Baba Farid University Of Health Sciences Tender

... More
The BFUHS has issued a formal invitation for competitive bids for the Baba Farid University Of Health Sciences project, for Providing And Installing Copper Pipes For Medical Gases System In Super Speciality Block in Faridkot, Punjab, with an estimated contract value of Rs. 1,86,97,470. The bid opening date for this tender is 20-02-2025 and the last date for bid submission is 28-02-2025. Interested bidders for Baba Farid University Of Health Sciences tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Baba Farid University Of Health Sciences - BFUHS Tender

Works
Healthcare and Medicine
Eprocure
Opening Date20 Feb 2025
Closing Date28 Feb 2025
Tender Amount₹ 1,86,97,470 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

  • EMD

    ₹ 3,98,000
  • Document Cost

    ₹ 5,900
  • Tender Fee

    ₹ 5,900

Summary

Providing And Installing Copper Pipes For Medical Gases System In Super Speciality Block

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Providing and Installing copper pipes for Medical Gases System in Super Speciality Block
Providing and Installing copper pipes for Medical Gases System in Super Speciality Block
Financial bid for providing and Installing copper pipes for Medical Gases System in Super Speciality Block
Report Missing Document

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply & erection of 54mm isolation ball valve with brass fitting BS:EN 13348 medical grade with proper fitting complete in all respect.

15

-

121500

... More
Supply, Installation, testing and commissioning of Medical four Gas Alarm Panel system with separate LED indicator for each gas.4 GAS Services (O2, Air-4Bar, Vac) complete in all respect.

3

-

108000

... More
Supply & erection of Bacteria Filter sutable for 684mm (HB)(MAX.) complete in all respect. 1. Borosilicate filter element 99.995% efficiency 2. l Compliant with MEMORANDUM 2022HEALTH TECHNICALl 3. Lightweight, corrosion-protected aluminium bodyl 4. Differential pressure gauge indicator for filterelement replacementl5. Sterilisable drain flask to capture biological fluidsl 6. l Vacuum flow rates from 850-7504 litres/min(30-265 scfm) 7. Available in 1” pipe connection

1

-

318600

... More
Supply & erection of 42 mm isolation ball valve with brass fitting BS:EN 13348 medical grade with proper fitting complete in all respect.

15

-

94500

... More
Supply & erection of copper pipe with required fitting BS:EN 13348 medical grade 22mm outer dia, 0.9 mm thick copper pipe able to handle minimum 6.00 kg pressure with paint as per standard norms including bend, Elbow, tee etc .

990

-

980100

... More
Add Civil Work item as per CSR 2020

1

-

1000000

... More
Supply & erection of copper pipe with required fitting BS:EN 13348 medical grade 28mm outer dia, 0.9 mm thick copper pipe able to handle minimum 6.00 kg pressure with paint as per standard norms including bend, Elbow, tee etc .

2350

-

2961000

... More
Supply & erection of copper pipe with required fitting BS:EN 13348 medical grade 12 mm outer dia, 0.7 mm thick copper pipe able to handle minimum 6.00 kg pressure with paint as per standard norms including bend, Elbow, tee etc .

510

-

257040

... More
Supply & erection of Air Regulator With Bypass: automatic pressure reducing air regulator made out of cast iron aluminum body having pressure range 0-10 bar along with 2 inch dial pressure gauge would be provided to regulate the air pressure coming from the system of capacity 3500 LPM along with all ball valve, NRV, ball brackets etc. Technical specification range 0-3500 LPM pressure 4 bar test pressure 15 bar gauge range 0-3500 LPM pressure 4 bar test pressure 15 bar guage 2 inch dial connection 28mm (along with bypass arrangement ) Make:- Janatics/Festo/Techno

2

-

70800

... More
Providing & installing of two stage Air Outlet indian point with parking & holding the gas pressure proper fitting DIN Standard

72

-

174960

... More
Medical Vacuum Base unit DUPLEX Medical Vacuum Base unit Supply & erection of vacuum system is installed by providing 2 nos. vacuum pump of reputed make of single stage ,2/3 cylinders. This pump is stationary, air-cooled; splash lubricated, Base Plate mounted reciprocating type.This pump Should fitted on cHANNEL and belts Should be guarded. The company also provide 1 no. vaccum tank of suitable water capacity as per IS 225 and construction code as per IS 2825 with all its accessories like vacuum gauge, drain valve, etc. The company shall provide interconnected copper piping of size 12mm 0.0 to 28mm OD with BSP vertical non return valve of required size with vacuum gauge of required size of bottom connection with silencer and vacuums Bacteria filters and all other work to complete the vacuum system and as per the entire satisfaction of Hospitals authority. The capacity of the pump Should be about 45 cfm per minute vacuum at 684mm (HG). Makes: - AIRTECH/ ANESTHIWATA/ INGERSOLL RAND TECHNICAL SPECIFICATION : VACCUM PUMP : (2 NOS.)1. No. Of Cylinders 2. Lubrication Splash 3. Vacuum/ Suction 149 cfm 4. Vacuum 684mm (HB)(MAX.) 5. Driver Electric Motor 6. Performance test International Standard 7. Stages 1 8. Mounting Base Plate Mounted 9. Cooling Air-cooled 10. Vacuum speed 600 RPM ELECTRIC MOTOR : 1. Capacity 10 H.P 2. Rounds per minute 1440 3. Volts 415 4. Phase 3 5. Electric Supply 50 Hz. 6. Performance test International Standard 7. Starter Star Delta direct on line 8.Insulation Class F VACCUM RECEIVER :1. Construction IS 2825 2. Capacity 2000 ltr (Approx.) 3. Foundation Skid 4. Blast Cap. 300psi 5. Fittings Pressure Gauge ,Safety Valve , Drain trap Inspection Window

