Andhra Pradesh Industrial Infrastructure Corporation Tender

To know what Andhra Pradesh government has posted about any AP etender, Bidassist helps us to get a one-stop platform where a registered bidder can have access to the details on each and every eprocurement tender. There is no need to provide the details on the AP E-procurement website i.e. https://www.apeprocurement.gov.in as BidAssist helps us find the specific etender we're looking for. BidAassist has collated each and every Eproc Andhra Pradesh Tender on its website.

Andhra Pradesh Industrial Infrastructure Corporation - APIIC Tender

Works
Civil And Construction
Building Construction
Opening Date18 Jun 2024
Closing Date3 Jul 2024
Tender Amount₹ 46,78,011 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Facade glass cleaning of APIIC building from top to bottom of area around 59180 Sq.ft. including cost and conveyance of all materials like scaffolding to all hieights, cleaning materials, safety measures, all labourcharges etc complete for finished item of work as directed by the Engineer - in - Charge (2times/year)

2

372834

186417

... More
SILICON (SEALANT) Work

-

-

-

... More
Replacement of exisiting elevation structures like ( ACP , HPL clading sheets and structural glazing(Glass Facade) sheets coring silicon sealent, adhesive baker rods, spacer tapes, necessary fixtures and tools ,technical personal and as per technical specifications ,weather sealant ,EPDM etc, complete including scafoliding charges , cost and conveyance of all materials & labour charges etc, complete for finished item of work as directed by engineer –in –charge.

45000

1890000

42

... More
Saniatry Fixtures

-

-

-

... More
Repalcement of Existing Health Faucet with 1m long tube and wall hook of Jaquar Continental series, Chrome Finish including fixtures ,cost and conveyance of all materails charges& labour charges etc complete for finished item of work as directed by the engineer engineer.( For 9th, 10th &11th floors Common Toilets)

45

110842

2463.17

... More
SOIL / WASTE PIPELINGS

-

-

-

... More
Replacement of Exisiting (broken) of PVC/SWR. Single/ Double Socket pipes of 4 kg/sq.cm ISI marked of approved make and fixing as per site requirements and including fixing of M.S. clamps if necessary with required no. of Bombay nails etc., Including all labour charges, all taxes etc,. complete for finished item of work as directed by the Engineer-In- Charge.

-

-

-

... More
A) Supplying and fixing of PVC/SWR 110mm dia Single Socket pipe

280

135142

482.65

... More
B) Supplying and fixing of PVC/SWR 75mm dia Single Socket pipe

280

86889

310.32

... More
C) Supplying and fixing of PVC/SWR 90 mm dia Single Socket pipe

220

90437

411.08

... More
Sanitary Valves

-

-

-

... More
A) Supplying & Fixing of PVC/SWR Plain Bend of 110 mm dia

35

7309

208.84

... More
B) Supplying& Fixing of PVC/SWR Door Bend of 110 mm dia

35

8223

234.97

... More
C) Supplying of PVC/SWR 45 degree Bend of 110 mm dia

35

6792

194.07

... More
D) Supplying & Fixing of PVC/SWR Single Tee of 110 mm dia.

35

8223

234.97

... More
E) Supplying & Fixing of PVC/SWR Single Tee with door of 110 mm dia.

35

9019

257.69

... More
F)Supplying & of PVC/SWR Double Tee of 110 mm dia.

35

12200

348.59

... More
G)Supplying & of PVC/SWR Double Tee with door of 110 mm dia

35

14506

414.48

... More
H)Supplying & of PVC/SWR Single Y of 110 mm dia.

35

9257

264.51

... More
I)Supplying & of PVC/SWR Single Y with door of 110 mm dia.

35

10570

302

... More
J)Supplying & of PVC/SWR Double Y of 110 mm dia.

