The SER has issued a formal invitation for competitive bids for the South Eastern Railway project, for Electrical Work For Provision Of Concealed Wiring With Accessories At Different Administrative Buildings And Central Hospital To Implement Fire Safety Recommendation in Kolkata, West Bengal, with an estimated contract value of Rs. 7,88,70,336. The bid opening date for this tender is 05-11-2026 and the last date for bid submission is 03-12-2026. Interested bidders for South Eastern Railway tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

South Eastern Railway - SER Tender - WB Tender

Opening Date5 Nov 2026
Closing Date3 Dec 2026
Tender Amount₹ 7,88,70,336.24 
Notes
Download

Costs

Summary

Electrical Work For Provision Of Concealed Wiring With Accessories At Different Administrative Buildings And Central Hospital To Implement Fire Safety Recommendation

Description

Electrical Work For Provision Of Concealed Wiring With Accessories At Different Administrative Buildings And Central Hospital To Implement Fire Safety Recommendation And Augmentation Of Power Supply Arrangement At Sub Station No 6 And 8 Grc S.e Railway.

AI Insights

Unlock AI Insights for this Tender

Sign in to request AI-powered insights, eligibility criteria and automated analysis for this tender.

Contact

Unlock the Tender details

GEM & Bid Advisory Services

Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

Unlock the Tender details
... More
Laying of 6 sq.mm multi strand FRLS insulated copper wire mentioned at item no 25 , 26 clamped to brick wall, cable tray etc., as required. All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using termination socket and connector.

1000

9

9440

... More
Supply installation including suspension, testing and commissioning of 1600A capacity sandwich bus trunking with aluminum bus bars having minimum current density of 130A 12 per sq cm at nominal current rating in 1.6mm thick GI enclosure, IP 55 protection in convenient section for use on 3 phase [3 phase + 100% Neutral + 100% isolated Earth+ Integral Ground Earth], 415V, 50 Hz AC supply including jointing of section, flexible joints, expansion joints, bends , suspenders, angle iron bracket, Stainless steel Fastners, connecting to earthing etc. as required to complete the work in all respect.

140

30851

4319154

... More
Laying of 25 mm x06 mm GI Flat bar clamped to brick wall, cable tray, etc., as 22 required. All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding

1000

35

35400

... More
Laying of 25mmx06 mm Cu Flat bar , clamped to brick wall, cable tray, etc., as 36 required. All the clamp, Fastners, Screw etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding

200

59

11800

... More
Supply of HT Heat shrinkable type End Termination Outdoor type as per specification IS-13573:2011 or latest suitable for 3 x 120-185 Sq mm XLPE cable 11KV grade.

15

3674

55117.8

... More
Laying of 16 sq.mm Cable (supplied by Railway) ,clamped to brick wall, tray etc., as 28 required. All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using termination socket and connector.

500

11

5900

... More
Supply of 125A,36kA, FP MCCB, 4pole, capacity 125A, with Spreader link for each pole, rated voltage 415V, 50Hz, 3-phase AC, conforming to IS/IEC 60947-1&2, breaking capacity 30KA, insulation voltage 690V AC or higher, capable to withstand 50 degree c ambient temperature, 53 fitted with adjustable thermal magnetic overload release and fixed magnetic short circuit release, impulse withstanding voltage capacity of 8KV or higher, having indication of ON/OFF/Tripped with locking arrangement in OFF position to avoid accidental ON position, maximum overall mechanical dimension of 140mm width. 195mm depth and 184mm height. MCCB shall be from any reputed make such as ABB/ L&T/ Schneider etc.

70

18399

1287981.8

... More
Laying of 8 SWG GI wire , clamped to brick wall, tray etc., as required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding.

400

9

3776

... More
Supply of 18 Way SPN DB with cable end box & Blank plates, wall mounted type, 45 made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 54, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard.