1

-

1817200

... More
ELECTRICAL CONTROL PANEL Supply & erection of electrical control panel suitable for medical Vacuum Pumps shall be suitable for the selected duplex system and will be fabricated to be a combined control panel. The combined electrical control panel will be provided complete with mains indicating lights, single phasing preventer, phase loss/ phase reversal indicating lights, individual MCBS for all starters, individual ammerters for all motors, contractors, overload relays, control circuti MCB , start/stop push buttons, auto/maunal switches relays with overriding feature. Technical specification : 1 . Main MCCB 160 amp 2. Spreader 160 amp 3. Bus bar 200amp 4. Relay 220 volts 5. MCCB three pole 100 6. Contractor 70 amp 7. Volt meter digital 8. Amp meter digital 9. C/t 150/5 10. Selector SW 11. Relay 24 volt 12. enclosure 1000x850x250 or above Make:- Schneider/L&T/ABB

1

-

318600

... More
Supply & erection of An automatic twin chamber heatless air dryer with bypass capacity 150cfm would also be installed to dry compressed air 90 -psi pressure at a temperature of 0-40 degree centigrade. The dryer would be automatic dully fitted with pneumatic operated valve, set of filters, pre-filters, oil filter and duly fitted with pressure gauges for test the filters condiiton. The in fill material in each tower would b the mixture of silica gel/activated alumina etc. for best performance. At a tie first chamber would be online and second chamber would be under regeneration process and vice-versa for continous dry air. This action can be achieved with the help of micro processed based control panel, Air drier:- Drying conditions, flow rate 150 CFM , pressure 60 psi, temperature 40 degree max, moisture contents 100% Rh, Dew point -40 degree. Make:- Trident/ATS/ Summits/Airtech

1

-

413000

... More
Supply & erection of illuminate the oil trases from air stream comint out from air reciever, a twin chamber coal tower with bypass facility would be install. the coal tower would be of capacity 500 CFM, inlet outlet connection would be 42 mm with automatic drain valve and in fill of activated carbon at a working pressure of 4 bar with test pressure of 16 bar duly painted with 2 coats of enamel paint. this unit would have inlet outlet ball valve with brass NRV. TECHNICAL SPECIFICATION: Capacity 500 CFM tower twin size 42mm drainage automatic working pressure 4 bar test. Make:- Multitech/Airtech

1

-

224200

... More
Supply & erection of Vacuum Filter sutable for 684mm (HB)(MAX.) complete in all respect. Medical Vacuum Filters - High Performance Series are designed to remove the liquid, solid andbacterial contamination from the suction side of the vacuum pump and the potential biological infection of the surroundingenvironment with low pressure drop. The filter elements and housings are designed for medical use and can be utilizedin hospitals, pharmaceutical laboratories, dentist’s surgery and other critical areas.Installed on suction side of vacuum pump to remove bacteria and prevent contamination to the pump and atmosphere.Biological liquids are collected in a transparent drain flask, which can be easily removed for sterilization. The flask shouldbe visually checked daily and removed for cleaning and sterilization. The filter element must be replaced at least every6 months or when the pressure drop reaches 100 mbar, towards the end of the red zone of the differential pressureindicator.The efficiency of the installed filter elements exceeds the 0.005% penetration specified in HTM 2022 for infectious diseaseunits, when tested in accordance with BS 3928.

1

-

967600

... More
Providing & installing of humidifier bottle with regulator with probes complete in all respect.

156

-

238680

... More
Supply & erection of copper pipe with required fitting BS:EN 13348 medical grade 15 mm outer dia, 0.9 mm thick copper pipe able to handle minimum 6.00 kg pressure with paint as per standard norms including bend, Elbow, tee etc .

1020

-

706860

... More
Providing & fixing 4' long Bed head panel made of power coated Aluminium Sheet 2 mm thick with inbuilt railing to accommodate iv pole, infusion pump, utility basket, examination lamp, ward vacuum unit & monitor tray including electrical socket as per specification.

30

-

324000

... More
Supply & erection of copper pipe with required fitting BS:EN 13348 medical grade 42mm outer dia, 1.2 mm thick copper pipe able to handle minimum 6.00 kg pressure with paint as per standard norms including bend, Elbow, tee etc .

485

-

1222200

... More
Providing & installing of two stage Suction Outlet indian point with parking & holding the gas pressure proper fitting DIN Standard

156

-

379080

... More
Providing & installing of 600ml suction jar with regulator KNOB with flexible pipe with probes complete in all respect.