35

10848

309.96

... More
Applying two coats of Synthetic Plaster Putty or Plaster of Paris Putty or Lime punning of average 1 to 2mm thick over plastered surface to prepare the surface even and smooth after thoroughly brushing the surface to remove all dirt and remains of loose powdered materials, applying emery paper, sand the surface, clean & wipe off loose dust, applying knifing paste filler by putty knife/muslin pad, air dry for 2-3 hours, sand with 180 and 320 No, emery paper for the surface preparation , applying primary superior grade one coat etc, complete including cost and conveyance of all materials to site, sales & other taxes, all operational, incidental and labour charges etc., complete for finished item of work for internal walls and ceiling. ( For APIIC 9th, 10th & 11th Floors Exisiting stari cases & walls)

500

178705

357.41

... More
Painting to new walls with two coats of plastic emulsion paint of approved brand and shade after thoroughly brushing the surface to remove all dirt and remains of loose powdered materials, including cost and conveyance of all materials to work site and all operational, incidental, labour charges etc.complete for finished item of work as per SS 911 for walls and ceiling( For APIIC 9th, 10th & 11th Floors Exisiting stari cases & walls)

500

84880

169.76

... More
ELECTRICAL ITEMS

-

-

-

... More
Providing services for day to day operation and maintenance of electrical installations by engaging One skilled electrician (General Shift) in APIIC Tower including attending all types of routine/preventive maintenance works such as checking /cleaning, tightening of all electrical accessories and switch gears, DBs, AB switch/Isolators, HT/LT breakers, HT/LT panels, feeder pillars, Distribution panels, Distribution boards, switch boards meter rooms and cleaning the same at regular intervals, attending repairs and rectifications, operation of Transformer, DG sets, switchgear, replacement of damaged lights fixtures, MCBs etc including all T & P required but, excluding cost of material if any required. Maintaining record (log books) of readings of sub-meters, voltage, current etc., and maintain statutory maintenance to get CEIG renewal approval and Conducting General Electrical Audit for optimum utilization of energy etc., complete for smooth operation and provide uninterrupted power supply to the building as directed by the Engineer-in-charge, duly utilizing engaged electricians/helpers in APIIC Tower.

12

304716

25393

... More
Supply of the following Modular Switch/Socket mounted on existing GI metallic box and modular front plate as per requirement at site including cost and conveyance charges. [Makes : Legrand (Arteor/Myrius)/MK Blenze]

-

-

-

... More
6/16A Combi Socket

4

764

191

... More
16A Switch

4

492

123

... More
6A Socket

4

556

139

... More
6A Switch

4

364

91

... More
Supply of the following ISI marked FRLS/ FRLS-H / HFFR PVC insulated flexible Copper wires of 1100 V grade as per IS : 694/1990 specification as per requirement at site, including cost and conveyance charges. [Makes: Finolex/Polycab /Havells ]

-

-

-

... More
1.5 Sq.mm

500

10000

20

... More
2.5 Sq.mm

500

16500

33

... More
4.0 Sq.mm

100

5000

50

... More
6.0 Sq.mm

100

7600

76

... More
16 Sq.mm

100

18600

186

... More
Supply of the following Outer dia medium grade rigid PVC Conduit (ISI) with IS: 9537 Part-3 with necessary associated accessories such as PVC bends, Junction Boxes, U nails etc., as per requirement at site including cost, and conveyance charges. [Makes: Sudhakar/Precision/GM/ Polycab/AKG]

-

-

-

... More
20mm outer dia (1.40 -1.55) mm thickness

100

3500

35

... More
25mm outer dia (1.60 -1.80) mm thickness

200

9400

47

... More
32mm outer dia (1.90 - 2.10) mm thickness

50

3700

74

... More
Supply of 12 mm height Casing and Caping (ISI) of the following widths as per requirement at site, including cost and conveyance charges. [Makes: Precision/Modi/Sudhakar/ GM]

-

-

-

... More
19/20 mm

100

3200

32

200

9800

49

50

2850

57

... More
Supply and transportation of the following 1100 V grade XLPE Insulated PVC Sheathed Armoured UG cables conforming to IS:7098 (Part-I) as per requirement at site including cost and conveyance charges [Makes: Polycab/Havells]

-

-

-

... More
16 Sq.mm X 4 core Aluminium Cable

200

46000

230

... More
70 Sq.mm X 3.5 core Aluminium Cable

50

30950

619

... More
10 Sq.mm x 4 core Copper Cable

10

11190

1119

... More
Supply and making end termination with the following heavy duty lug (pin/ring type) as per IS specification, duly crimped with crimping tool, PVC tape etc., for the following cables, including cost, conveyance and labour charges etc., complete. [Makes: Dowells/Jainson/Comet]

-

-

-

... More
Aluminium lug for cables up to 16 sq.mm

32

448

14

... More
Aluminium lug for 70 Sq.mm cable.

