Military Engineer Services Tender

... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Provision Of Certain Technical Lab (a) Under Ge(i)(p)(af) Tezpur in Sonitpur, Assam, with an estimated contract value of Rs. 10,64,88,700. The bid opening date for this tender is 14-08-2019 and the last date for bid submission is 20-05-2020. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender

Opening Date14 Aug 2019
Closing Date20 May 2020
Tender Amount₹ 10,64,88,700 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Report Missing Document

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
S & F for 15 mm bore long body bib taps, chromium plated cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe complete all as specified and as directed.

8

-

-

... More
Supply & fixing of ISI marked (IS: 15683) Portable Fire Extinguisher, Trolley mounted Mech Foam type capacity 09 ltrs with gun metal cap and nozzle and complete respects in all respects including initial fill and wall suspension, complete, all as specified and directed.

2

-

-

... More
(a) 400 A, Isc = 30kA for 1 second

10

-

-

... More
Supply & installation of 7200 RPM. Surveillance HDD (Hard Disk Drive) capacity of 6 TB for storing data all as per specified & directed. Make : WD or Equivalent

1

-

-

... More
S & F for MCB SP 6 to 32 Amps (C-Curve), breaking capacity 10 KA, 240 volts with cable connection and copper lugs complete all as specified and directed.

86

-

-

... More
Supply & fixing in position stem mercury in glass filled industrial thermometers (Range 0-70 deg C) with fittings, complete, all as specified and directed.

16

-

-

... More
(b) 300mm width X 50 mm depth X 1.6 mm thickness

4

-

-

... More
SCHEDULE "A" PART- VIII (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
S & F for MCB DP 6 to 32 Amps (C-Curve), breaking capacity 10 KA, 240 volts with cable connection and copper lugs complete all as specified and directed.

6

-

-

... More
Supply, installation, testing & commissioning of DC power supply rectifier 10 KW 10%, 3 Phase, 4 Wire, 50 Hz and output DC 28 V complete all as specified and directed. Make : APLAB/MERLIN/HAWK/AZ Electronics

2

-

-

... More
Item no 10.60 (Contd...) (iv) Digital frequency meter - 01 No (v) Instrument fuses & control wiring (vi) Pilot lamp for 'Load on' and 'Set running' (vii) Incoming & outgoing terminals (viii) AMF control Panel with accessories with control power contactor 800 amps TP, microprocessor based relay & wiring etc - 01 No (ix) Over load protection system with relay - 01 No (x) Electronic type 3 phase muilti function meter - 01 No (E) Accessories: (i) Base frame of sturdy design - 01 No (ii) Fuel tank rectangle shape capacity suitable for running 12 hrs on full load. (iii) Battery 12 V maintenance free with leads & connecting accessoies - 02 Nos (F) Spare parts & tools: (i) Rotary pump diseal with 3 mt hose - 01 set (ii) Box spanner set complete with all sizes (iii) Oil filter set - 02 Nos (iv) Air filter complete with element - 02 Nos (v) Fuel filter set - 02 Nos (vi) AVR - 01 No (vii) Insulated rubber matt of size 900mm x 1500 mm x 3 mm thick - 02 Nos (viii) Jerrican MS sheet capacity 20 ltr - 02 Nos Note : (i) PCC foundation of adequate/required size extending 500mm all round more than size of DG set, as per manufacturer design.

-

-

-

... More
Supply, installation, testing & commissioning of 2 x 75 KVA input voltage 400 ± 15% 400 Volt AC 3 Ph -3 ph 4 wire settable , output THD2% with lenier load, output voltage regulation ± typical load PF range 0.8 to 1.0 UPS shall be equipped with IGBT technology based rectifier and inverter, include protection against overload, short circuit, input low voltage, output over voltage, etc complete all as specified & directed.

1

-

-

... More
Supply & installation of 3 mtr CAT 6 patch Cord all specified & directed. Make: Molex/Comscop/Legrand

15

-

-

... More
Supply & fixing of 3W LED Exit Signs Light, Dual voltage 120/77 VAC input with surge protection. The Luminaire provide solid-state charging system with low voltage disconnect, AC lookout and brownout features. Dual voltage 120/277 VAC input with surge protection. This luminaire should utilize a self contained, maintenance free Ni-Cad battery that will provide a minimum of 90 minutes of illumination. Operating temperature range of 10° C to 40° C (50°F to 104° F), complete, all as specified and directed. MODEL & MAKE: Phillips, Model No. 44R Line Cat No. CE-10400 or equivalent of listed makes

2

-

-

... More
Supply, installation, testing & commissioning of cable termination for cable of 3 Core 6 Sqmm with Al/Copper lugs & flameproof brass compressing glands on both the ends with inhibiting compound etc, complete, all as specified and directed.

16

-

-

... More
Supply & fixing of ISI marked (IS: 15683) Portable Fire Extinguisher, 6.0 Kg ABC type, finished externally with red enamel paint, complete in all respects including initial fill and wall suspension, complete, all as specified and directed.

8

-

-

... More
(a) 400 A, Isc = 30kA for 1 second

10

-

-

... More
Item no 10.60 (Contd...) (xiv) Exhaust pipe / stack from top of shed with insulation structural steel required for supporting exhaust pipe / stack, fixed supports, sliding supports etc. (xv) First fill of lube oil and coolant. (xvi) Residential silencer eith cladding & supports (B) Alternator Alternator conforming to IS-13364 with standard design with IP 23 protection, suitably rated at 400 KVA at 0.8 PF, 415 volts, 3-phase, 4 wires, 50 Hz, 1500 RPM, self excited brushless excavation and self regulated, band of voltage regulation +/- 1.5% of rated voltage ( from no load to full load ) and class "H" insulation, alternator should be mounted on common single base frame and coupled directly to the engine (C) Acoustic Enclouser Acoustic enclose as per norms of central pollution control board (CPCB) issued by ministry of environment & forests, Govt. of india (D) Control panel cum AMF panel: The panel is equipped with as follows:- (i) ACB FP 800 Amp 50 KA manual draw out type - 02 Nos (ii) Digital ammeter with selector switch - 01 No (iii) Digital voltmeter with selector switch - 01 No

-

-

-

... More
S & F and installing on wall or suspension on ceiling , testing and commissioning of following capacity Air Insulated compact type Bus Trucking for use on 3 Phase 4 wire 415 V , 50 Hz A.C supply with metal clad enclosure having IP -54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly power coated in convenient section complete with 4 Nos aluminium bus bars having current density of 130A /Sq cm at nominal current rating , necessary joints elbow joints & expansion joints, fire barrier at each floor , continuous earthing with Nos. aluminium strip of suitable size (one on each side ) including , G.I clamping brackets, suspenders angle iron brackets, steel fasteners, connection to earthing system etc. as required complete all as specified as and as directed.