290

9075

2631860.2

... More
Fixing and commissioning of maintenance free Earthing system (Pipe in pipe technology) as mentioned at item no 15.Erection of Maintenance free earthing shall be done by excavation of pit either manual or by machine in any kind of soil, pit making and making of sump 16 box with back fill compound of adequate quantity etc. and construction of RCC Cover for sump box of minimum dimension of 1.5ftx1.5ftx1.5 ft. Cost also includes connection of earth wires/strips between earth pole and main switch/DB/Street light pole/LT /HT panels etc. as per site supervisor's instruction. Cost also includes earth clamp and testing of earth resistance jointly with Railway representative. The earth value shall be printed on the earth sump box. The work shall follow the code of practice as per IS 3043 (1987).

50

3446

172339

... More
Laying of 8 SWG Cu wire , clamped to brick wall, tray etc., as required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding.

400

11

4720

... More
Supply of Shock Treatment Chart with teak wood frame and glass cover [Size minimum 90 cm x 60 cm] as approved by Electrical Inspector/ railway authority.

20

2950

59000

... More
Supply of LT panel Outdoor type (IP-65) , made of CRCA Sheet Steel, powder coated complete with TPN copper busbar with earth terminal, neutral link consisting of Incoming : 1x400A,50kA FP, MCCB, Outgoing: 10x 63A 15kA MCB (FP) (B curve) with suitable Cu. Bus bar, metering-voltmeter, ammeter, energy meter on incoming side and ammeter with selector switch, HRC back up fuse in outgoing side for protective circuit, appropriate spreader link for MCCB.MCCB and MCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025. Before fabrication firm has to submit the requisite drawing of LT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987). LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc.

-

-

8

... More
Erection and fixing of Danger notice plate as mentioned at item no 37 with stainless steel clamps, bolts and nuts of approved size for HT & LT (25 x 20 cm) size as per direction of railway representative.

50

59

2950

... More
Installation and commissioning of 8 way double door Vertical TPN DB as mentioned at item no 43, along with installation of MCCB/MCB as per site requirement and direction of railway authority (MCCB/MCB will be provided from railway store).Its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987).DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority.

-

-

44

... More
Supply Of HT panel consisting of 12KV, 25KA,800Amps Indoor type VCB-01nos 12KV, 25KA, with all other accessories (with power pack up, battery and charger) complete set. Including Ammeter, voltmeter, led indicator, Energy meter,CT ,PT, Protective relay e.t.c with suitable metalic enclosure and complete wiring to complete the job with 1000Amp capacity Cu. Busbar and with interlocking facilities) as per specification no SER/ELEC/GS/ DESCRIPTION / VCB/Indoor/1/2023,Rev.'0' Dec. 2023. . VCB confirms to IS 13118 (1991), IS:IEC-62271-100 / IEC62271-1 & latest, Cu Bus bar conforms to IS:613/latest & 2826/latest. Dressing of wire inside the panel for protection circuit shall be done as per code of IS 732. Before fabrication firm has to submit the requisite drawing of HT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987).

-

-

2

... More
Installation and commissioning of 18 Way SPN DB as mentioned at item no 47, along with installation of MCB, SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning 48 thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority.

10

1007

10077.2

... More
Installation and commissioning of 16 Way SPN DB as mentioned at item no 51, along with installation of MCB, SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning 52 thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority.

10

985

9853

... More
Laying of 12 SWG Cu wire , clamped to brick wall, tray etc., as required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding.

300

11

3540

... More
Supply of 50mmx06mm Cu Flat strip for proper connection of earthing.

-

-

19

... More
Supply of 8 way double door Vertical TPN DB with cable end box & Blank plates , wall mounted type, made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 54, IK 09, confirms to IS 43 8623-1 & 3, IEC 6143-1 & 3 , double door, powder coated complete with TPN copper busbar [having current capacity of 250A] with earth terminal, neutral link and suitable upto 250A MCCB incomer , Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per relevant IS standard.

