Rajasthan Renewable Energy Corporation Limited Tender

... More
The RRECL has issued a formal invitation for competitive bids for the Rajasthan Renewable Energy Corporation Limited project, for Construction Of Power Evacuation System For Development Of 2450 Mw Solar Park At Pugal, Bikaner in Bikaner, Rajasthan, with an estimated contract value of Rs. 4,27,34,00,000. The bid opening date for this tender is 09-04-2025 and the last date for bid submission is 04-06-2025. Interested bidders for Rajasthan Renewable Energy Corporation Limited tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Rajasthan Renewable Energy Corporation Limited - RRECL Tender

Works
Civil And Construction
Energy, Oil and Gas
Electrical and Electronics
Solar Installation and Products
Consultancy Services
Civil And Architectural Services
Eprocure
Opening Date9 Apr 2025
Closing Date4 Jun 2025
Tender Amount₹ 4,27,34,00,000 
Notes
Download

AI Insights

Work Experience Requirements
... View More
The bidder is required to have prior work experience in the following areas: 1. Civil Works: Experience of Civil Works for at least 1 No. 400 kV or above voltage class Substations or at least 02 Nos. of 220kV or above voltage class substations, including Equipment and Structure foundations, Transformer/reactor foundation, Trenches, Control Room, etc. in the last five years, with successful completion of these civil works for at least 6 months prior to the date of bid opening. 2. Erection, Testing, and Commissioning: Experience of erection, testing, and commissioning of at least 1 No. 400 kV or above voltage class bays or at least 02 No. 220 kV or above voltage class bays, including Structures, Transformer, Equipments, C&R Panel erection, and Cable laying & terminations, etc. in the last five years, with successful completion of these works for at least 6 months prior to the date of bid opening. 3. Transmission Line related works: Experience of civil works related to transmission line tower foundations, of 220kV or above towers, etc., and experience of erection, testing, and commissioning of at least 1 KM of 220kV or above voltage class transmission line. The value and percentage of similar works completed are not explicitly mentioned, except that sub-vendors for major items/equipments/elements costing more than 5% of the overall cost of supplies quoted for the project should be proposed by the bidder. A monetary value is mentioned for the bid security, which is 2% of the estimated procurement cost of the respective LOT(s) in which the Bidder participates.
Class Of Bidder
... View More
Micro, Small or Medium enterprise

Costs

  • EMD

    ₹ 8,54,68,000
  • Document Cost

    ₹ 29,500
  • Tender Fee

    ₹ 2,950

Summary

Construction Of Power Evacuation System For Development Of 2450 Mw Solar Park At Pugal, Bikaner

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply. erection, testing & commissioning of Ethernet Switch, Gateway, Firewall, OFC, BCU, IEDs etc. to complete the scope specification .

1

-

-

... More
50 V, SMPS battery charger of 100 Amp. DC Load capacity suitable for charging of VRLA battery set alongwith additional one No. 25 SMPS Module.

2

-

-

... More
145 kV 2000 Amp., 40 kA triple pole, gang operated horizontal double break type motor operated, outdoor Isolator metallic without earth blade complete with accessories including terminal connectors and post insulators.

12

-

-

... More
Wave Trap

-

-

-

... More
Current Transformer

-

-

-

... More
145 kV single phase 4400 pF CVT suitable for high frequency (HF) coupling required for power line communication with voltage ratio 132/0.11 kV, 0.2 Class and three secondary windings with terminal connector.

24

-

-

... More
AIR-CONDITIONING AND VENTILATION SYSTEM FOLLOWING

-

-

-

... More
Marshalling Kiosk For 400 Kv and 132kV

1

-

-

... More
33 KV 3 phase H G Fuse set with support structure

2

-

-

... More
Hydrant System

1

-

-

... More
TESTING AND MEASURING EQUIPMENTS as per Annex.

1

-

-

... More
HTLS conductor

1

-

-

... More
LT SWITCHGEAR

-

-

-

... More
125 MVAr, 420 kV, 3 phase, 50 Hz, Bus Reactor including insulating oil, atmoseal conservator, bushing CTs, self dehydreated breather, all other fittings and accessories as per technical specification.

1

-

-

... More
Capacitive Voltage Transformer

-

-

-

... More
48 V, 600 AH VRLA Battery set along with accessories and stand.

2

-

-

... More
GENERAL TOOLS & TACKLES as per Annex.