-

-

-

... More
S & F for GI pipe bracket light grade bracket for street light not less than 1.2 m long 40mm bore, bent to shape as required fixed on wall with suitable size FI clamps, nut, bolts, washer etc including two coats of aluminium paint over a coat of red oxide zinc chrome primer, complete, all as specified and directed.

4

-

-

... More
Supply and fixing of GI volume control dampers for ducts, complete, all as specified and directed.

1

-

-

... More
Supply, Fabricating mounting connecting & Testing front handle operated 630 Amp, 4 pole, on load change Over switch mounted in 2.0mm thick CRCA sheet metal enclosure openable from front & rear both with & incoming & outgoing feeder complete, the grey powder coated enclosure shall be mounted on 60 mm long, 50 mm x 6 mm angle iron frame duly painted with 2 coats of synthetic enamel black paint over a coat of red oxide primer all four legs of angle iron shall be grouted in floor with PCC 1:3:6 type C2 Complete all as specified and as directed.

4

-

-

... More
Supply and fixing of 32mm dia Insulated ball valves, complete, all as specified and directed.

5

-

-

... More
Supply and installation of automatic street lights switch of rating 12 KW in three Phase using nature sensor for automatic switching ON/OFF of street lighting Based on Lux level of nature light along with 63amp three Pole power Contactor MCB 63 amp three pole with support terminal prewired pre wired with PVC insulated 16 Sqmm Multi strand copper wire enclosed / housed in pole wall mounted enclosed made of rust proof, shock proof, termite proof & dust proof FR grade special moulded compound confirming to IP 54 complete at as specified & directed . Model – Swadeep -02EC , 12 KW 3P, make – 1) Nature – Nature Switch , Kakatiya Energy system Pvt ltd / heater / Bajaj . 2) Contractor :- BCH/L& T /Schneider 3) MCB – Hager / Schneider /Legrand 4) Circuit Wiring –Finolex / Polycab for external Area.

1

-

-

... More
Supply, installation, testing & commissioning of Control panel actuator, including electrical, spring type actuator, remote indication of the fire damper position, complete, all as specified and directed.

2

-

-

... More
SPECIAL POWER SUPPLY Supply, installation, testing & commissioning of static frequency converter 5 KVA input 400 V (±) 10%, 3 Phase, 4 Wire, 50 Hz and output 208 V AC phase to phase, 400 Hz 3 Phase 4 wire complete all as specified and directed. Make : APLAB/MERLIN/HAWK/AZ Electronics

1

-

-

... More
Supply, installation, testing & commissioning of 500 Ltr Open expansion tank duly insulated and with all accessories. The Open vessel expansion tank shall be complete with all accessories so as to make it ready for installation and commissioning on site. The tank shall be insulated with the approved method of insulation, and shall be complete with water make up connection & system. The expansion tank will be supplied with Non return Valve and interconnection piping, complete, all as specified and directed.

8

-

-

... More
(c) 630 A, Isc = 50kA for 1 second

3

-

-

... More
(c ) 630 A, Isc = 50kA for 1 second

15

-

-

... More
SCHEDULE "A" PART- X (LIGHTEING PROTECTION) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
Supply & installation of wall mount 12 U Rack with tray, cable manager & PDU (Power Distribution Unit) Make: APW/Valrack/WQ

1

-

-

... More
CENTRAL AIR CONDITIONING Supply, installation, testing & commissioning of vertical inline centrifugal pumps, condenser water pumps, each capable of delivering specified flow rate, complete with bronze impeller, TEFC motor of 415 ± 10% volts, 3 phase, 50 Hz alongwith anti-vibration pads, flexible nylon expansion bellows at both ends for pipe connection, suction guide vanes etc. complete all as specified and directed with the following specification. (a) Capacity : 150 USGPM x 20m head (b) Head: 20m or as required (c) Min Efficiency : 75% Note: Total static pressure given minimum required for the system. Actual static pressure shall be calculated & confirmed by the manufacturer.

3

-

-

... More
SCHEDULE "A" PART-V (HARD STANDING) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
SECURITY SURVILIANCE Supply, installation, testing and commissioning of indoor dome type CCTV camera with Pole/Wall Mount 1 /2.8” Progressive Scan CMOS : H.265, 0 Lux with IR range 15M, 60fps, 2 MP, Min 2.8mm fixed lens; 120 dB WDR; Triple Streams; 3D DNR;BLC;ICR;IP66;IK10;P0E; Built in micro SD; 128 GB; ONVIF Profile S& G Cyber Security; User access log, TLSI.2, AES-256, SSH/Telnet, closed FTP disabled, PCI-DSS compliance, Hardware chipset for private key UL & RoHS certified with video analytic lic Motion Detection, Video Tampering, Face Detection, SD Card error, SD card capacity warning, Audio Detection, Object Abandoned, Object Missing Tripwire, infusion supported. Make: Honeywell/Axis/Mobotix/Avigilon