32

1312

41

... More
Copper lug for 10 Sq.mm Copper cable.

32

896

28

... More
Supply of the following rating MCB of 10 kA, C/D Curve, ISI Mark conforming to IS: 60898 - 1 : 2002 as per requirement at site. [Makes: Legrand-DX3/Schneider-Acti9/L&T-AU]

-

-

-

... More
63A TP MCB

2

4016

2008

... More
32A DP MCB

2

1572

786

... More
6-32A SP MCB

10

2590

259

... More
Supply and transportation of the following rating LED Driver as per IS 15885 (Part 2 / Sec 13) 2012 with input line voltage 120V-270V AC, 50 Hz with surge protection more than 2.5 kV, IP20, with 2 Years Warranty, as per requirement at site.

-

-

-

... More
12/15/18/20 W suitable for indoor luminaire

5

1845

369

... More
36W suitable for indoor luminaire

5

3100

620

... More
Supply and transportation of 18-20 W, not less than 1100 mm length LED batten light with extruded Aluminium housing and polycarbonate cover, input voltage AC 220 - 260 Volts with PF 0.9, Surge protection: 2 kV, THD 15%, with inbuilt driver and frosted cover CCT: 5700 K, minimum CRI 70, etc., complete with warranty not less than 2 years as per requirement at site. a) LUMINAIRE MAKES : Philips (Signify)/GE-Venture/Crompton/Wipro/Havells; b) LED MAKES : PHILIPS LUMILEDS/CREE/NICHIA /OSRAM/SAMSUNG/Everlight

10

5990

599

... More
TRANSFORMER YARD MAINTENANCE

-

-

-

... More
Testing of Transformer oil for dielectric breakdown strength as per requirement at site.

1

810

810

... More
Filteration of transformer oil as per IS specifications filters to dielectric strength above 40 kV as per requirement at site.

500

7000

14

... More
Supply of new and tested transformer oil as per IS-335 - 1972 (per Ltr) as per requirement at site.

500

81000

162

... More
Labour Charges for Routine maintenance of Transformer, including testing of insulation resistance, oil break down strength. Reconditioning/replacement of silica Gel, cleaning of transformer and topping upto oil level if required (extra cost will be paid for oil).

1

6074

6074

... More
Cleaning and drying the repaired 1600 kVA Transformer with appropriate heat/air as per requirement at site.

1

7424

7424

... More
Carrying out routine maintenance and servicing of LT Cubical Panel board having approximately 15 to 22 Nos. of switches cleaning with power blower and servicing the contacts, tightening the connection of incoming and outgoing cables, and checking the operating mechanism for smooth functioning of switches and putting them in smooth working condition.

4

16196

4049

... More
Preventive and Break down Maintenance of 11kV, 630 A, 26.3 kA HT Vacuum Circuit Breaker of KIRLOSKAR make (Single Panel - Outdoor type) and providing service reports including repairing charges but excluding spares. (Regular Maintenance Contract - One year Service Support)

2

30000

15000

... More
Preventive and Break down Maintenance of the following capacities of ACBs and providing service reports including repairing charges but excluding spares. (Regular Maintenance Contract - One year Service Support)

-

-

-

... More
2500A FP EDO, 50 kA ACB (Panel Mounted) (Existing qnty. : 4 Nos. of Schneider (Masterpact NW25H1) and 1 No. L&T (CN-CS 2500S1))

5

36000

7200

... More
1250A/1000A FP EDO, 50 kA ACB (Panel Mounted) (Existing qnty.: 5 Nos. of 1000 A Schneider (Masterpact NW10H1) and 2 Nos. of 1250 A of L&T (CN-CS 1250S1))

7

50400

7200

... More
Testing charges for 3-Phase Energy Meter, with the Calibrated Power analyzer, Comparing the Meter values and Analyzer, Calculating the % Error, and Test report submission.