1

-

-

... More
315 MVA, 400/132/33 kV Auto Transformer

-

-

-

... More
2000-1000/1-1-1 Amp., 40kA,145 kV single phase multi core current transformers with120% extended current rating (Live Tank Type only) with terminal connector.

117

-

-

... More
33/.433 kV, 500 kVA, LT three phase station transformer

-

-

-

... More
145 kV 2000 Amp., 40 kA triple pole, gang operated horizontal double break type motor operated, outdoor Isolator metallic with double earth blade complete with accessories including terminal connectors and post insulators.

24

-

-

... More
XLPE Cable for 33kV Station Transformer as per requriment

1

-

-

... More
IllUMINATION SYSTEM :

-

-

-

... More
Furniture for Control Room building as per Annex.

1

-

-

... More
AC DISTRIBUTION BOARD (For triple source as per IS)

1

-

-

... More
Complete substation automation system along with necessary license, grid security, redundancy provision and spares for 5 years satisfactory operation as per scope of the specification.

1

-

-

... More
Desktop Computer, Laser Printer and photocopy machine with latest configuration as per Annex.

1

-

-

... More
Copper Control Cable as per requriment

1

-

-

... More
400 KV Bus Bar Protection Scheme having one no. central unit and 16 nos. peripheral units (PU)

1

-

-

... More
145 kV 2000 Amp., 40 kA triple pole, gang operated Horizontal Double break type, motor operated, outdoor, Isolator metallic fitted with single earth blade complete with accessories including terminal connectors and post insulators.

22

-

-

... More
145 kV,2000 Amp., 40 kA rupturing capacity circuit Breaker with mounting structures, foundation bolts and nuts, Terminal Connectors and first filling of SF6 gas plus 20% spare gas including accessories and auxiliaries.

17

-

-

... More
420 kV 3150 Amp.,63kA triple pole, gang operated Horizontal Double break type, motor operated, outdoor, Isolator metallic fitted with single earth blade complete with accessories including terminal connectors and post insulators. Required capacity of isolators to be as per SLD and scope of work.

12

-

-

... More
Potential Transformer

-

-

-

... More
GPS with Digital clock

1

-

-

... More
COMMUNICATION AND CARRIER PROTECTION EQUIPMENTS

-

-

-

... More
DG SET Diesel Generator set of stationary type having a net electrical out put of 160KVA capacity at specified site conditions with all its accessories for installation at 400 kV substation

1

-

-

... More
AAC Tarantulla conductor

1

-

-

... More
Add: Any other supply item, if any, bidder may require completing the substation as per specification requirements. (if amount quoted, list of items alongwith quantity be indicated in technical **Note :- BOQ shown above is for tender purpose only. It shall be finalized at the time of detail engineering by bidder as per the specification / requirement. offer)

1

-

-

... More
Design, supply, installation, testing and commissioning of Air conditioning & ventilation system for the control room building for Control Room, PLCC Room, SE/XEN/AEN/Staff/Rest Rooms alongwith the necessary spares for satisfactory operation for 5 (five) years.

1

-

-

... More
420 kV 3150 Amp. , 63kA triple pole, gang operated horizontal double break type motor operated, outdoor Isolator metallic with double earth blade complete with accessories including terminal connectors and post insulators.

19

-

-

... More
ACSR Moose conductor

1

-

-

... More
Fibre Optic Telecummunication equipments with associated accessories

1

-

-

... More
HAND APPLIANCES as per Annex

1

-

-

... More
420 kV single phase 4400 pF CVT suitable for high frequency (HF) coupling required for power line communication with voltage ratio 400/0.11 kV, 0.2 Class and three secondary windings with terminal connector.

6

-

-

... More
132 kV, 0.2 mH / 2500 A Wave Traps Pedestal mounting type with tuning unit, protection device, terminals clamps, corona rings, bird barriers etc.

8

-

-

... More
420 kV,3150 Amp., 63 kA rupturing capacity circuit Breaker with closing resistor suitable for single and three phase rapid auto reclosing complete with mounting structures, foundation bolts and nuts, Terminal Connectors and first filling of SF6 gas plus 20% spare gas including accessories and auxiliaries.

12

-

-

... More
FRLS Cables as per requriment

1

-

-

... More
Cables along with accessories as per requriment

-

-

-

... More
Switchyard Flood Lighting

1

-

-

... More
PLCC equipments with associated accessories

1

-

-

... More
DC DISTRIBUTION BOARD **Note:- ACDB & DCDB should be designed in such a manner so that each AC and DC feeder have duplicate connectivity.