5

-

-

... More
Item No 10.67 (Contd...) Incoming: a) 160 Amp FP, change over switch, 36 KA - 01 No b) RYB phase LED indication lamps with toggle switches and suitable protection fuses - 03 set c) Digital multimeter with inbuilt selector switch and 160 / 5 Amps suitable VA, CL 1, CTs-1 phase indicating light shall be protected by 2 Amp SP MCB's - 1 Set Busbar 250 amps TPN Aluminium busbar with heat coloured shrinkable insulation sleeve - 01 No Outgoing: a) MCCB FP 100 A 415 V 16 kA - 01 No b) MCCB FP 63 A 415 V 16 kA - 02 Nos c) MCCB FP 25 A 415 V 16 kA - 03 Nos d) MCCB FP 16 A 415 V 10 kA - 01 No Spare 100 Amp FP MCCB 10 KA - 01 No

-

-

-

... More
Supply, installation & laying of CAT-6 STP LAN cable in trenches, in cable racks in trays, in protective pipes, poles, columns in conduits, in panels, in building, walls, ceiling & structure etc. including the supply & installation of all required materials such as per specification drawings & direction of the site engineers including cost of the cable in required length ( 1 Box of CAT 6 Cable 300 RPM) Make : Molex/Comscope/Legrand

3

-

-

... More
S & F for sub main wiring with 2 runs of single core 16 Sqmm (Nominal area) PVC insulated unsheathed multi-stranded copper conductor cable LT 1100 Volts grade (FR-LSH), drawn through in and including concealed non metallic, medium duty, rigid PVC conduit not less than 25 mm dia pipe with accessories including earth continuity conductor using PVC insulated unsheathed copper conductor cable with one run of single core 16 Sqmm (Nominal area) (FR-LSH) connected to common earth dolly complete all as specified and as directed. Notes: 1. 3 runs of 16 sqmm and one run of non metallic, medium duty, rigid PVC conduit not less than 25 mm dia with accessories shall be measured as one run length. 2. Cutting chases, making good disturbed surface shall be included in quoted lump sum of schedule 'A' Part-I and nothing extra shall be paid on this account.

50

-

-

... More
(a) 450mm width X 50 mm depth X 2.0 mm thickness

5

-

-

... More
AREA DRAINAGE M & L for PCC (1:3:6) type C-2, using 40 mm graded stone aggregate as in concrete bed to drain pipe including packing under and completely surrounding pipes with concrete after they are laid and tested for 150 mm bore pipe complete all as specified and directed.

8

-

-

... More
(b) 500 A, Isc = 35kA for 1 second

4

-

-

... More
SCHEDULE "A" PART- XI (FIRE ALARM AND DETECTION) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
Supply and application of 9 mm thick nitrile rubber insulation of density of the nitrile rubber shall be 40-60 Kg per meter cube. The product shall have temperature range of -40 degree C to 105 deg C. The insulation material shall be fire rated for Class 0 as per BS 476 Part 6 : 1989 for fire propagation test and for Class 1 as per BS 476 Part 7, 1987 for surface spread of flame test. Water vapour permeability shall not be less than 0.024 per inch (2.48 x 10-14 kg/m.s Pa i.e Mu7000: Water vapor diffusion resistance), complete, all as specified and directed.

500

-

-

... More
Supply and fixing of MCCB 63A with adjustable thermal & adjustable magnetic settings, rupturing capacity 16 KA, FP, 415 Volts, including all necessary incoming and outgoing electric connections, complete, all as specified and directed.

2

-

-

... More
Supply, installation, testing & commissioning of Insulated three way valve of 65mm dia. with modulating motors and microprocessors based temperature controller suitable for 24 volt supply for AHUs, complete, all as specified and directed.

2

-

-

... More
S & F for 15 mm bore angular stop cock cast copper alloy, chromium plated, screwed down, high pressure with crutch or butterfly handle with long shank and cup, screwed for iron pipe complete all as specified and as directed.

18

-

-

... More
Supply and installing of perforated GI cable tray of size 100 mm Width x 50 mm Depth x 1.6 mm Thickness, GI bends with perforation not more than 17.5% joined with connectors, suspended from the ceiling with suitable suspenders including GI bolts & nuts, painting of suspenders etc., complete, all as specified and directed.

130

-

-

... More
M & L for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised earth wire of size 4 mm dia by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 15 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) including testing complete all as specified and as directed.

8

-

-

... More
Supply and installation with bracket / supports water based fire extinguisher (IS : 15683) of 9 litres capacity suitable for A class of fires with easy snap safety seal, state of art pressure gauge, controllable discharge mechanism, EPDM rubber hose pipe as required, complete, all as specified and directed.

2

-

-

... More
S & F for 100 mm dia High density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 fixed complete to walls, ceilings or in floors etc. complete all as specified and as directed.

50

-

-

... More
S & F, installation, testing & commissioning of following capacity end Feed unit for the existing air Insulated compact type bus trucking / rising mains for use on 3 phase 4 wire 415 V, 50Hz A.C supply made with 1.6mm thick steel sheet enclosure ( IP54) duly powder coasted with provision of MCCB/ACB ( but without MCCB/ACB ) complete with necessary joints including clamping brackets, angle iron bracket , steel fasteners , connecting to earthing system etc as required complete all as specified as and as directed.

-

-

-

... More
Supply and fixing of 80mm dia Insulated check valves, complete, all as specified and directed.

3

-

-

... More
Supply and fixing of 30mm dia PVC pipe for condensate drain duly insulated with kinny foam & vapour barrier duly secured with adhesive tape as per specification, cut to required length and installed with all joints, including the necessary fittings (For all the AHU/FCU units upto the main header in the shaft dor vertical risers), complete, all as specified and directed.

15

-

-

... More
Supply and fixing of butterfly valve of 32mm dia, complete, all as specified and directed.

2

-

-

... More
Supply, installation, testing & commissioning of cable termination for cable of 4 Core 6 Sqmm with Al/Copper lugs & flameproof brass compressing glands on both the ends with inhibiting compound etc, complete, all as specified and directed.

4

-

-

... More
(d) 315 A, Isc = 25kA for 1 second

25

-

-

... More
M & L for earthing complete with copper plate electrode 600 mm x 600 mm x 3 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with copper strip of size 20 x 3mm by means of nuts, bolts, check nuts and washers to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on complete all as specified and as directed.