98

19241

1885625.84

... More
Laying of 40mmx06 mm GI Flat bar strip , clamped to brick wall, cable tray etc., as 24 required . All the clamps, Fastners, Screws etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding

1000

47

47200

... More
Supply ,installation, testing and commissioning of 400A, Isc =50KA for 1 sec, capacity 13 plug in/ tap off box on the existing bus trunking/rising mains for use on 3 phase [3 phase + 100% Neutral + 100% isolated Earth+ Integral Ground Earth], 415V, 50 Hz, AC supply made with 1.6 mm thick sheet steel enclosure (IP 55), duly powder coated with provision of MCCB (but without MCCB) complete as required.

10

17539

175395.2

... More
Supply of 40mmx06 mm GI Flat bar strip for proper connection of earthing.

-

-

23

... More
Supply of 6 sq. mm, Single Core, Multistrand (84/0.3mm), Copper Conductor 25 (flexible), Unsheathed, , Flame Retardant Low Smoke and Halogen(FR-LSH), PVC insulated of 1100V grade, Type C PVC Compound as per IS 5831, Conforming to IS :694 - 2010 (Reaffirmed 2020) with all amendments, ISI marked.

1000

118

118000

... More
Laying of 50 mmx06mm Cu Flat bar , clamped to brick wall, cable tray, etc., as 20 required. All the clamp, Fastners, Screw etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welding

400

106

42480

... More
Supply of 250A,36kA, FP MCCB, 4pole, capacity 250A,with Spreader link for each pole rated voltage, 415V, 50Hz, 3-phase AC, conforming to IS/IEC 60947-1&2, breaking capacity 36KA, insulation voltage 690V AC or higher, capable to withstand 50 degree c ambient temperature, fitted 54 with adjustable thermal magnetic overload release and fixed magnetic short circuit release, impulse withstanding voltage capacity of 8KV or higher, having indication of ON/OFF/Tripped with locking arrangement in OFF position to avoid accidental ON position, maximum overall mechanical dimension of 140mm width. 195mm depth and 184mm height. MCCB shall be from any reputed make such as ABB/ L&T/ Schneider etc.

28

36399

1019184.88

... More
Supply of 25mmx06 mm Cu Flat strip for proper connection of earthing.

-

-

35

... More
Supply of 16 Way SPN DB with cable end box & Blank plates, wall mounted type, 51 made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 67, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard.

10

8877

88771.4

... More
Installation, testing and commissioning of outdoor plinth mounted Transformer, 1000 KVA, 6.6-6kV/415V complete as per IS:1180 (Level 2)/Latest. The scope of work also covers construction of plinth by excavation of soil, preparation of foundation with concrete structure and plastering as per site condition and as advised by Rly. The plinth shall be 0.6-1.2 m height from the ground level. Width and length of the plinth shall be sufficient enough for a person to stand along the transformer for maintenance work. The plinth shall be made up of concrete having grade M 15 or higher. PVC pipe of sufficient dia to be inserted in the plinth for ease of cable entry as per site 01 requirement. Concreate flooring (thickness 8cm minimum) to be developed at surrounding area of plinth with minimum M 15 Grade material. The foundation should be strong enough to carry the heavy load of transformer and it should be efficiently designed to prevent accumulation of water below the platform. Danger board of 60x60 cm of Stainless steel to be provided. The transformer will be supplied by the railway. All the cost of loading, unloading and transportation of transformer from railway store to installation site (at GRC colony both north and south), termination of cable using nut bolts, Bi metallic strips (if required), HT & LT termination kit if required has to be borne by the firm. For testing commissioning the requisite data shall be collected by both firm and railway for EIG approval.

1

58410

58410

... More
Fixing and Commissioning of HT Heat shrinkable type End Termination (as specified at item no 4) Outdoor type as per specification IS-13573:2011 or latest suitable for 3 x 120-185 Sq mm XLPE cable 11KV .

