Odisha State Housing Board Tender
... More
The OSHB has issued a formal invitation for competitive bids for the Odisha State Housing Board project, for Installation Of Basement Lobby And Lift Well Pressurization Work With Fire Resistance Door At Fire Exit Staircase Of All Floors In Connection With Fire Fighting System Of B Plus G Plus12 Storied Residential Apartment Kharavela Enclavejagamara Bbsr in Bhubaneswar, Odisha, with an estimated contract value of Rs. 49,31,000. The bid opening date for this tender is 25-09-2024 and the last date for bid submission is 08-10-2024. Interested bidders for Odisha State Housing Board tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Odisha State Housing Board - OSHB Tender
Civil And Construction
Building Construction
Security and Emergency Services
Eprocure
Opening Date25 Sep 2024
Closing Date8 Oct 2024
Tender Amount₹ 49,31,000
Costs
EMD
₹ 50,000Document Cost
₹ 7,080Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_OSHB_105141_1Bid Award Id
ViewTender No
01/CE/OSHB/2024-25Tender Authority
Odisha State Housing Board ViewPurchaser Address
-Website
http://tendersodisha.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
PRESSURIZED AIR FAN DETAILS : Supply, Installation, Testing & Commissioning of direct driven Standard temprature Fans as per specifications with Long casing ( Motor should completely be accommodated inside the fan casing). Fan shall be AMCA Certified (For both Air and Sound Performance as per AMCA 210 & 300). Fan should be of G.S.S. , the Steel sheet should be JFE Galvazinc (Base metal cold rolled), JIS G3302, SGCC with Z22 (minimum coating weight on both sides @ 220 g/m2) zinc coating & Zero Spangle, skinpassed, chromated and dry. Fan motor shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply of class 'F' insulation. The fan shall be equipped with mounting bracket & spring isolators for the installation of the fans.. Fan shall be with fire proof flexible connection at inlet and outlet..Emergency Fans shall be activated from fire signal from fire alarm system. Fan static pressure shall be as indicated but actual fan static pressure to be checked by vendor.All tube/vane axial fans motors shall be of minimum IE3 efficiency. Fan total efficiency should not be less than 70 %, noise level should not be more than 75 dbA @ 3 m distance for normal operation fans and 80 dbA @ 3 m distance for emergency operation fans when measured in hemisperical reverberant room conditions. Sound attenutors of appropriate length shall be included in the cost to achieve the desired result. Outlet velocity of fans shall not be exceed 15m/s for more info refer details drawings, including cost of all materials, all labour, sundries, T&P etc. .Further, any damage caused should be re-done matching the original structure at the cost and risk of executant agency etc. complete in all respect as per direction of Engineer-in-Charge.
( Make : Kruger / Dynair / Green heck / Flaktwood
-
-
-
... More
( B) FOR 6 Nos. of 7.5 KW pressurized air fan - Passenger Lift Well
6
171000
28500
... More
Supplying & fixing of powder coated extruded aluminium supply Air Grills with collar damper etc. complete in all respect with approved specification and design as per the instruction of Engineer - Charge.
Make: Caryaire /Swirl Air / Pineair
4.1
51250
12500
... More
Supplying & fixing of powder coated extruded aluminium supply Air Louvers etc. complete in all respect with approved specification and design as per the instruction of Engineer - Charge.. Make: Caryaire /Swirl Air / Pineair
8
116000
14500
... More
Axial flow type - ceiling mounted supply air fan for basement lift lobby pressurization - Capacity: 15500 CFM with static pressure upto 30 mm W.G.,
4
620000
155000
... More
DISMANTLING WORK :Supplying all materials and labour for Dismantling and removing old marble flooring including removing the base coarse and stacking the useful materials for reuse and removing the debris within 50m lead etc. complete in all respect as per the direction of Engineer- in - Charge. BASEMENT
10.37
1457
140.5
... More
3C x 4 sq.mm CU. Cable
120
34200
285
... More
L.T. CABLES : The rates for all Item of work shall include the following: ( A)Effective proper and adequate connection at terminations. (B) Providing and fixing all accessories such as clamps, nuts, bolts & screws. (C) Jointing by crimping type lugs. ( D) Cutting, chases holes & making good the same wherever requiredfor more info refer details drawings, including cost of all materials, all labour, sundries, T&P etc. .Further, any damage caused should be re-done matching the original structure at the cost and risk of executant agency etc. complete in all respect as per direction of Engineer-in-Charge. Providing, laying / fixing, testing & commissioning of following size of 1.1 KA grade PVC insulated copper conductor armoured FRLS cables laid in ready trench, laid on cable trays, fixing on walls in an approved manner or required complete with earthing alongwith cable (earthing will be measured separately & need not be quoted under this Item) all complete as required as per final direction and approval Make: R R kabel/Polycab/KEI
-
-
-
... More
Priming one coat with wall cement primer (water bound) to make an even finished surface in all floors and heights to wall surface of approved make and shade including sand papering, applying putty wherever necessary & cost of scaffolding, staging charges with cost, conveyance, cost of all labour,labour cess T&P etc. complete as per the direction of the Engineer-in-charge.