10

-

-

... More
S & F for street light fitting complete with LM6 dia cost aluminium housing, polycarbonate cover LED Driver having power consumption not more than 72 watt, IP rating IP -66, Lumen output not more than 7000 Im, Lumen efficacy 100 Im/watt , colour colour temperature 5100K, CRI 70, THD )% , PF 0.95, operating voltage 140 -270, 59 Hz complete mounted on & including GI pipe bracket medium grade not less than 1.2 m long 40 mm bore, bent to shape as required fixed on wall with suitable size FI clamps, nut, bolts, washer etc including two cats of aluminium paint over a coat of red oxide zinc chrome primer complete all as specified as and as directed. Make Phillips Cat No. BRP 4 10 LED 72 CW HE MR FG S2 PSU GR ) or equivalent approved makes as per list of make.

4

-

-

... More
15.07 (Contd...\) Outgoings (a) 3 nos, 100 Amp, MCCB, 35 KA with operating handles for Chiller (2W +1S) (b) 3 nos, 32Amp, TP MCB, 10 KA with operating handle with DOL starter, OLP with SPPR etc.)(2 working + 1 standby) for chilled water pumps (c) 3 nos, 32Amp, TP MCB, 10 KA with operating handle with Star delta starter, OLP with SPPR etc.)(2 working + 1 standby) for condenser water pumps (d) 2 nos, 20Amp, TP MCCB, 10 KA with operating handle with DOL starter, OLP with SPPR etc.)(2 working + 0 standby) for cooling towers (e) 2 nos, spare space (f) The base frame shall be 75 mm x 5 mm NOTES: 1. The panel drawing shall be approved before taking up the fabrication and compitable BMS if required. 2. In All panel Each starter should have remote control and interlocking facilities including auto manual switch, NO/NC contacts for control and must have auto manual operation suitable to take signal from fire alarm panel for automatic operation of fan in case of fire. All smoke /vent. fan panel the starters shall have suitable facility to operate with fire sensing control modules.

-

-

-

... More
Supply, installation, testing & commissioning of static frequency converter 45 KVA input 400 V (±) 10%, 3 Phase, 4 Wire, 50 Hz and output 208 V AC phase to phase, 400 Hz 3 Phase 4 wire complete all as specified and directed. Make : APLAB/MERLIN/HAWK/AZ Electronics

2

-

-

... More
S & F for street lights fittings complete with LM6 dia cost aluminium housing , polycarbonate cover LED driver having power consumption not more than 110 watt IP rating IP-66, Lumen output not than 11000Im, lumen efficacy 100 Im / watt colour temperature 5100 K , CRI 70, THD 0% , PF 0.95, operating voltage 140 -270 AC 50Hz complete mounted on & including GI pipe bracket medium grade not less than 1.2 m long 40mm bore, bent to shape as required fixed on wall with suitable size FI clamps, nut, bolts, washer etc including two cats of aluminium paint over a coat of red oxide zinc chrome primer complete all as specified as and as directed. Make; Phillips Cat No BRP410 LED 110 CW HE MR FG S2 PSU GR or equivalent approved makes as per list of make.

4

-

-

... More
Supply & fixing fire buckets (Filled with Dry sand) conforming to IS: 2546 (4 Nos set with stand) round bottom type enamel painted, white inside & red outside and letter “FIRE” in black outside and handle with mounting bracket, complete, all as specified and directed.

2

-

-

... More
M&L for concealed point wiring with two single core PVC insulated, unsheathed, multi stranded copper conductor of size 1.5 sqmm and one single core PVC insulated unsheathed stranded copper conductor of size 1.5 sqmm green in colour as earth lead in and including PVC rigid conduit (medium grade) with all fittings & accessories including provn of MS sunk terminal box of appropriate size suitable for piano switch fixed flush to wall for mounting for 5 pin; 5/6 A socket pin switch sockets etc. with 3 mm thick hylum sheet top cover with screws & cup washers for one SSC point, complete, all as specified and directed. Note : Cost of making good the disturbed surfaces (if any) matching with the existing surface is deemed to be included in the unit quoted rates

2

-

-

... More
Material and labour for Sealing the openings around the sleeve of the fire dampers with approved fire sealant, as per the recommendations of the manufacturer, complete, all as specified and directed.

1

-

-

... More
S & F for cable junction Box of size 165 mm x 125 mm x 82 mm in size made out of Thermoplastic sheet having IP 66 protection with metric knockouts for cable entry for outdoor installation fixed with 4 way Bakelite cable terminals including 03 NOs polymide gland with check nut (M-32-2 Nos) and one no MCB SP 6 amps complete fixed on poles with flat aluminum clamps of required size, nuts, bolts, washers etc cable junction box complete all as specified and as directed.

8

-

-

... More
(c) 630 A, Isc = 50kA for 1 second

6

-

-

... More
M & L for high density polythene film (transperent colour) in single layer of 150 Micron thickness virgin quality as per ASTMD 2103/IS 2508 laid with side and ovelapping not less than 300mm complete all as specified and directed

423.79

-

-

... More
Supply and install, testing & commissioning of Isolation transformer of 100 KVA, output 380 Volt, AC 50 Hz, 3 Phase inter connecting cable, sockets including necessary connections upto required points complete all as specified and directed.

1

-

-

... More
Supply, installation, testing and commissioning of outdoor PTZ dome type CCTV camera with Pole/Wall Mount 1/3” progressive Scan CMOS: 4.5 mm -135 mm, H.265, 0 Lux with IR Range-100M, 60fps, 4MP, 120 dB WDR, triple streams; 3D DNR; BLC; ICR, IP66, PoE; Built in micro SD 128GB, ONVIF Profile S & G, Cyber Security, HTTPS, IP Filter , IEEE 802, 1x, Digest authentication, User access log, UL & RoHS certified with video analytic lic: Motion detection, Face Detection, Auto Tracking supported. Make:Honeywell/Axis/Mobotix/Avigilon

1

-

-

... More
M & L for boring of holes carefully under road / pavement / hard standing by trenches using manual boring or with machines without damaging the existing road and getting out in any type of soil and disposal of soil to a distance not exceeding 50 m from the site of work with and including 100 mm dia GI/HDPE pipe meduim grade, complete, all as specified and directed.

