Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Repair Replacement Maintenance Of Ht 11 Kv Cable Overhead Line Vcb Transformer Painting Of Ht Pole Junction Boxes Replacement Of Unserviceable Ht Poles And Allied Works At Af Station Kumbhirgram Under Age I Af Kumbhirgram 2nd Call in Cachar, Assam, with an estimated contract value of Rs. 29,33,000. The bid opening date for this tender is 30-03-2020 and the last date for bid submission is 06-05-2020. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Costs
EMD
₹ 58,660Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2020_MES_326423_2Tender No
CWE (AF)/KUM/TOKEN-26 OF 2019-20Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
M&L for repairing to Outdoor/Indoor transformer Porcelain insulator for HT bushing of any size complete all as directed.
4
-
-
... More
S & F in repair GI strip 25 x 3 mm fixed with saddles and screws etc and connect with VCB/Tranformer etc. for down conductor above the ground level on wall, complete all as specified and as directed
50
-
-
... More
M&L for Indoor cable end termination joint heat shrinkable type suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable including testing after jointing complete all as specified and as directed.
Make: Densons/Cabseal/3M.
2
-
-
... More
All as per Ser item No 41 above but Square Bar
5
-
-
... More
All as per Ser item No 41 above but Post Insulator
8
-
-
... More
All as per Ser item No 41 above but Flexible Tape
18
-
-
... More
Supply only Digital Frequecy meter of size 144 mm x 144 mm, suitable for HV panel board 11000 V, ranging 40 to 200 Hz complete all as directed.
Make: AE/Siemens/CG/Recom.
1
-
-
... More
All as per item No 21 above but for transformer of capacity 250 KVA to 315 KVA
1
-
-
... More
M&L for PCC (1 : 2 : 4) type B2 (using 40 mm graded crushed stone aggregate) as in foundation for panel, Copping of Steel pole complete all as specified and directed.
8
-
-
... More
All as per Ser item No 41 above but Male - female Contact point
18
-
-
... More
Supplying and Laying Reinforced Precast Concrete Cable Cover, class HVP, type – 1, flat size 300 mm x 180 mm x 40 mm complete all as specified and as directed
2700
-
-
... More
All as per serial item No. 50 above but for using old serviceable ACSR conductors.
1.5
-
-
... More
S&F disc type insulator, Polymer 145 mm height and 255 mm dia ball and socket type white brown or green complete assembly for tension with tension clamps for conductors working pressure 11000 Volts complete all as directed.
Make:JAIPURIA BROS/PACTIL/BHEL/JAYASHREE BARODA/ WS INDUSTRIES
15
-
-
... More
Excavation in trenches not exceeding 1.5 mtr wide and not exc 1.5 m depth and getting out in soft /loose soil complete all as directed.
196
-
-
... More
M&L for transformer gasket for top cover 4mm thick cork sheet complete all as per site requirement complete all as directed.
2
-
-
... More
S&F in repair transformer oil level indicator Glass or fiber type with iron frame, glass, rubber packing sheet, nuts, bolts and washers etc as per existing complete all as directed.
4
-
-
... More
M&L for straight through joints, outdoor, heat shrinkable type (Earthed) suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable with jointing materials and accessories including testing after jointing complete all as specified and as directed. Make: Densons/Cabseal/3M.
2
-
-
... More
M&L for repairing to Outdoor/Indoor transformer for Porcelain insulator for LT bushing of any size complete all as directed.
4
-
-
... More
Supply only Neon indicator lamp LED type with high intensity 40-240 volts AC and 40-220 volts DC with holder in different colour complete all as directed. Make:- Vanishns/AE/Recom/L&T
18
-
-
... More
Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bended galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11/6.35 KV grade suitable for earthed system cross sectional area 120 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole complete all as directed . Make:Havells India Ltd/KEI Industries Ltd/Asian (RPG)/CCI/ Polycab/Finolex/Crystal Cable Industries Ltd/ Ravin Cables Ltd/ Grandlay.