(Make: Asian/ Berger/ Dulex/ ICI or equivalent make duly approved by Engineer-in-Charge)
216.11
17526
81.1
... More
4C x 4 sq.mm CU. Cable
360
126000
350
... More
3C x 2.5 sq.mm CU. Cable
80
19200
240
... More
Providing, laying, fixing , connecting and tseting of under noted sizes of copper strip / GI Strip / GI wire from earth electrode to equipment, loop and earthing system in trenches , on the surface , a lighting pole, including excavation where required for layong of copper/ GI strip / GI wire and filling back complete conforming to relevent IS ans as specified etc. complete in all respect as per the direction of Engineer-inCharge. ( A) 12 SWG x 1W G.I.
220
24200
110
... More
DISMENTLING WORKS :Supplying all materials and labour for Dismantling and removing RCC columns,beams,slab,staircase landing,lintels,wall including stacking the useful materials for reuse and removing the debris within 50m lead.etc. complete in all respect as per the direction of Engineer- in - Charge. GROUND FLOOR
1.42
2355
1655.2
... More
Axial flow type - surface mounted supply air fan for fire lift well pressurization - Capacity: 20,500 CFM, static pressure upto 35 mm W.G.,
6
1050000
175000
... More
2C x 1.5 sq.mm CU. Cable
300
39000
130
... More
Supply, installation, balancing and commissioning of factory fabricated double canvass (fire retardant) flexible connection etc. complete in all respect with approved specification and design as per the instruction of Engineer - Charge.. Note: Fabrication and jointing of duct shall be as per IS standard and hanging shall be as per SMACNA. Make: Caryaire /Swirl Air / Pineair
10
45000
4500
... More
Providing and fixing ISI Marked un-insulated fire rated door confirming to IS 3614:2021,& tested to IS17518,and shall carry a unique label with certification/test report number.The fire rating shall be for 120minutes integrity only.Material shall be galvanised steel conforming to IS 277, made out of minimum 1.2(18 SWG) for both frame and shutter, G.I. sheet (zinc coating 120 gsm/sqm).Frame shall be 125 x 55 grooved profile with built in rebate for fire rated smoke seal. Frame shall be mitered and field assembled. EPDM smoke seal to be provided along with frame as standard. Door shutter shall be double skin of 46mm thick with required fire rating and with vision panel. The infill material shall be resin bonded honeycomb core. All doorset shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks and door closers.The door stiles should be interlocked, for pairs of doors integral astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite, minimum 5mm clear fire rated glass of size 150 x 750mm (max 0.12sq.mt) on both shutters, fixing with clipon arrangement.
-
-
-
... More
DISMENTALING WORKS :Supplying all materials and labour for Dismantaling brick or stone masonary in lime or cement mortar above 3 mtr height including stacking the useful materials for reuse and removing the debris within 50m lead.etc. complete in all respect as per the direction of Engineer- in - Charge. GROUND FLOOR
6.17
9681
1569.9
... More
CIVIL WORKS : Fly Ash brick masonry in cement mortar (1:6) in super structure using Fly Ash bricks of 25 x 12 x 8 cm size having a crushing strength of not less than 75 kg./sqcm with dimensional tolerance ± 2% including splays cutting circular moulding chamfering and corbelling and similar such type of works with all necessary projections watering and curing after immersing the bricks in water at least for six hours before use including cost, conveyance, royalties and taxes of all materials with all labour,labour cess and T & P required for the work complete in all respect as per direction of Engineer-in-Charge. GROUND FLOOR
23.51
131828
5607.1
... More
DUCTING & GRILLS- ACCESSORIES : Supply, installation, balancing and commissioning of Site fabricated GSS sheet metal rectangular ducting with supports as per IS 655-2006 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following gauges for more info refer details drawings, including cost of all materials, all labour, sundries, T&P etc. .Further, any damage caused should be re-done matching the original structure at the cost and risk of executant agency etc. complete in all respect as per direction of Engineer-in-Charge. -
Note: Fabrication and jointing of duct shall be as per IS standard and hanging shall be as per SMACNA.
Make : Jindal / TATA / SAIL Thickness 0.8 mm sheet (22G)
240
331200
1380
... More
ELECTRICAL- THREE PHASE STARTER AND CONTROL PANEL :Supply, Erection, Testing & Commissioning of Electrical 3 phase starter & Control panel for above fans- DOL/ STAR DELTA with suitable MCCB isolator with overload/ short circuit protection, auto manual selector switch & suitable relay module for linking with fire alarm signal, also provide potential free cotact for ON/OFF signal status. Etc. complete in all respect as per the Direction of Engineer - In - Charge
Make: Seimens / L&T / ABB ( A) FOR 4 Nos. of 5.5 KW pressurized air fan - Fire Lift Lobby
4
102000
25500
... More
Fixing granite tiles of approved dimension area above 0.4 sqm (20mm thick) in floor, treads of steps and landing on 20mm thick bed of cement mortar (1:4) jointed with neat cement slurry mixed with pigment to match the shades of the tiles including rubbing and polishing etc. complete with cost, conveyance, royalties and taxes of all materials complete in all respects as per direction of Engineer-in-Charge.