10

-

-

... More
(d) 315 A, Isc = 25kA for 1 second

15

-

-

... More
Supply, installation, testing & commissioning of vertical line centrifugal chilled water pumpsets as per the detailed specification with suitable electric motor for re-circulation of chilled water for central air-conditioning system. The pump motor shall be suitable for 415 ± 10% volts, 50 Hz, 3 Phase power supply. The system shall be complete in all respects including the anti-vibration pads, flexible nylon bellows at both ends for pipe connection, suction guide vanes etc. and suitable for following ratings as per specification. Pump performance characteristics shall be suitable for parallel operation as follows: (a) Capacity : 90 USGPM (b) Head: 25 m for chiller or as required (c) Min Efficiency : 75% Note: Total static pressure given minimum required for the system. Actual static pressure shall be calculated & confirmed by the manufacturer.

3

-

-

... More
SCHEDULE "A" PART- XII (FIRE FIGHTING) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
SCHEDULE "A" PART- IV (INTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
SCHEDULE "A" PART- IX (EXTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
S&F rigid non-metallic PVC conduits 25 mm dia inclusive of junction box & all tees, bends, elbows, reducers, bells, mouth tube ens and fixing accessories such as couplers lock nuts, saddles, pipe, hooks etc. for CAT-6 OFC cabling complete all as specified & directed.

550

-

-

... More
Supply, installation, commissioning and testing of indoor LT panel of size suitable to accommodate mentioned accessories, factory made, (CPRI approved), indoor cubical compartmental type, double door both side openable with hinged doors & locking arrangement made out of 2 mm thick mild steel CRCA sheet supported and fixed on structural frame of angle iron of size 50 mm X 50 mm x 6 mm angle iron frame including earthing stud labeling, painting to all internal & external exposed steel surfaces with powder coating paint (seven stage tank treatment process), duly fixed in ground with PCC foundation (1:2:4) type B1 with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour suitable for 3 phase 4 wire system, 415 V grade with aluminum bus bars of 250 A rating, necessary wiring with PVC sheathed stranded copper conductor of appropriate length size with and including fixing lugs bolts, screws etc complete all as specified and as directed.

1

-

-

... More
S & F for Water heater (Geyser) storage type25 ltr capacity, vertical , thermoplastic body having max EER rating including grouting of stove enamelled fastener by drilling in wall and provn of 02 nos PVC connection pipe of 600 mm long suitable for hot water with brass nut and 02 nos brass chromium plated angular valves suitable for hot water for 15 mm bore pipe of water supply including a 15 amp plug top complete all as specified and as directed.

7

-

-

... More
M & L for construction of brick masonary valve pit of size 90 cm x 90 cm x 90 cm (internal dimensions) with one brick thick wall in cement mortar (1 : 4) on 100 mm thick PCC (1:4:8) D2 (using 40 mm graded broken stone aggregate) as in foundation lean concrete, including PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate) as in beding and coping and 10 mm thick cement plaster in CM (1:4) internally and externally upto 15 cm below ground level providing valve pit 40 mm X 40 mm X 6 mm angle iron frame all round the fixed point by means of 04 Nos holdfast 150 mm long made out of flat iron 40 mm X 6 mm embedded in PCC block (1:2:4) type B1 (using 20 mm graded crushed stone aggregate) of size 250 mm X 200 mm X 150 mm including provision of hinges welded with Mild Steel cover 3 mm thick, MS handle of suitable and size welded with MS cover and suitable locking arrangement including 65 mm dia Godrej pad lock and 3 Nos. key and applying two coats synthetic enamel paint over a coat of red oxide primer on steel surface including necessary excavation and earth work in soft/loose soil complete all as specified and directed.

2

-

-

... More
S & F switch socket combination 5 in 1, 5/6 A complete all as specified & directed.

2

-

-

... More
S & F for 2 x 20 Watt 4 feet long flame proof industrial type CMRI certified LED tube light fitting in aluminium alloy LM 6 with wire guard and reflectors retrofit type, including lamp and electrical connection with 3 core flexible wire of appropriate size from ceiling rose to light fitting complete all as specified and as directed.

42

-

-

... More
(b) 300mm width X 50 mm depth X 1.6 mm thickness

4

-

-

... More
SCHEDULE "A" PART- XIII (CENTRAL AIR CONDITIONING) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
Supply and fixing of 80mm dia. Insulated suction guide or suction diffusers/Flow straighteners or y-strainer, complete, all as specified and directed.

3

-

-

... More
S & F for 18 W LED Tube light fitting surface mounted including LED lamp having input voltage 220- 240 V, natural anodized aluminium housing, output 2100 lm, colour temperature 6500K, built-in driver, including necessary electrical connection with 3 core flexible wire of appropriate size from ceiling rose to the tube light fitting with complete all as specified and as directed. Make: Philips Cat No TMC 501 P1 x T-LED 22W P3241 or equivalent approved make as per list of make

28

-

-

... More
Supply and fixing of suction guide/suction diffusers/Flow straighteners of 100 mm dia., complete, all as specified and directed.

3

-

-

... More
Supply and fixing of interconnecting wiring for the fire alarm system with the AHU and the smoke dampers, complete, all as specified and directed.

1

-

-

... More
All as per Srl Item No.15.07 here-in-before but for AHU with the following incoming and out going:- Incoming: (a) 01 No 63 Amp MCCB (b) Phase indicating lights with control fuses (c) Breaker ON/OFF/TRIP indicating lights (d) Bus bars (e) 80 amp TPN aluminium Bus bar with heat shrinkable insulation colored sleeves Outgoing: (a) 3 nos, 9-14A, TP MPCB (with DOL) starter) incl. 01 No. MPCB spare (b) The base frame shall be 75 mm x 5 mm

1

-

-

... More
Supply, installation, Testing & commissioning of double layer canvas connection with 1 /2 hr fire rating, complete, all as specfied and directed.