180
-
-
... More
M&L for straight through joints, outdoor, heat shrinkable type (Earthed) suitable for 3 core 120 Sqmm 11000 Volts grade XLPE cable with jointing materials and accessories including testing after jointing complete all as specified and as directed.
Make: Densons/Cabseal/3M.
2
-
-
... More
Supply only vacuum interputer for HT11 KV VCBs, 630 Amps, breaking capacity 13.1 KA suitable for Alstom make VCB complete all as directed. Make :- Bharat Electronics/CG/Areva/Alstom(Areva)
3
-
-
... More
Supply only limit switch 110 volts operated suitable for HT 11 KV VCB charging motor circuit complete all as directed. Make: BCH/Crompton Greaves/STS./KAYCEE
4
-
-
... More
M&L for outdoor cable end termination joint heat shrinkable type suitable for 3 core 120 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing complete all as specified and as directed.
Make: Densons/Cabseal/3M.
2
-
-
... More
Supply & strainging of ACSR conductor on HT over head line including necessary binding work, jumpering, maintaing, proper sag as per IE Rule all complete all as directed.
1.8
-
-
... More
Material and labour for earthing complete with galvanized steel plate electrodes of size 600x600x6mm thick buried directly in ground with earth pit not less than 2.25 meter deep below normal ground level with top edge of plate not less than 1.5 meter below normal ground level connected to galvanized strip of size 32 x 6 mm earth lead by means of nuts bolts check nuts GI washers earth wire protected by galvanized iron pipe 40 mm bore ( light grade) for poles/lightening arrestors/GO Switch/ transformer/panel including connection to HT overhead lines all as directed including concrete pit in PCC (1:3:6) type CI, precast RCC cover slab of size 55x55x15 cm with one handle for lifting made out of 8 mm diameter MS bar finnel wire mesh 20 mm bore galvanized iron pipe (medium grade) for watering charcoal or coke and salt in alternate layers necessary earth work in soft/loose soil complete all as shown in electrical plate No. 3 of SSR Part-I including testing on completion complete all as specified and directed.
6
-
-
... More
M&L for repairing to Outdoor/Indoor transformer LT Brass spindle/Bushing Assembly with 04 Nos nuts, check nuts and washer of dia 16 mm complete all as directed.
2
-
-
... More
SCHEDULE 'A' PART-I (B/R PORTION)
-
-
-
... More
S&F in repair switch air break gang operated triple pole out door type on HT 11 KV 50 cycle AC suitable for current rating upto 200 amps mechanically operated mounted on insulators and frame with operating mechanism worked from ground level with and including locking arrangementcomplete all as directed.
Make PACTIL/NATIONAL/CEC/ECE/JAIPURIA
5
-
-
... More
S&F in repair aluminium bus bar of size 50 mm X 8 mm thick insulated with HT sleeves and provision of making holes as required with GI nuts, bolts & washers suitable for HT 11 KV busbar junction box complete all as directed.
18
-
-
... More
Supply only breaker control switch (Trip/Neutral/Close) 40 Amps 660 Volts AC suitable for HT 11 KV VCB panel as per sample existing in VCB complete all as directed.
Make : Switron/Recom/Kaycee.
2
-
-
... More
Laying only old serviceable HT cable of size 95-120 Sqmm 3 core laid in trenches/duct all necessary fixing arrangements such as lugs, glands and terminals etc complete all as as directed.
170
-
-
... More
S&F in repair Outdoor/Indoor transformer HT bushing assembly with new Brass spindle with 03 Nos nuts, chuck nuts and washer of dia 16 mm without disturbing the other parts complete all as directed
2
-
-
... More
Supply and errect Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11 metres long) on specified location complete all as specified and directed.
2
-
-
... More
S&F 100 mm bore GI tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.
Make: Jindal/Bansal/Prakash/Swastik/Zenith
60
-
-
... More
Dismantling/Taking down of over head ACSR conductor of any size and kept in safe custody for reuse/ removing unserviceabe conductor from site complete all as directed.