1

-

-

... More
Non-Standard Pipe Support Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for Pipe Support structure as per specification requirements] **Note:- (1)The above estimated quantities of structures are only for tender purpose. The contractor shall supply, erect & commission the structures to meet out complete requirement for successful commissioning , maintenance & operation of the substation in accordance with the specification. (2) Details of Tower structures & girders / beams available in Vol.II, of specification are tentative and for tender purpose only. The bidder shall have to design the structures & girders / beams based on actual loadings on the basis of short circuit force calculations, if required.

1

-

-

... More
Non-Standard Lattice Structure [Design, engineering, procurement of materials, fabrication galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure as per specification requirements]:

1

-

-

... More
EARTHING MATERIAL (GS & MS flats of all sizes and Cu/Al Flexible braids)

1

-

-

... More
Power Cables as per requriment

1

-

-

... More
420 kV 3150 Amp. , 63kA triple pole, gang operated horizontal double break type motor operated, outdoor Isolator metallic without earth blade complete with accessories including terminal connectors and post insulators.

4

-

-

... More
Phasor Measurement Unit with accessories

1

-

-

... More
FIRE FIGHTING SYSTEM ( AS PER TECHNICAL SPECIFICATION)

-

-

-

... More
CONTROL ROOM BUILDING AND STREET LIGHTING

1

-

-

... More
GS Earth wire

1

-

-

... More
BATTERY AND BATTERY CHARGER

-

-

-

... More
STRUCTURES : Design, engineering, procurement of materials, fabrication galvaising, proto- assembly, FOR destination delivery & erection including nuts, bolts, gusset plates, base plates, foundation bolts, fixing arrangement for control cabinets/MB of equipments and other accessories for lattice steel structure. Conforming to IS:2062 and GI pipe conforming to grade YST 22 or higher grade as per IS:806.

-

-

-

... More
315 MVA, 400/132/33 kV, 3 phase, 50 Hz, auto transformer including insulating oil, ON LOAD TAP CHANGER, Digital RTCC Panel, atmoseal conservator, bushing CTs, self dehydreated breather, Optical Temprature Sensors including measuring Units alongwith all associated accessories/ Fittings as per specifications, one set of four Nos. Hydraulic jacks.

4

-

-

... More
SUBSTATION AUTOMATION SYSTEM

-

-

-

... More
CONTROL, RELAY & PROTECTION PANELS COMPATIABLE WITH SUBSTATION AUTOMATION SYSTEM ALONG WITH ASSOCIATED EQUIPMENTS.

1

-

-

... More
420 kV single phase PT with voltage ratio 400/0.11 kV, 0.2 Class with two secondary windings with terminal connector.

12

-

-

... More
Standard Lattice Structure [Design, engineering, procurement of materials, fabrication, galvaising, proto-assembly, FOR destination delivery & erection including nuts, bolts, washer, gusset plates, base plates, foundation bolts and other accessories for lattice steel structure as per specification requirements]:

1

-

-

... More
33/.433 kV, 500 kVA, LT three phase station transformer complete with all fittings, accessories and associated equipment as per specification.

2

-

-

... More
220V, 100Amp/70Amp float cum boost Battery Charger (Separate sections for float and boost charging operation).

2

-

-

... More
125 MVAr 420 KV Bus Reactor

-

-

-

... More
Isolator

-

-

-

... More
Circuit Breakers

-

-

-

... More
Single pole voltage -coordinated, outdoor station class heavy duty current limiting type 390 kV lightning arresters suitable for connection between phase and ground on 3 phase 420 kV neutral grounded system complete with insulating base, surge counter and current meter, accessories.

21

-

-

... More
HARDWARE AND BUS BAR MATERIAL

1

-

-

... More
Single pole voltage -coordinated, outdoor station class heavy duty current limiting type 120 kV lightning arresters suitable for connection between phase and ground on 3 phase 132 kV neutral grounded system complete with insulating base, surge counter and current meter, accessories.

36

-

-

... More
Surge Arresters

-

-

-

... More
OFFICE & MISCELLANEOUS EQUIPMENTS / ITEMS

-

-

-

... More
Mulsifyre System

1

-

-

... More
FIRE DETECTION AND ALARM SYSTEM

1

-

-

... More
145 kV single phase PT with voltage ratio 132/0.11 kV, 0.2 Class with two secondary windings with terminal connector.

42

-

-

... More
2000-1000/1-1-1-1-1 Amp., 63kA,420 kV single phase multi core current transformers with120% extended current rating (Live Tank Type only) with terminal connector.

72

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.