10

-

-

... More
Item no 10.60 (Contd...) (ii) DG set shall be tested as type test routine as per IS in presence of GE/his rep. (iii) Contractor shall submit QAP ( quality assurance programme ) after the 15 days from placement of order for DG set testing to factory. DG set shall be dispatch after inspection clearance by inspecting officer. (iv) The contractor shall get approval of GE for the make of DG set they plan to procure (v) Prior manufacturing the general arrangement drawing design details of the DG set and AMF panel shall be got approved by GE

-

-

-

... More
Supply, installation, testing & commissioning of copper conductor, PVC insulated, PVC sheathed armoured cable of 8 Core 1.5 Sqmm of 1.1 KV grade (which is interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU), complete, all as specified and directed.

20

-

-

... More
SCHEDULE "A" PART- II (EARTH WORK) Details of prepriced Schedule is given in tender documents

1

-

-

... More
(c) 150 mm width X 50 mm depth x 1.6 mm thickness

20

-

-

... More
S & F for following size of perforated painted with powder coating M.S cable trays bends with perforation not more than 17.5% joined with connectors, suspenders including bolts & nuts, painting suspenders etc. as required complete all as specified as and as directed.

-

-

-

... More
SCHEDULE "A" PART- VII (SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
Supply, installation, testing & commissioning of motorized Bare fire Dampers with 400 mm sleeve (spring return type) of atleast 120 minutes fire rating. The fire damper shall be complete with electronic temperature sensor and electrically operated actuator. The fire dampers shall be located in the supply/return air ducts, at all fire rated cross overs (shafts/walls) etc. The control panel will be located such that the reset can be easily done. These combination smoke and fire dampers shall be interlocked with the building management system for fire detection /HVAC and shall trip/close in the event of fire/smoke in the respective zone, complete, all as specified and directed.

2

-

-

... More
Supply & installation of 4x4 PVC Junction Box with I/O (Information Outlet) Port all as specified & directed Make : Molex/Comscop/Legrand

6

-

-

... More
Supply, installation, testing & commissioning of standalone access control system with software consisting of the following:- (a) Slender & compact design Brushed Metal Panel. (b) 1.2 GHz quad-core CPU with large capacity memory. (c) High sensitivity optical sensor (d) Advanced fingerprint recognition algorithm, max 150,000 match/sec. (e) Fake finger detection (Rubber, paper, glue, clay) (f) Multi card identification. (g)EM/HID_Prox/Mifare/DesFire_EV1/ Class_SE/ Seos (h) Versatile Interfaces: RS-485/TTL/Relay/Wiegand (i) TCP/IP Network connect (j) Multi-Colour LED, Muti tone Buzzer (k) IP67 Protection Make- Honeywell/Morpho/Tyco

5

-

-

... More
(c) 150mm width X 50 mm depth X 1.6 mm thickness

8

-

-

... More
(b) 500 A, Isc = 35kA for 1 second

8

-

-

... More
S & F for Ventilating fan in powder coated metalic body of size 300 mm sweep,1400 RPM, 230 volt, AC, Air delivery 1850 Cum/Hr, noise level - 40 to 45 db, having double ball bearing with fixing MS louver of suitable size and including necessary electric connection with twin core twisted flexible wire copper conductor cable of suitable size from ceiling rose to ventilating fan complete all as specified and as directed.

14

-

-

... More
SCHEDULE "A" Part - I (BUILDINGS/STRUCTURES) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.5 signifies this fact only.

-

-

-

... More
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised strip of size 32 mm x 6 mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on complete all as specified and as directed.

12

-

-

... More
Construction of Avionics Lab complete all as specified and as shown on drawings.

1

-

-

... More
SEWAGE DISPOSAL Construction of septic tank for 50 users complete all as specified and as shown on drawings.

1

-

-

... More
Supply and fixing of Flexible connection on pipes with guide bolts of 100mm dia., complete, all as specified and directed.

12

-

-

... More
Supply, installation, testing & commissioning of static frequency converter 1 KVA input 400 V (±) 10%, 3 Phase, 4 Wire, 50 Hz and output 36 V AC phase to phase, 400 Hz 3 Phase 4 wire complete all as specified and directed. Make : APLAB/MERLIN/HAWK/AZ Electronics

1

-

-

... More
(a) 450mm width X 50 mm depth X 2.0 mm thickness

2

-

-

... More
Supply, installation, testing & commissioning of extruded aluminium Fresh Air/Exhaust louvers with frame bird screen frame, mounting arrangement etc. complete, all as specified and directed.

1

-

-

... More
Supply and fixing of balancing valve of 100mm dia, complete, all as specified and directed.

5

-

-

... More
S & F for sub main wiring with 2 runs of single core 10 Sqmm (Nominal area) PVC insulated unsheathed multi-stranded copper conductor cable LT 1100 Volts grade (FR-LSH), drawn through in and including concealed non metallic, medium duty, rigid PVC conduit not less than 25 mm dia pipe with accessories including earth continuity conductor using PVC insulated unsheathed copper conductor cable with one run of single core 10 Sqmm (Nominal area) (FR-LSH) connected to common earth dolly complete all as specified and as directed. Notes: 1. 3 runs of 10 sqmm and one run of non metallic, medium duty, rigid PVC conduit not less than 25 mm dia with accessories shall be measured as one run length. 2. Cutting chases, making good disturbed surface shall be included in quoted lump sum of schedule 'A' Part-I and nothing extra shall be paid on this account.

150

-

-

... More
SCHEDULE "A" PART- III (INTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
EXTERNAL WATER SUPPLY M & L for 100mm bore CI sluice valve PN- 1.0, IS 14846-2000 with spindle iron (heavy duty) wheel head and both ends flanged and Mild Steel nut bolts and washers and pair of rubber/fiber gasket fixed in position having body & wedge rings - Bronze IS : 318 Gr. LTB2. spindle :- SS, IS : 6603 Gr. 12Cr12. Gland packing : greasy jute packing. flange drilling - IS 1538, table 4 & 6 complete all as specified and directed.