15

225

3380.7

... More
Supply of HT Cable route Markers (stainless steel) for HT cable route marking.

-

-

39

... More
Supply of LT panel Outdoor type (IP-65), made of CRCA Sheet Steel, powder coated complete with TPN copper busbar with earth terminal, neutral link consisting of Incoming : 2x400A,50kA FP MCCB, Bus cuppler - 1x400A,50kA FP MCCB, Outgoing: 16 x 125A,36kA, FP, MCCB with suitable Cu. Bus bar, metering-voltmeter, ammeter, energy meter on incoming side and 10 ammeter with selector switch, HRC back up fuse in outgoing side for protective circuit, appropriate spreader link for MCCB .MCCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025. Before fabrication firm has to submit the requisite drawing of LT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987). LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc.

7

475439

3328077.9

... More
Supply of Danger notice plate of l.6mm thick Stainless steel vitreous enameled white with letters, figures and conventional skull and bones in signal red colour for HT and LT (25 x 20 cm) size. The prior approval of design and content shall be taken from railway authority before supply.

50

590

29500

... More
Installation and commissioning of LT panel Outdoor type (IP-65) (as specified at item no 10) . The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labors required for PCC foundation as per advise of Rly. authority, grouting/installation of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with 11 incoming & outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732.The earthing connection work shall follow the code of practice as per IS 3043 (1987).

7

23771

166397.7

... More
Erection of HT Cable route Markers as mentioned at item no 39 at every 15 mtrs interval on the cable route and also at cable routes turning points on a concrete structure/ foundation.

60

177

10620

... More
Supply of 50mmx10mm GI Flat bar strip for proper connection of earthing.

-

-

17

... More
Installation and commissioning of LT panel Outdoor type (IP-65) (as specified at item no 08). The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labors required for PCC foundation as per advise of Rly. authority, grouting/installation of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with 09 incoming & outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732 .The earthing connection work shall follow the code of practice as per IS 3043 (1987)

3

4535

13607.76

... More
Supply ,installation, testing and commissioning of 1250A, Isc =50KA for 1 sec, capacity end Feed unit on the existing bus trunking/rising mains for use on 3 phase [3 phase + 14 100% Neutral + 100% isolated Earth+ Integral Ground Earth] 415V, 50 Hz, AC supply made with 1.6 mm thick sheet steel enclosure (IP 54), duly powder coated with provision of 1250 A ACB 50KA, Microprocessor Based , MDO type (including supply and installation) complete as required. LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc.

2

375001

750003.28

... More
Fixing and commissioning of LT Panel Outdoor type (IP-65) (as specified at item no 06). The work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labours required for PCC foundation as per advise of Rly. authority, grouting/installation of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with incoming & 07 outgoing cables with necessary termination with cable/wires glands/Lugs/ Bimetalic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732.The earthing connection work shall follow the code of practice as per IS 3043 (1987).

2

76257

152515

... More
Laying of 50 mmx10mm GI Flat bar , clamped to brick wall, cable tray, etc., as 18 required. All the clamp, Fastners, Screw etc to be used for fixation purpose shall be made of stainless steel. All the intermediate joints shall be connected using clamp and nut bolt arrangement or properly welded

1000

35

35400

... More
Installation and commissioning of HT panel consisting of 12KV, 25KA,800Amps Indoor type VCB-01nos 12KV, 25KA, with all other accessories (with power pack up, battery and charger) complete set (as mentioned at item no 2). The cost also includes for making cable ducting and RCC slab to cover the cable trenching as per site requirement. This work includes complete installation over appropriate foundation including supply/arranging all related civil and associated materials including all labours required for PCC foundation as per advise of Rly. authority, grouting/installation 03 of the materials as per site requirement, connections/terminations as per specific site requirement and its connection with incoming & outgoing cables with necessary termination with cable glands and terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc shall be carried out in the presence of railway representative with adequate load(cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire inside the panel for protection circuit shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987).