-
-
-
... More
Uprooting and cleaning of wild bushes / vegetation around the sub stn building / poles / tranformer platform/feeder pillar boxes etc in (5m x 4m = 20 sq m) complete all as directed
30
-
-
... More
M&L for painting with spray machine to transformer of capacity 250 KVA to 315 KVA with two coats of synthetic enamel paints including surface preparation and painting / marking SM MES No Capacity etc complete all as directed.
2
-
-
... More
All as per Ser item No 41 above but Supporter
6
-
-
... More
All as per serial item No 56 above but for two pole sturcture
6
-
-
... More
Supply and fixing in repair temprature guage ( 0 degree to 120 degree centigrade ) range dial temprature complete all as directed.
4
-
-
... More
Supply only high speed master trip relay (3 element) of operating limits 50 to 120% if rated coil voltage, operational time 10-15ms normal rated voltage, coil rating 24V/30V/110V/220V DC or AC, burden @ 30VDC/24VDC:7VA, 110 VDC : 10 Va, 220 VDC:7 VA, mechanical flag (red to alarm and white for normal) in window HR type operational indicator 3No+1NC contacts, as per IS 3232-1981 including setting of relay and testing complete all as directed. Make : Ashida Type : AVAJH33 or equivalent model of Make Crompton Greaves/Areva/Siemens.
-
-
-
... More
M&L for horizontal boring across the existing road without disturbing the road surface for inserting 100 mm bore GI pipe, complete all as directed.
Note: GI pipe shall be measured and paid for separately under respective item.
40
-
-
... More
M&L for straight through joints, outdoor, heat shrinkable type (Earthed) suitable for 1 core 120 Sqmm 11000 Volts grade XLPE cable with jointing materials and accessories including testing after jointing complete all as specified and as directed. Make: Densons/Cabseal/3M.
3
-
-
... More
Labour only for rewinding of transformer after disconnecting transformer outdoor / indoor type copper wound 11 KV /433 Volt supply system ellectrically both side, earth terminal and taking down carefully from pole / platform mounted on PCC foundation etc and carrying to work shop for repair and rewinding 100 KVA HT & LT coil with super enamelled / paper coated copper wire of existing gauge including all associated insulating material such as separator etc varnishing, heating including dismantling of top cover conservator all internal connection and taking out core with proper care, cutting and removing of burnt coils, cleaning of tank and reinstllation after rewinding work and all arrangement for draining out of transformer oil and refilling after necessary filtration including all internal connection etc of any type / capacity transformer complete all as directed.
Note : (i) Filtration of oil shall be measured and paid separately under respective item.
(ii). Rewinding of transformer should be done in persence of rep of Engr-in-charge
(iii). Rewinding of winding material shall be measured and paid seprately as supply only under respective item.
1
-
-
... More
S&F in repair Silica gel breather assembly unit including Silica gel by providing proper gasket including replacement of corroded pipe connections to breather assembly suitable for transformer of capacity 100 - 315 KVA complete all as directed.
5
-
-
... More
Dehydration, filtration desludging of transformer oil of any type / capacity of transformer at site including all arrangement of tools and plants etc to achieve dielectric strength not less than 40 KV(rms) for 60 Sec with 2.5 mm testing gap complete all as directed.
(Note: All area including Kumpha pump house one 100 kva Tranformer)
3500
-
-
... More
Supply only Digital Volt meter of size 144 mm x 144 mm, suitable for HV panel board 11000 V, ranging 0 to 15 KV (excluding PT) complete all as directed.
Make: AE/Siemens/CG/Recom.
-
-
-
... More
M&L for painting of transformer of capacity 63 KVA upto 200 KVA with two coats of synthetic enamel paints including preparation of surface and painting / marking SM MES No Capacity etc complete all as directed.
(Note: All area including Kumpha pump house one 100 kva Tranformer)
2
-
-
... More
Supply only Numerical protection relay with LCD display for HT 11 KV VCB 4 element (3 Phase + EF) non directional over current IDMT/DMT, instantaneous over current protection with adjustable timer, breaker failure detection,inbuilt CB trip circuit supervision function during pre close and post close of CB, on site CT secondary selection 1A/5A, wide range of power supply input 18V to 250 V AC/DC, 4 digital output contacts for local alarm as trip, 2 dedicated staus input for trip circuit monitoring, 5 Nos of fault data stored with keypad interface and time stamping including setting of relay and testing complete all as directed. Make : Areva Type : F111 or equivalent model of Make Crompton Greaves/Areva/Siemens.