2

-

-

... More
(a) 450mm width x 50 mm depth x 2.0 mm thickness

35

-

-

... More
S & F, installation , testing & commissioning of following capacity Plug In/ tap off box on the existing air Insulated compact type bus trucking / rising mains for use on 3 phase 4 wire 415 V , 50 Hz A.C supply made with 1.6mm thick sheet enclosure (IP54) duly powder coated with provision of MCCB ( but without MCCB) complete etc as required complete all as specified as and as directed.

-

-

-

... More
Supply, installation, testing & commissioning of Auto air vent with isolating ball valves of 15 mm dia in the chilled water piping, alongwith isolation ball valves, complete, all as specified and directed.

6

-

-

... More
Supply, installation, testing & commissioning of proportional cooling / heating type digital display type thermostat at air-handler unit and fan coil units, complete, all as specified and directed.

2

-

-

... More
S & F for ceiling fan 1200 mm sweep 240 volt AC, including down rod of suitable size, connected with twin core twisted flexible wire copper conductor cable with suitable size from ceiling rose to ceiling fan complete all as specified and as directed.

4

-

-

... More
(c) 315 A, Isc = 25kA for 1 second

5

-

-

... More
Supply and fixing of extruded aluminium duly powder coated return air diffuser without damper, complete, all as specified and directed.

8

-

-

... More
FIRE FIGHTING Supply & fixing of 4.5 Kg Light weight squeeze grip CO2 type fire extinguisher consisting of welded M.S. Cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 30 cm long high pressure discharge hose, discharge nozzle, suspension bracket, confirming to IS: 15683 finished externally with red enamel paint and fixed to wall with brackets with raw/plug/dash fasteners complete with internal charge, complete, all as specified and directed.

8

-

-

... More
Supply and fixing of extruded aluminium duly powder coated supply air diffuser with damper, complete, all as specified and directed.

8

-

-

... More
Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of LT panel for PLANT ROOM fabricated out of 14 guage CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness. All Sub panels with Suitable Capacitor. Incoming: (a) 01 No 250 Amp MCCB (b) 0-500 Volts Voltmeter with SS with control fuses(1 set) (c) 0-200 amp ammeter with SS and 200/5 CT’s (01 set) (d) Phase indicating lights with control fuses (01 set) (e) Breaker ON/OFF/TRIP indicating lights (01 set) (f) KW, Hz and power factor meter (02 set) (g) Bus bars (h) 300 amp TPN aluminium Bus bar with heat shrinkable insulation colored sleeves

1

-

-

... More
Supply and installing of perforated GI cable tray of size 225 mm Width x 50 mm Depth x 1.6 mm Thickness, GI bends with perforation not more than 17.5% joined with connectors, suspended from the ceiling with suitable suspenders including GI bolts & nuts, painting of suspenders etc., complete, all as specified and directed. Note:- For Central Air Conditioning works applicable to Serial item Nos- 14.77 to 15.16 (a) Manning & operation of AC plant in three shifts everyday from date of completion till expiry of defect liability period shall be responsibilty of the contactor. (b) List of essential spares required to repair the plant and maintain the same in 24 hours running condition, shall be supplied by the manufacturer. (c) Contact Nos (landline/mobile) with email-ID & fax No. of representative/manufacturer firn shall be submitted by the contactor in writing before asking for completion of work. (d) Providing all associated civil and foundation work related to HVAC work for the respective items such as 'Foundation' for all equipments in plant room including chillers,pumps, HWG,cooling tower etc as per the manufacturer's instruction duly approved before execution. (e) Cable alley inside the plant room. (f) Cable entry into the plant room,AHU rooms. (g) Braking & making good of walls required for ducts and chilled water pipes (h) PCC blocks for AHUs. (j) Any minor items which are not listed here-in-before but essential for entire completion of work.

30

-

-

... More
Supply, installation, testing and Supply, installation, testing & commissioning of 32” colour LED display monitors for connectivity with PC complete with keyboard & Mouse alongwith interconnecting cable, complete, all as specified and directed. Make: Sony/Dell/Samsung or approval equivalent

1

-

-

... More
(b) 500 A, Isc = 35kA for 1 second

5

-

-

... More
Supply, installation, testing and commissioning of Apex Auto Hand Drier complete all as specified and as directed. Make: Philips / Haier or equivalent approved make as per list of make

4

-

-

... More
(c ) 150mm width X 50 mm depth X 1.6 mm thickness

3

-

-

... More
Construction of Parking Shed for 2 wheelers complete all as specified and as shown on drawings.

1

-

-

... More
Supply and fixing of 80mm dia. Insulated y-strainer, complete, all as specified and directed.

2

-

-

... More
Supply, installing, Testing & Commissioning of Network, Video recording storage system, NVR, 08-Channel, H.265, 12 MP, 4 SATA, 08 PoE inbuilt or external, No HDD, UL & RoHS including viewer Software with necessary licenses to monitor both the connected NVR in a Single client Hardware. Make: Honeywell or equivalent Bosch/Pelco/Axis/Mobotix

1

-

-

... More
DG SET Supply, installation, commissioning and testing of Silent diesel engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS: 10001/10002, ISO - 3046, BS - 5514, DIN - 6271 of capacity 400 KVA, 4 Stroke, designed to run continuously at 1500 RPM complete with the following accessories:- (A) Diesel Engine:- (i) Radiator cooling (ii) Radiator fan with guard (iii) Fly wheel with starter ring (iv) Dry type air cleaner (v) Vacuum indicator (vi) Mechenical governor (vii) Exhaust silencer (viii) Fuel filter (ix) Inline fuel pump (x) Water pump (xi) Lub oil filter (xii) 24 V electric start system complete with starter, battery charging alternator (xiii) Engine control panel consisting of starting key switch, lub oil pressure gauge, ammeter safety shut down system for low lube oil pressure and coolant temperature engine maintenance manual with spare parts list.