23

20700

900

... More
Supply and fixing of Three Phase Electronic energy Meter AC, 50 Hz as per IS 13010 up to 40A range with 200% over load capacity complete with connections etc., complete on the existing board. [Makes: CONZERVE/ELMEASURE/MECO/ HPL/ HAVELLS/L&T]

2

6998

3499

... More
Supply & Transportation of the following dia double walled corrugated HDPE duct made as per specification BSEN - 500 86/IS 14930 Part-II. [Makes: DURA LINE (Dura Guard)/Precision or its equivalent]

-

-

-

... More
Outer dia 50mm and Inner dia 38mm

50

6200

124

... More
Outer dia 63mm and Inner dia 51mm

20

3180

159

... More
Removing the soil around the existing earth pit by excavating the pit to a depth of 0.9 m in soil and filling up the surrounding space around existing pipe with Bentonite powder of 30 kg up to 0.6 m from the bottom and remaining space of the pit with loose earth after isolating earth wire from earth electrode with other safety precautions and cleaning the earth electrode with emery paper, changing the rusted bolts/nuts/Washers/damaged GI Wires/flats, measuring and recording the earth pit resistance parameters, re-fixing electrode, hume pipe ring to original position as directed by the Engineer-in-charge.

6

4296

716

... More
Supply and fixing of Current Transformer up to 150/5 ratio, 5 V, Class 1 accuracy, with all necessary support in existing panel including connection etc., as required

6

3060

510

... More
Supply and laying of the following sizes Earth wire/Strip in horizontal/Vertical run in Ground/surface/ Recess including, riveting, soldering, saddles, making connection etc., as required. (Jointing shall be done by overlapping and with 2 sets of G.I nut bolt & Spring washer spaced at 50 mm)

-

-

-

... More
8 SWG GI wire (0.104 kg/m)

500

5500

11

... More
25mm x 3mm GI Flat (0.656 kg/m)

100

6200

62

... More
8 SWG Copper wire(0.1155 kg/m)

50

5250

105

... More
25mm x 3mm Copper Flat (0.663 kg/m)

100

60100

601

... More
Providing independent earthing by excavating a pit to a depth of 2.10 m with 0.30 m dia in soil using 40 mm dia 'B' class GI pipe as per IS 1239 (ISI mark) of 2.5 m length with tapered casting at the lower end having staggered holes, filling up the surrounding space around the pipe with Bentonite powder of 77 kg up to 1.8 m from the bottom and remaining space of the pit with loose earth and fixing hume pipe ring (3 mm Thick) with necessary accessories and proper connections including cost, conveyance of all materials, and labour charges etc., complete.

3

8067

2689

... More
Providing independent earthing as per IS 3043 with Copper earth plate of size 600 mm (L) x 600 mm (B) x 3.15 mm (Thick) by embodying 3.0 m to 4.0 m below the ground level with 40 mm dia 'B' Class G.I Pipe with staggered holes and tapered bottom by excavating a pit to a depth of 3 to 4 m in all soils for Sophisticated Electronic equipment as per National Electric Code and earth connection from electrode Copper strip of 25 mm x 5 mm of 200 mm length to be bolted with nut bolts to G.I. pipe including 25 mm x 3 mm copper strip of 6.0 m length connected from plate to Copper strip including filling with 20 kg Salt and 40 kg Charcoal in layers of 150 mm height or 40 kg bentonite powder including all accessories like nuts bolts reducer, nipple, wire meshed G.I funnel and CC finished chamber of width: 320 mm, Length: 320 mm, Height: 192 mm, Weight 30 kg and load bearing Capacity: 5000 kg, covered with SMC-Fibre Reinforced Polymer (FRP) 5 Tons capacity manhole cover of size 300 X 300 mm, including cost, conveyance and labour charges etc., complete.

2

41004

20502

... More
No. of BOQ items: 34(Thirty Four) only

-

4678010

-

... More
(Rupees Forty Six lakhs Seventy Eight thousand and Eleven Only)

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.