156

-

351000

... More
Supply & erection of Interconnecting Copper Pipe (From Air Compressor to Air Tank):- copper tube of soiled drawn seamless deoxidized, non arsenical, half hard, tempered and degreased as per BSEN 13348:2001 duly supported with manufacture test certificate for physical properties and chemical composition. Make:- Maxflow/Mandev/Janya

1

-

70800

... More
Supply & erection of 15 mm isolation ball valve with brass fitting BS:EN 13348 medical grade with proper fitting complete in all respect.

210

-

321300

... More
Providing & installing of two stage Oxygen Outlet indian point with parking & holding the gas pressure proper fitting with probes Ventilator DIN Standard

156

-

379080

... More
compressed air system Supply & erection of The compressed air system are installed by installation of 02 number oil-cooled, splash lubricated and skid mounted screw type compressor. Capacity to produce 3600 liters approximately free air delivery at maximum pressure of 90 PSI. It would be fitted with 22 KW capacity induction electric motor of class F insulation It will be pre fitted with slide rails. The compressor would be installed duly fitted with suction filters, after coolers with moisture separator. The moisture separator and after coolers duly fitted with electrically operated auto drain traps will also be provided before air receiver. This whole unit would be covered by MS Steel powder coated canopy. It's is silent in nature.The whole compressed air unit is controlled by an electronic micro processed based digital PLC for the smooth operation of compressor, this PLC would total running hour, service alarms, fault. This system would also be fitted with bypass airline, safety valve for pressure indicators. 2 nos air compressor, screw type, lubrication splash lubricated , air delivery 3600 LPM each , working pressure 60 psi, higher discharge 90-psi , driver coupling , performance test as per is 5456, stages 1. mounting skid (in silent canopy ), cooling air cooling, compressor speed 288 RPM, electric motor: capacity 22 KW, round per minute 1440, volts 415 . phase 3. Electric supply 50 hz performance test as per IS 325 Make:- Kaeser/Atlas Copco/IR/Elgi/Airtech

1

-

2360000

... More
Supply & erection of 12 mm isolation ball valve with brass fitting BS:EN 13348 medical grade with proper fitting complete in all respect.

186

-

251100

... More
Supply & erection of Fine filtration system with 1no. Of fine having replacable filter cartridge class 1 to 4 removal of traces of particle, moisture, carbon particles and oil contents from air stream. These set of 1 filters would also have individually bypass arrangement of smoth functioning and easy maintenance. TECHNICAL SPECIFICATION: Type dry cartage (set of 3) removal of particles class 1 removal of moisture class 4 removal of oil contents class 1 activate carbon filter class 1 Make:- Multitech/ATS/Domnivk/Airtech

5

-

354000

... More
Supply & erection of copper pipe with required fitting BS:EN 13348 medical grade 54mm outer dia, 1.2 mm thick copper pipe able to handle minimum 6.00 kg pressure with paint as per standard norms including bend, Elbow, tee etc .

485

-

1964250

... More
Supply & erection of Air receiver of 2000L water capacity made out of MS plate 5mm thick as per is 2825 dually 2 coat of primer and 2 coat of enamel paint (1 pre painted and other at site) duly fitted with 3no. Lux having arrangement of foundation bolt. The reciever would have connection points for pressure gauge/safety valve/ drain valve. the air reciever would be hydrostated tested @300 PSI before dispatch. TECHNICAL SPECIFICATION: Construction IS2825, 2. capacity 200 ltr 3. fountation skid 4. blast cap 300 PSI 5. fittings pressure gauge safety valve, drain trap. Make:- Multitech/B-Tech/Airtech

1

-

141600

... More
Supply & erection of electrical control panel suitable for medical air compressors shall be suitable for the selected duplex system and will be fabricated to be a combined control panel. The combined electrical control panel will be provided complete with mains indicating lights, single phasing preventer, phase loss/ phase reversal indicating lights, individual MCBS for all starters, individual ammerters for all motors, contractors, overload relays, control circuti MCB , start/stop push buttons, auto/maunal switches relays with overriding feature. Technical specification : 1 . Main MCCB 160 amp 2. Spreader 160 amp 3. Bus bar 200amp 4. Relay 220 volts 5. MCCB three pole 100 6. Contractor 70 amp 7. Volt meter digital 8. Amp meter digital 9. C/t 150/5 10. Selector SW 11. Relay 24 volt 12. enclosure 1000x850x250 or above Make:- Schneider/L&T/ABB

1

-

295000

... More
Supply & erection of Fine filtration system with 1no. Of fine having replacable filter cartridge class 1 to 4 removal of traces of particle, moisture, carbon particles and oil contents from air stream. These set of 1 filters would also have individually bypass arrangement of smoth functioning and easy maintenance. TECHNICAL SPECIFICATION: Type dry cartage (set of 3) removal of particles class 1 removal of moisture class 4 removal of oil contents class 1 activate carbon filter class 1 Make:- Multitech/ATS/Domnivk/Airtech

5

-

354000



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.