2

-

-

... More
EXTERNAL ELECTRIFICATION M & L for employing labour, T& P and hired truck for disconnecting existing HT/LT cable from Transformer 400 KVA capacity earthing strip from body and neutral of transformer lifting complete at installed site after trying it with MS Shilling / chains /Hooks /U – clamps etc and loading on plate form of a hired truck by employing extendable boom type crane and transporting to proposed site carefully and again unloading from hired truck for placing at desired place and reconnecting HT & LT connection at site complete all as specified as and as directed.

1

-

-

... More
Supply & Fixing of Nickel cadmium batteries for 295 Nos 30 minutes back up with all accessories (a) 1.2 Volt, 210 AH sealed Maintenance free batteries model-KPH 210 Make: HBL or equivalent

1

-

-

... More
SCHEDULE "A" PART- VI (AREA DRAINAGE ) Details of prepriced Schedule is given in tender documents.

1

-

-

... More
Supply, installation, Testing & commissioning of Insulation material for Duct Acoustic Lining shall be resin bounded fiberglass wool with one side factory laminated either Black Glass Oven Cloth or Black Glass Tissue. The thermal conductivity of the fiberglass for air-conditioning application shall not exceed 0.034 W/m K at 25 deg C mean temperature and average Noise Reduction Coefficient (NRC=1, frequency range from 100 Hz to 8000Hz). The density of insulation material shall be either 32 Kg/cum and thickness of insulation material shall not be less than 25 mm, complete, all as specified and directed.

40

-

-

... More
SCHEDULE "A" PART -XIV (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES.

-

-

-

... More
(b) 300 mm width X 50 mm depth x 1.6 mm thickness

45

-

-

... More
HARD STANDING M & L for providing and laying 100 mm thick (compacted thickness) Wet Mixed Macadam (WMM), using gradings requirement of aggregate as per Table 400-II of yellow book of MORTH using mechanical paver and rolled with power roller of 8-10 tonne capacity of required camber and gradient complete all as speicified and as directed.

42.38

-

-

... More
FIRE ALARM AND DETECTION M & L for Concealed point wiring with 2 Core x 1.5 Sqmm (nominal area) FRLS PVC insulated and armoured 1100V grade copper conductor cable drawn through and including PVC concealed conduit (medium grade) not less than 20 mm dia with all fittings and accessories including testing on completion complete all as specified and as directed. Notes: 1. Cost of metal flush box and modular cover plate shall be included in the item. 2. Cutting chases, making good disturbed surface shall be included in quoted lump sum of schedule 'A' Part-I and nothing extra shall be paid on this account.

1105.5

-

-

... More
Supply & application of 13-15 mm thick nitrile rubber insulation of density of the nitrile rubber shall be 40-60 Kg per meter cube. The product shall have temperature range of -40 deg C to 105 deg C. The insulation material shall be fine rated for Class 0 as per BS 476 Part 6 : 1989 for fire propagation test and for Class 1 as per BS 476 Part 7, 1987 for surface spread of flame test. Water vapour permeability shall be not less than 0.024 per inch (2.48 x 10-14 Kg/m.s Pa i.e Mu7000: Water vapour diffusion resistance), complete, all as specified and directed.

1400

-

-

... More
S & F for following size of perforated painted with powder coating M.S cable trays with perforation not more than 17.5% in convenient sections, joined with connectors, suspended from the ceiling with M.S suspenders including bolts & nuts, painting suspenders etc. as required complete all as specified as and as directed.

-

-

-

... More
S & F for energy efficient 1X10 W LED Tube light fitting 600 mm long recess mounted including LED lamp having input voltage 220- 240 V, including electrical connection with 3 core flexible wire of appropriate size from ceiling rose to the tube light fitting complete all as specified and as directed. Make: Philips Cat No. BN 021 LED 10S-6500PSU GR S1 or equivalent approved make as per list of make

14

-

-

... More
Supply, installation, testing & commissioning of 1 KVA line interactive sine wave UPS with 40 minutes battery backup with maintenance free sealed UPS including trolley & cabinet complete in all respect power supply access control, CCTV system & NVR/POE switches/moniter all as per specified & directed. Make: APC/MICROTEK

1

-

-

... More
Construction of Parking Shed for 4 wheelers complete all as specified and as shown on drawings.

1

-

-

... More
Supply and fixing of Flexible connection on pipes with guide bolts of 80mm dia., complete, all as specified and directed.

12

-

-

... More
S & F for enery saving high power LED green line light luminaire in pressure die cast LM6 aluminium housing, IP 66 with and unique peanut lens to ensure uniform light distribution including connecting with 3 core flexible wire of appropriate size complete all as specified and as directed. Make: Philips Cat no Green line P type BRP 409 LED 065/064 CW HE MR /NR FG S1 PSU GR or equivalent approved make as per list of make

4

-

-

... More
S & F for SITC of ISI mark (IS :8472) Centrifugal mono block pump set, TEFC permanent split capacitor type (PSC), fitted with thermal overload protection, mechanical seal, 2880/ 3000 RPM, single phase (180 to 240 V ), including cost of hardware etc. on existing platform complete. Pump shall have 5.0 HP, 1-0, (22) Mtr Head, (650) LPM Rating, complete all as specified and as directed.

2

-

-

... More
Supply, installing, Testing & commissioning of power supply unit with 200 watt hour SM battery of 2 x 12 volts for 15 minutes back up, complete in wall mounted. MS cabinet unit for PTZ cameras & PoE switches all as per specified & directed. Make: Meanwell/MICROTEK

1

-

-

... More
(a) 400 A, Isc = 30kA for 1 second

5

-

-

... More
Supply, installation, testing & commissioning of cable termination for cable of 3 Core 35 Sqmm with Al/Copper lugs & flameproof brass compressing glands on both the ends with inhibiting compound etc, complete, all as specified and directed.

6

-

-

... More
Supply and fixing of 80mm dia Insulated balancing valves, complete, all as specified and directed.

5

-

-

... More
Supply and installing of perforated GI cable tray of size 150 mm Width x 50 mm Depth x 1.6 mm Thickness, GI bends with perforation not more than 17.5% joined with connectors, suspended from the ceiling with suitable suspenders including GI bolts & nuts, painting of suspenders etc., complete, all as specified and directed.

30

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.