1
-
-
... More
Taking down of existing damged steel/PCC pole with taking down all clamps/brackets/disc/overhead etc and breaking the foundation complete all as directed
2
-
-
... More
Supply only Epoxy resin cost tottaly enclosed dual core type Current transfomer (CT) for protection and measuring of system having ratio of 100/50 : 5 A , Burden-10VA, class-I, insulation level 12/28/75 KV, STC- 18.4 KA for 1 sec as per ISS-2705 and IEC-60044 complete all as directed .
Make: Areva(Alstom)/Crompton Greves/Siemens.
1
-
-
... More
Supply and filling of new transformer oil for toping up / replacement of transformer oil having dielectric strength not less than 40 KV (rms) with gap of 2.5 mm all as conforming to IS 335 of 1993 complete all as directed.
Make: Power/Electrol/Savita
420
-
-
... More
Taking down HT under ground cable of size 95-120 Sqmm 3 core laid in trenches/duct with cable protection complete all as directed.
-
-
-
... More
All as per serial item No. 67 above but exceeding 1.50 metre but not exceeding 3.00 metre in depth.
4.2
-
-
... More
All as per Ser item No 41 above but Rocker CI / GI complete
8
-
-
... More
All as per serial item No 41 above but DO rod made of GI pipe medium grade 20mm dia up to 7 mtr in length with insulated Handle for operating mannualy and locking arrangement .
4
-
-
... More
M&L for sand cushioning with coarse sand in trenches for protection of underground electric cable, spread to uniform 23 cm thickness and punned down gently to 18 cm complete all as directed.
35
-
-
... More
All as per serial item No 56 above but for single pole .
(Note: Including pole from Sonatala pump house to kumbha Pump House)
18
-
-
... More
All as per serial item No 56 above but for four pole sturcture
2
-
-
... More
M&L for loose filling with crushed stone aggregate of Size 40 mm to 80 mm deposited, spread and levelled in layers n.exc 30 cm thick complete all as specified and directed.
20
-
-
... More
Supply only Digital Ammeter CT operated of size 144 mm x 144mm, suitable for HV panel board 11000 V ranging 0 to 100/50 Amp and 60/30 Amps complete all as directed.
Make: AE/Siemens/CG/Recom.
-
-
-
... More
M & L for repairing to Outdoor/Indoor transformer Rubber bush round type of any size complete all as directed.
12
-
-
... More
M&L for preparation of old painted surfaces of steel tubular pole of six pole structure, 11/12 metre height including cross/arms by cleaning old rusted paint by scrapper and applying two coats of aluminium paint over a coat of red oxide primer up to 1.2 mtr height of pole from ground level including marking of pole No with black paint with all arrangement for ladder complete all as directed.
2
-
-
... More
Supply only Hydrographic post insulator suitable for HT 11 KV with both ends with suitable size of bolts for HT busbar junction box complete all as directed.
6
-
-
... More
S&F in repair copper bus bar of size 50 mm X 8 mm thick insulated with HT sleeves and provision of making holes as required with copper nuts, bolts & washers suitable for HT 11 KV VCB panel complete all as directed.
9
-
-
... More
S&F pin type insulator polymer type including one galvanized mild steel spindle, two galvanized iron washer and one galvanized iron nut 150 mm height, 150 dia for 11000 volts grade complete all as directed. Make:JAIPURIA BROS/PACTIL/BHEL/JAYASHREE BARODA/ WS INDUSTRIES
15
-
-
... More
Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and as directed.
96
-
-
... More
S&F cross arms, bracing, support, clamps etc made out of mild steel channel or angle section of required size and shape including clamp, back plate with bolts, nuts & washers drilled for insulator bolts, welding bending cold or hot in any shape or size including all fixing arrangement on HT over head line and painted with two coats of synthetic enemel paint over a coat of red oxide primer complete all as directed.
