Central Building Research Institute Tender
View complete overview of Uttarakhand CBRI Tender
Central Building Research Institute - CBRI Tender
Metals and Non-Metals
Eprocure
Opening Date31 Aug 2021
Closing Date9 Sep 2021
Tender Amount₹ 48,16,751 This is an estimated amount, exact amount may vary.
Costs
EMD
Refer DocumentsDocument Cost
₹ 590Tender Fee
Refer Documents
Summary
Construction Of U Value Apparatus For Full Scale Building Component Testing
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_CSIR_86605_1Bid Award Id
ViewTender No
193(572) EST/2021-22Tender Authority
Central Building Research Institute ViewPurchaser Address
-Website
http://https://www.csir.res.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Providing skilled manpower for shifting of various items, furneture,old testing models and materials from construction site to specified space in the institute as per direction of Engineer-in-charge
12
-
-
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
14
-
-
Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead :Of area 3 sq. metres and below
8
-
-
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar
24
-
-
Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50metres lead
200
-
-
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge
2
-
-
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
45
-
-
Providing Tractor trolly for shifting of malba, debrise, soil, various old testing models and materials from construction site to outside of institute and out site area of nagar nigum Roorkee including loading unloading complete work in all respect as per direction of Engineer-in-charge.
4
-
-
Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq. meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete, including disposal of rubbish to the dumping ground within 50 metres lead :
28
-
-
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m All kinds of soil.
37
-
-
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
17
-
-
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
22
-
-
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
16
-
-
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.
14
-
-
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete.40 mm thick with 20 mm nominal size stone aggregate
95
-
-
Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick
164
-
-
Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).Light shade pigment using white cement
18
-
-
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand)
12
-
-
Brick work in superstructure of class designation 75 in Cement mortar 1:6 (1 Cement : 1 coarse sand).
29
-
-
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size)
8
-
-
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement :
3
-
-
Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse
sand(zone-III) : 3 graded stone aggregate 20 mm nominal size).
15
-
-
Centering and shuttering including strutting, propping etc. and removal of form for :
-
-
-
Foundations, footings, bases of columns, etc. for mass concrete
22
-
-
Suspended floors, roofs, landings, balconies and access platform
66
-
-
Lintels, beams, plinth beams, girders, bressumers and cantilevers
72
-
-
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Cold twisted bars
3062
-
-
Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete :100x10
88
-
-
Providing and fixing special quality bright finished brass cupboard or ward robe locks with four levers of approved quality including necessary screws etc. complete.50 mm
44
-
-
Providing and fixing bright finished brass handles with screws etc. complete:100 mm
88
-
-
Providing and fixing magnetic catcher of approved quality in cupboard /ward robe shutters, including fixing with necessary screws etc. complete.Double strip (horizontal type)
44
-
-
Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
2
-
-
Providing and fixing aluminium hanging floor door stopper, ISI marked,anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper.
2
-
-
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete
2
-
-
6 mm thick cement plaster on ceiling with cement mortar 1:3 (1 cement: 3 fine sand).
38
-
-
12 mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand.
55
-
-
15 mm thick cement plaster rough side brick work 1:6 cement mortar(1cement :6 coarse sand) .
37
-
-
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface :
193
-
-
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
193
-
-
Grinding and polishing of existing floor including labour T&P material complete in all respect at site asper direction of engineer-in-charge.
42
-
-
Providing insulation inside doors with interlocking precoated PUF panel having GI sheet on both sides with 150mm thick, PUF insulation denstiy :38kg/cum, PUF thermal conductivity : 0.035W/m/K at 30 deg.C mean temperature, Facing material: Powder coated GI sheet, Facing Material thickness : 0.6mm, including complete in all respect at site as per direction of Engineer-in-charge.
16
-
-
Providing insulation inside walls, floors, and roofs with interlocking precoated PUF panel having GI sheet on both sides with 150mm thick, PUF insulation denstiy :38kg/cum, PUF thermal conductivity : 0.035W/m/K at 30 deg.C mean temperature, Facing material: Powder coated GI sheet, Facing Material thickness : 0.6mm, including complete in all respect at site as per direction of Engineer-in-charge.
