointing / connecting / terminating, testing and commissioning :

-

-

-

... More
3.5 CORES AL. CONDUCTOR

-

-

-

... More
35 sq.mm. Al Ar. XLPE cable

50

-

238

... More
50 sq.mm. Al Ar. XLPE cable

60

-

308

... More
70 sq.mm. Al Ar. XLPE cable

65

-

420

... More
95 sq.mm. Al Ar. XLPE cable

80

-

506

... More
120 sq.mm. Al Ar. XLPE cable

95

-

633

... More
150 sq.mm. Al Ar. XLPE cable

105

-

749

... More
185 sq.mm. Al Ar. XLPE cable

158

-

935

... More
300 sq.mm. Al Ar. XLPE cable

300

-

1442

... More
3 CORES AL. CONDUCTOR

-

-

-

... More
16 sq.mm. Al Ar. XLPE cable

210

-

132

... More
35 sq.mm. Al Ar. XLPE cable

158

-

211

... More
4 CORES Cu. CONDUCTOR

-

-

-

... More
4 sq.mm. Cu Ar. XLPE cable

1122

-

227

... More
6 sq.mm. Cu Ar. XLPE cable

74

-

318

... More
1.5 sq.mm. Cu Ar. XLPE cable

4250

-

120

... More
3 CORES Cu. CONDUCTOR

-

-

-

... More
2.5 sq.mm. Cu Flexible cable

4000

-

135

... More
6 sq.mm. Cu Ar. XLPE cable

50

-

247

... More
STARTERS PANEL

-

-

-

... More
Supplying, assembling, erecting, connecting, testing and commissioning of dust, damp and vermin proof wall mounting factory built sheet steel enclosed non-drawout modular type single starter cubicle fabricated out of suitable sized 1.6mm thick PCRC sheet, duly painted complete with earth studs, numbering & sign writing, interconnection & including copper conductor flexible connection with all accessories, etc. complete & as per specifications and mounted with the followings etc. complete as required. Item including 4core 1.5sq.mm FRLS flexible cable with ON/OFF LED iluminated push buttons in seperate enclosure box to be in recessed manner. (Starters should have NO/ NC contacts for remote/ fire control facility etc. complete as required.)

-

-

-

... More
Fully automatic DOL starter suitable for 0.55 KW motor including suitable size of MPCB as per type-ii cordination chart'and Push Buttons, LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper control/ power wiring etc. Complete as required.

12

-

10835

... More
Fully automatic DOL starter suitable for 0.75 KW motor including suitable size of MPCB as per type-ii cordination chart'and Push Buttons, LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper control/ power wiring etc. Complete as required.

12

-

10835

... More
Fully automatic DOL starter suitable for 1.10 KW motor including suitable size of MPCB as per type-ii cordination chart' and Push Buttons, LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper control/ power wiring etc. Complete as required.

6

-

10933

... More
Fully automatic DOL starter suitable for 1.5 KW motor including suitable size of MPCB as per type-ii cordination chart' and Push Buttons, LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper control/ power wiring etc. Complete as required.

13

-

11654

... More
Fully automatic DOL starter suitable for 2.20 KW motor including suitable size of MPCB as per type-ii cordination chart' and Push Buttons, LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper control/ power wiring etc. Complete as required.

17

-

11654

... More
Fully automatic DOL starter suitable for 3.70 KW motor including suitable size of MPCB as per type-ii cordination chart' and Push Buttons, LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper control/ power wiring etc. Complete as required.

9

-

11770

... More
Fabricating and installation following size of perforated hot dipped G.I. cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting with powder coating etc. as required:-

-

-

-

... More
150 mm. Width x 50mm. Depth x 1.6mm. Thickness.

200

-

379

... More
300 mm. Width x 50mm. Depth x 1.6mm. Thickness.

195

-

613

... More
450 mm. Width x 50mm. Depth x 2.0 mm. thickness.

150

-

998

... More
600 mm. Width x 75mm. Depth x 2.0 mm. thickness.

200

-

1363

... More
900 mm. Width x 75mm. Depth x 2.0 mm. thickness.

50

-

1907

... More
EARTHING

-

-

-

... More
Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal / coke and salt as required.

8

-

13048

... More
Providing and fixing 25 x 5 mm G.I. Strip in 40 mm dia. G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

50

-

285

... More
Providing and fixing 25 x 5 mm G.I. Strip on surface or in recess for connections etc. as required.

850

-

201

... More
Providing and fixing 6 SWG dia. GI wire on surface or in recess for loop earthing along with the existing surface / recessed conduits / submain wiring / cable as required.

100

-

99

... More
Providing and fixing 50 x 6 mm G.I. Strip on cable tray for Hvac panels connections etc. as required.

400

-

285

... More
SUB-HEAD 'I' - OPERATION & MAINTENANCE

-

-

-

... More
During operation and maintenaince period the agency has to deploy minimum 2 no of operators and 3 no helper in liabilities of ESI & EPF to be borne by the contractual agency.

-

-

-

... More
For 1st year (during defect liablity period) @2.5% of capital cost (Part-1) (ONLY OPERATION)

1

-

1553895

... More
During operation and comprehensive maintenaince period the agency has to deploy minimum 2 no of operators and 3 no helper in liabilities of ESI & EPF to be borne by the contractual agency.

-

-

-

... More
For 1st year (after defect liability period) @3.5% of capital cost (Part-1) (Operation + Comprehensive mtc)

1

-

2175453

... More
For 2nd year (after defect liability period) @3.67% of capital cost (Part-1) (Operation + Comprehensive mtc)

1

-

2281118

... More
For 3rd year (after defect liability period) @3.86% of capital cost (Part-1) (Operation + Comprehensive mtc)

1

-

2399214

... More
For 4th year (after defect liability period) @4.05% of capital cost (Part-1) (Operation + Comprehensive mtc)

1

-

2517310

... More
For 5th year (after defect liability period) @4.25% of capital cost (Part-1) (Operation + Comprehensive mtc)

1

-

2641622



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.