9

20042

180380.7

... More
Supply of 16 Way SPN DB with cable end box & Blank plates, wall mounted type, 49 made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 54, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard.

290

8877

2574370.6

... More
Installation and commissioning of 16 Way SPN DB as mentioned at item no 49, along 50 with installation of MCB, SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority.

290

985

285737

... More
Supply of 8 SWG GI wire for proper connection of earthing.

-

-

29

... More
Installation of Shock Treatment Chart with teak wood frame and glass cover as mentioned at item no 41 with stainless steel clams/ screws etc as per site requirement.

20

118

2360

... More
Supply of 8 SWG Cu wire for proper connection of earthing.

-

-

31

... More
Supply of 12 SWG Cu wire for proper connection of earthing.

-

-

33

... More
Installation and commissioning of 18 Way SPN DB as mentioned at item no 45, along with installation of MCB,SPD and RCBO as per site requirement and as per direction of railway authority (MCB/RCBO/SPD will be provided from railway store).its connection and installation with incoming & outgoing cables/wires with necessary termination with cable/wires glands/Lugs/ Bimetallic Lugs terminal etc. with proper crimping as per site requirement. After commissioning 46 thermal test, Earthing testing, tripping test etc. shall be carried out in the presence of railway representative with adequate load (cost for that test shall be borne by the contractor) and proper labeling (circuit identification) of the outgoing side and incoming side switchgear shall be done by pasting sticker. Dressing of wire shall be done as per code of IS 732. The earthing connection work shall follow the code of practice as per IS 3043 (1987). DB fixation shall be done by cutting the wall to accommodate the DB wall flushed fixation, plastering & levelling the wall before DB fixation, fixation of DB with GI/SS fasteners, re-filling/re-finishing the wall like original with necessary plastering, painting asper direction of railway authority.

290

1007

292238.8

... More
Supply of 18 Way SPN DB with cable end box & Blank plates, wall mounted type, 47 made of CRCA Sheet Steel [Minimum thickness 1.6mm], IP 67, IK 09, confirms to IS 8623-1 & 3, IEC 6143-1 & 3, double door, powder coated complete with earth terminal, neutral link. Cu Bus bar conforms to IS:613/latest & 2826/latest and all other items as per relevant specifications and as per IS Standard.

10

9075

90753.8

... More
Supply, of LT Panel Outdoor type (IP-65) consisting with 4-pole Draw-out type ACB 1600 A, 50KA, Microprocessor Based , MDO type - 02 Nos as incomer, ACB 1600 A, 50KA, Microprocessor Based , Draw-out type - 01 Nos as bus coupler with , 4-pole 800A 50kA MCCB 02 nos & 4-pole 400A 50 kA MCCB -06nos as outgoing with suitable Cu. Bus bar, metering-voltmeter, ammeter, energy meter on incoming side and ammeter with selector switch, HRC back up fuse in 06 outgoing side and protective circuit & Sheet steel enclosure , appropriate spreader link for MCCB and mechanical/electrical interlocking for ACB with necessary item for seal the cable entry and outgoing point. ACB Conforms to IS/IEC 60947-2 & IEC 60947-2 and MCCB shall be suitable for 415 V, 50 Hz, 3 phase AC supply &, conforms to IS: 13947 (Pt.2)/latest, Cu Bus bar conforms to IS:613/latest & 2826/latest, for HRC fuse as per IS: 13703-2-1 (1993) and as per specification no SER/ELEC/GS/DESCRIPTION/LT PANEL/1/REV-2/JUNE 2025. Before fabrication firm has to submit the requisite drawing of LT panel. The earthing connection work shall follow the code of practice as per IS 3043 (1987). LT switch gear shall be from any reputed make such as ABB/ L&T/ Schneider etc.

-

-

4



Evaluation Notes How It Works ?

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.