13.71
38222
2787.9
... More
Supplying Cutting, straightening coiled or bent up M.S. Rod or tor steel of primary steel producers such as SAIL / TATA / RINL / JINDAL STEEL / SHYAM STEEL/ SEL Tiger (grade Fe-500D) etc. including bending, binding, welding and jointing if necessary and tying the grills and placing in position as required for R.C.C. Work and for providing fan hooks as required, hoisting, lowering, laying including cost, conveyances of M.S. Rod or tor steel and binding wires of 18 to 20 gauge and labour required for the work for bending, binding and tying the grills in all floors with labour cess etc. (payment will be made on standard weight of B.I.S. for M.S. Rods or tor steel only) etc. complete as per specification & direction of Engineer-in-charge.
2.96
25434
8592.7
... More
Providing, lifting, hoisting and laying Reinforced cement concrete of M-25 grade as per approved designs and drawings having a minimum compressive strength (in work test) 250 Kg. / Square cm. in 15 cm. cubes at 28 days after mixing and test conducted in accordance with I.S. 516 using 12 mm. to 20 mm. size black hard crushed broken granite stone chips and screened and washed sharp sand for mortar of approved quality from approved quarry, washed and cleaned ( 20mm. size chips not to exceeds 25 % ) to be mixed in concrete mixture with Portland slag cement (PSC) including hoisting, lowering, laying and compaction concrete by using vibrators, watering and curing for 28 days, centering and shuttering then after dismantling and removing debris from the work site and finishing the exposed surface smooth providing grooves or beads wherever necessary including cost, conveyance, loading, unloading, royalties and taxes of all materials and cost of all labours, sundries, T & P required of the work etc. complete in all respect as directed by the Engineer-in-Charge. But excluding cost and conveyance of M.S. rods or Tor steel and binding wires and labour charges for straightening, cutting, bending etc. of M.S. rods or tor steel tying the grills and placing in proper position etc.complete in all respect as per the direction of Engineer- in - Charge. GROUND FLOOR : LINTEL
1.97
28485
14459.6
... More
Supply, installation, testing and commissioning of bird screen for more info refer details drawings, including cost of all materials, all labour, sundries, T&P etc. .Further, any damage caused should be re-done matching the original structure at the cost and risk of executant agency etc. complete in all respect as per direction of Engineer-in-Charge.
8
22800
2850
... More
Supply, Fabrication and Installation of MS frame using channels/angle iron sections as required for mounting of Centrifugal Fans. The frame work shall be applied with red oxide primer and thereafter, two coats of enamel paint of approved colour etc. complete in all respect with approved specification and design as per the instruction of Engineer - Charge..
200
30000
150
... More
Supply of GI Slotted Cable Tray ( 150mm) for more info refer details drawings, including cost of all materials, all labour, sundries, T&P etc. .Further, any damage caused should be re-done matching the original structure at the cost and risk of executant agency etc. complete in all respect as per direction of Engineer-in-Charge.
50
42500
850
... More
Fixing granite tiles of approved dimension area above 0.1 up to 0.4 sqm (10mm thick) in Dados, treads of steps and landing on 12mm thick cement mortar (1:3) jointed with neat cement slurry mixed with pigment to match the shades of the tiles including rubbing and polishing etc. complete with cost, conveyance, royalties and taxes of all materials complete in all respects as per direction of Engineer-in-Charge.
3.4
6958
2048.3
... More
All frame and door shutter shall be finished polyster powder coated to minimum 50microns, of approved colour as per the direction of the engineer incharge. Cost of double leaf doorset shall include following hardware and accessories as a complete assembly. SS ball bearing hinges of SS-304 grade of size100x75x3mm,1no Fire rated mortise dead lock, 55mm BS, 20mm sq. forend, including escutheion, sss as per EN 12209 with both side key cylinder on active leaf and 2nos flush bolt on the inactive leaf in case of double leaf door along with dust proof socket at bottom, 1pairs Pull handle D type, 22dia, CTC 300mm, back to back per leaf, with spindle,SS 304, SS finish. 1no of Door closer with spring size of EN 2- 4, as per EN1154 and CE marked per leaf. Suitable anchor fastners for fixing on different type of wall construction as per manufacturer recommendation.Once frames is installed it shall be filled with fire rated PUF. Manufacturer test certificates shall covers complete door set as a un-latched assembly with a valid test certificate not exceeding 5 years from the date of issue of report. for more info refer doors details drawings, including cost of all materials, all labour, sundries, T&P etc. .Further, any damage caused should be re-done matching the original structure at the cost and risk of executant agency etc. complete in all respect as per direction of Engineer-in-Charge.(make-Saint gobain,Shakti Hormannm, Tata pravesh) Make;-ASES Security/ ( FOR ALL FLOORS)
106.16
1745286