1.4
-
-
... More
Supply only electric hooter 110 volts operated suitable for HT 11 KV VCB panel in common connection complete all as directed. Make:- Vanishns/AE/Recom/Quatak
-
-
-
... More
M&L for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts & nuts of approved size of HT 25 x 20 cm size complete all as directed. Make : 3M or equivalent
30
-
-
... More
S&F in repair hand set of 11 KV gang operated fitting air break swithches complete all as directed.
4
-
-
... More
M&L for complete repairing/ Serviceing of HT 11 KV, 400 Amp Vaccum circuit breaker (VCB) after disconnecting of all incoming and outgoing connection, checking/finding of the defective spare/parts, removing of all moisture content with suitable grade chemical, replacement of rusted nuts, bolts and washer, replacement of all unserviceable post insulator, HRC fuse, push bottom switch, connector, male/ female contactor, relays, charging spring and repair of all busbar joints and covered with HT insulation tape, painting of all internal surface where required and complete external surface as per existing colour and quality, replacement of all defective internal AC/DC circuit wiring, repair/servicing of breaker trolly including motorized operating mechanism, current transformer / Potential transformer, power pack and calibration of triping relays system and tripping mechanism for regulating the fault flow (Over Current, Earth Fault, Differential) in sequence from down stream for receiving Sub station for accuracy and effective functioning of VCB complete all as directed. (Make of VCB installed: Areva).
Note: (i) Nuts, bolts, washer, painting, cleaning material, insulation tape, copper wire for circuit wiring, male /female contactor (finger),charging spring and other minor items for repair of VCB shall be deemed included in quoted rate.
(ii) Material cost of major unserviceable spares/accessories except mentioned under note (i) shall be measured and paid separately as supply only under respective items.
(iii) During repair work/serviceing work carried out in VCB panel all the existing HT connection/HT cable shall be connected with other VCB for continuous supply to the feeder.
2
-
-
... More
Supply only Ammeter R-Y-B selector switch 5 Amps 440 Volts AC suitable for HT 11 KV VCB panel complete as per exinting in VCB complete all as directed. Make : Switron/Recom/Kaycee
-
-
-
... More
Supply only Heater 230 volts AC 60 watt as per sample for 11 KV HT VCB panel complete all as directed.
Make :Heatco/Vileco Electrical.
2
-
-
... More
S&F in repair HT lightening arrester expulsion type with all fittings discharging capacity 65 KA 11000 volts grade complete all as directed.
Make :- Alstom/Oblum/Crompton Greaves.
5
-
-
... More
Supply only Remote/Local selector switch 16 Amps 250 Volts DC suitable for HT 11 KV VCB panel complete as per existing in VCB complete all as specified and as directed. Make : Switron/Recom. /KAYCEE
-
-
-
... More
Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bended galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11/6.35 KV grade suitable for earthed system cross sectional area 95 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole complete all as directed. Make:Havells India Ltd/KEI Industries Ltd/Asian (RPG)/CCI/ Polycab/Finolex/Crystal Cable Industries Ltd/ Ravin Cables Ltd/ Grandlay
180
-
-
... More
M&L for indoor cable end termination joint heat shrinkable type suitable for 3 core 120 Sqmm 11000 Volts grade XLPE cable including testing after jointing complete all as specified and as directed.
Make: Densons/Cabseal/3M.
2
-
-
... More
Supply only pre insulated Varnished EDPC paper of HT copper winding Coil of transformer 11 KV grade complete all as directed.
180
-
-
... More
M&L for outdoor cable end termination joint heat shrinkable type suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable including testing after jointing complete all as specified and as directed.
Make: Densons/Cabseal/3M.
3
-
-
... More
Supply only Epoxy resin cost tottaly enclosed dual core type Current transfomer (CT) for protection and measuring of system having ratio of 60/30 : 5 A , Burden-10VA, class-I, insulation level 12/28/75 KV, STC- 18.4 KA for 1 sec as per ISS-2705 and IEC-60044 complete all as directed.
Make: Areva(Alstom)/Crompton Greves/Siemens.