647
-
-
Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size)
4
-
-
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.110 mm diameter
120
-
-
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete.110 mm
12
-
-
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
31
-
-
Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
250
-
-
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade:New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
193
-
-
Wiring for light Point /fan point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/recessed steel conduit with modular switch of Havells Modular /Legrand MOSAIC / Anchore ROMA/ Make or its equivelent make ,ISI marked, modular plate suitable G.I Box and earthing the point with 1.5 sq mm FRLS PVC insulated multi strand copper conductor single core cable of Polycab/Havell’s /KEI Cables /RR Kable/Finolex make or its equivelent make I.S.I. marked 1100 volts grade as required for Group ‘C’Point including ceiling rose or lamp holder as required
24
-
-
Wiring for circuit /sub-main wiring along with earthwire the following size of FRLS PVC Insulated multi standard copper conductor single core cable of Polycab/Havell’s /KEI Cables /RR Kable/Finolex make or its equivelent make I.S.I marked 1100Volts grade in surface/ recessed steel conduit as required
-
-
-
2 x 1.5 sqmm + 1 x 2.5 sqmm earth wire
100
-
-
2 x 2.5 sqmm + 1 x 2.5 sqmm earth wire
100
-
-
2 x 4 sqmm + 1 x 4 sqmm earth wire
180
-
-
2 x 6 sq.mm + 1 x 6 sq mm earth wire
20
-
-
4 x 6 sq.mm + 2 x 6 sq mm earth wire
10
-
-
S/F 4 module GI box of size 125 x 75 mm along with modular base and cover plate for modular switches in recess etc as required.complete in all respect.
1
-
-
Supply and fixing 5/6 Amps Modular type switch on the existing Modular plate & switch box including connections but excluding modular plate etc. as required complete in all respect.
4
-
-
Supplying and fixing 3 pin 5 amp. ceiling rose on the existing junction box /wooden block including connection etc as required
4
-
-
Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required.
10
-
-
Supply and fixing suitable size G.I Box with modular plate and cover in front on surface/recessed including P/F 5 pin 5/6 Amps modular socket outlet and 5/6Amps modular switch of Havells Modular /Legrand MOSAIC / Anchore ROMA/ Make or its equivelent make,ISI marked, connections painting etc as required
12
-
-
Supply and fixing suitable size G.I Box with modular plate and cover in front on surface/recessed including P/F 6 pin 15/16 Amps and 5/6 Amps modular socket outlet and 15/16Amps modular switch of Havells Modular /Legrand MOSAIC / Anchore ROMA/ Makeor its equivelent make ,ISI marked, connections painting etc as required
12
-
-
Supply and fixing 20 amps 240 Volts SPN industrial type socket outlet with two pole and earth metal enclosed plug top along with 20 Amps ‘C’ Cueve, SP, MCB, in sheet steel enclosure, on surface or in recesses with chained metal cover for the socket outlet complete with connection, testing, commissioning etc. as required of Havells / Legrand /L&T/ Sciemense Make or its equivelent make .
1
-
-
Supply and fixing 30 amps 415 Volts TPN industrial type socket outlet with four pole and earth metal enclosed plug top along with 32 Amps ‘C’ curve, TPMCB in sheet steel enclosure on surface or in recesses with chained metal cover for the socket outlet complete with connection, testing, commissioning etc. as required of. Havells / Legrand /L&T/ Sciemense/ABB Make or its equivelent make.
1
-
-
Supply and Fixing 8Way double door surface/recess mounting vertical type 415 volts,TPN, MCB distribution board of sheet steel,dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bars, common neutral link, earthbar, dinbar for mounting MCB’s (But without MCBs and incomer MCCB)of Havells make model load line or its equivalent of Legrand/ABB /L&T/ Sciemense Make or its equivelent make including painting earthing etc. as required.
1
-
-
Providing and fixing 100 amps 16 KA rating and breaking capacity three pole MCCB in existing cubical panel board including drilling holes in cubical panel making connection etc. including testing and commissioning. as required of Legrand/ Havells /L&T/ Sciemense Make or its equivelent make .
1
-
-
Supply and fixing 5amps-to- 32 amps rating 240/415 Volts C Curve miniature circuit Breaker suitable for inductive loads of Single Pole in the existing MCB DB complete with connections, testing and commissioning etc as required of Legrand/ Havells /L&T/ Sciemense Make or its equivelent make .
24
-
-
Earthing with G.I. earth plate 600mm x 600mm x 6 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc with charcoal / coke and salt complete as required.
2
-
-
Supply and laying 25mmx5mm G.I strip at 0.50 meter below ground as strip earth electode,incluidinng connection/terminating with G.I.Nut,bolt,spring,washer etc. as required.
60
-
-
Providing and Laying 6 SWG G.I. wire at 0.5 m below ground level for conductor earth electrode including connection ter mination with G.I. thimble etc. as required.
110
-
-
Laying of one number PVC insulated and PVC sheathed/ XLPE aluminium conductor power cable of 1.1 KV grade of size Above 35 sq.mm and Up to95 sq.mm in the existing RCC/HUME/ METAL/ DWC HDPE pipe etc. as required.
40
-
-
Laying of one number PVC insulated and PVC sheathed/ XLPE aluminium conductor power cable of 1.1 KV grade of size Above 185 sq.mm andUp to400 sq.mm in the existing RCC/HUME/ METAL/ DWC HDPE pipe etc. as required.
50
-
-
Supplying and laying of 90 mm dia (OD-90 mm & ID-76 mm nominal) size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
90
-
-
Supplying and making indoor end termination with brass compression gland and aluminium lugs for 3.5 x 70 sq.mm(38 mm )size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
2
-
-
Supplying and making indoor end termination with brass compression gland and aluminium lugs for 3.5 x 240 sq.mm(62 mm )size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4
-
-
Supplying & Fixing of 32 mm diax2.00 meters long G.I. pipe(medium class) bracket for mounting of street light fitting on wall including bending the pipe to the required shape,40mmx3mm flate iron clamp and wiring with1.5 sq.mm wp/pvc wire and painting the flate iron with primer and finish paint etc. as required
4
-
-
Taking out carefully old electric point wiring, sub-main, switch board, Power Points and electrical fitting & fixture including all other old electrical items taken under renovation area complete in all respect and shifting of old materials as required.
1
-
-
Supply and fixing 1400 mm sweep double ball bearing type heavy duty ceiling fan of Havells make model velocity/velocity HS or equivelent of cinni/ crompton make complete in all respect as required and directed by the Engineer –in-charge.
1
-
-
Supply and fixing factory wired Havells make STOUT PLUS LED Light battens 0f 40 watt including suitable size M.S.Patti cat.no. STOUTPLUS1200BS40WLED840(or 857)SPCWH or its equivalent make of Bajaj/Phillips make complete in all respect as required.
12
-
-
Supply for laying, including testing connecting etc. in the existing trench/ surface/ wall PVC insulated and PVC sheathes XLPE armoured heavy duty 1100 volts grade Gems Cab /Havell’s/Poly Cab/KEI make ISI marked,Heavy Duty, aluminium conductor electric cable as per latest I.S.Spesification, including connection testing etc complete in all respect as required of size
3.5corex70 sq.mm
40
-
-
Supply for laying including testing,connecting etc. in existing trench/ surface/ wall PVC insulated and PVC sheathes XLPE armoured heavy duty 1100 volts grade Gems Cab /Havell’s/Poly Cab/KEI make or its equivelent make ISI marked,Heavy Duty, aluminium conductor electric cable as per latest I.S.Spesification, including connection testing etc complete in all respect as required and directed by engineer Incharge of size
3.5corex240 sq.mm
50
-
-
S/F LED Street Light fixture of new generation energy saving and environmental friendly long life LED Street Light made up of pressure die cast aluminium housing with high power LEDas lighting source and lens embedded PC cover having TOP OPENING seprate driver compartment with ,IP66 protection and impact resistance of IK07 with 10 KV Built-in Surge protection Device of Havells make 90 Watt 230 volts odering code ENDURAPEARLPLUSSL90WLED757SASYTOPC or its equivalent make of Bajaj/ Phillips make complete as required
4
-
-
Supplying installation, testing commissioning, of Indoor type totally enclosed floor mounted Panel board of 600 mm deep having fully compartmentalizedFactoryfabricated from 2mm thick CRCA sheet steelwith base frame mounted on cement concrete foundation/ MS Angle iron frame of size 50mmx50mmx5mm thick, ,including making of suitable size cable trench for installation of cubical type LT Panel board of size 2200mmx1800mmx600mm suitable for 415 V,3phase, 4wire 50Hz AC Supply system,3mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade having extensible type a TPN aluminium Alloy bus bar of high conductivity, DMC/SMC bus bar supports fabrication shall be done in transportable section entire panel shall have a common aluminium earth bar of size 25mm x 5mm at the rear with 02 Nos. earth stud ,solid connections from main bus bar to switch gear with required size of AL.bus bars ,gland plates including indicating lamps on incoming etc.The instruments chamber shall be separate and shall comprise of flush type ammeter, voltmeter selector switches for ammeter and voltmeter instruments SP MCB etc in two half i/c providing following switch gears (I)Incomings:(1) 02 Nos.-400 Amps 4 pole MCCB for fault breaking capacity 35KA.
(2)01Nos.400 Amps 4 Pole on load Change Over Switch
(II)Bus Bars:TPN aluminium bus bars of minimum of 600Amps capacity 4 strip “with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section side supports (III)Outgoings:2. (1)02 Nos. 200 Amps 4 pole MCCB 25KA
3. (2)02 Nos. 100 Amps 4 pole MCCB 16KA
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements