Odisha Industrial Infrastructure Development Corporation Tender

... More
Search from a pool of business opportunities related to Odisha tenders on the online platform of BidAssist. Be it an Odisha PWD tender or a civil aviation tender, one can find every tender Odisha government, as well as PSUs and other organizations, post online. Every tender, active or achieved, is sourced from the eProcurement Odisha website and thus carries full credibility.

Odisha Industrial Infrastructure Development Corporation - IDCO Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date20 May 2025
Closing Date11 Jun 2025
Tender Amount₹ 6,63,87,341 
Notes
Download

AI Insights

Class Of Bidder
... View More
The eligible classes required by a bidder to participate or bid in the tender are: 1. OEM 2. HVAC Contractor 3. Special class contractor 4. 'A' class contractor
Technical Capacity
... View More
The bidder is required to have experience in HVAC Chiller Plant System Works in any Govt PSU or ULB, with a list of projects under execution or executed that are similar in nature to the work. The similar nature of work should be of an appropriate amount, but specific values or percentages of similar works completed are not mentioned. However, the bidder must submit a statement showing the value of existing commitments and ongoing works, as well as the total value of work performed in the last five years. If the qualifying work is completed in the specified five-year period, it will be considered as meeting the qualifying requirements. Additionally, the bidder needs to furnish a scanned copy of valid OEM or authorized dealer having authorization from manufacturer, having experience in similar nature of works in Govt sector / PSU / ULB. No specific amount or percentage is mentioned for similar works completed.

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Twin/Mono screw type helical rotary compressor semi-hermatic complete with automatic capacity control, safety switches, speed increasing gears, forced feed lubrication system etc. as per specifications.

-

-

-

... More
1 No.- Suitable capacity squirrel cage induction motor with class B / H (As per manufacturers standards) insulation suitable for operation on 415±10% volts, 3-phase, 50Hz A.C. supply.

-

-

-

... More
Variable Frequency Drive (with necessary logic controller for speed variation) for the motor with CTs, over load/ under voltage protection, protection against phase reversal, single phase preventors, timer control & trip circuit complete as required. The VFD shall be unit mount

-

-

-

... More
1 Set- Microprocessor based BMS compatible control panel with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet, condenser inlet and outlet temperature parameters, operating pressures etc.

-

-

-

... More
Necessary drive arrangement

-

-

-

... More
1 No.- ASME stamped matching shell and tube water cooled condenser of M.S. shell and integrally finned copper tubes. Fouling factor 0.001 (FPS Unit). Pressure drop in condenser shall not exceed 30 ft of Wg.

-

-

-

... More
1 No.- ASME stamped matching shell and tube DX / flooded type chiller for screw type units of MS shell and copper tubes. Fouling factor 0.0005 (FPS Unit). The pressureop in chiller shall not exceed 20 ft of Wg.

-

-

-

... More
1 Lot- Refrigerant piping fittings, valves and accessories to inter connect compressor, condenser, chiller and expansion valve, sensing element for HP/LP/ Anti freez etc complete as required.

-

-

-

... More
Lot- Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications, liquid level control etc.

-

-

-

... More
Lot- Water flow switches at inlet and outlet of condenser & chiller, water drain & air purge valves wherever required.

-

-

-

... More
Lot- Suction line and chiller insulation with minimum 19mm thick polvinyl / nitrile rubber insulation finished with 0.63mm thick G.S.S. cladding complete as required.

-

-

-

... More
Lot- Frame work (including victaulic couplings at the inlet & outlet of cooler & condenser; & painting of all components) for mounting the above condenser, chiller compressor and motor with base plate complete with antivibration pads/ springs.

-

-

-

... More
Lot- Initial / first charge of refrigerant gas & compressor oil

-

-

-

... More
Refrigerant piping shall be factory assembled as per the specifications.

-

-

-

... More
Additional Safety Devices shall include Internal Thermostat for Compressor Motor, Fusible Plug, Discharge Gas Thermostat, Operation Hour-Meter etc.

-

-

-

... More
450.0 TR actual capacity

-

-

-

... More
Make: Carrier/ Trane/ Dunham-bush/ York/ Daikin

-

-

-

... More
225.0 TR actual capacity

-

-

-

... More
450.0 TR actual capacity

2

9863041

-

... More
Overhauling of 225 TR YORK Make Screw Chiller

1

500000

-

... More
Chilled Water & Condenser Water Pumps

-

-

-

... More
Supply, installation, testing and commissioning of End-suction Back Pullout Split Coupled/ Long-Coupled (with rigid aluminium alloy coupling between pump shaft and motor shaft) single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Common fatory fitted Baseframe & Coupling Guard. Casing (Volute) - Cast Iron (BS 1452 Grade 220) - PN 16 Impeller - Gunmetal Bronze (BS1400LG2C) - Statically and Dynamically Balanced Casing Gasket - Confined Non Asbestos Fiber Pump Shaft - SS (BS970 416) Mechanical Seal - Outside Balanced/ Inside Spring. Must withstand 2000 TDS. Motor Type - TEFC Squirrel Cage, Efficiency Class - IE3, Insulation - Class F, 415V ± 10% , 50Hz ± 5%, 3Ø AC Power Supply

-

-

-

... More
Chilled Water Pump (1W + 1S) (For Primary system) Water Flow Rate: 1080 USGPM Head : 42 m WC Full Load Efficiency : Minimum 78% (to be declared by manufacturer) Part Load Efficiency: Minimum 68% (to be declared by manufacturer) Note: Flowrate & head are indicative, this should be finaized only after finalization of chiller & measurement of head at site.

2

469910

-

... More
Chilled Water Pump (1W + 1S) (For Primary system) Water Flow Rate: 540 USGPM Head : 42 m WC Full Load Efficiency : Minimum 75% (to be declared by manufacturer) Part Load Efficiency: Minimum 75% (to be declared by manufacturer) Note: Flowrate & head are indicative, this should be finaized only after finalization of chiller & measurement of head at site.

2

270499

-

... More
Condenser Water Pump (1W + 1S) Water Flow Rate: 1800 USGPM Head : 30 m WC Full Load Efficiency : Minimum 85% (to be declared by manufacturer) Part Load Efficiency: Minimum 70% (to be declared by manufacturer) Note: Flowrate & head are indicative, this should be finaized only after finalization of chiller & measurement of head at site.

2

381076

-

... More
Cooling Water Pump (1W + 1S) Water Flow Rate: 900 USGPM Head : 30 m WC Full Load Efficiency : Minimum 80% (to be declared by manufacturer) Part Load Efficiency: Minimum 75% (to be declared by manufacturer) Note: Flowrate & head are indicative, this should be finaized only after finalization of chiller & measurement of head at site.

2

688542

-

... More
Cooling Tower

-

-

-

... More
Supplying, installing, testing and commissioning of Induced draft Counter flow FRP cooling tower of 500TR (1507000 K.Cal /hr.) heat rejection capacity with eliminators complete with hot water basin either fitted with spray nozzles or having self rotating sprinklers, statically and dynamically balanced axial flow type fan-direct driven or driven through reduction gear box with TEFC induction motor, suction screen make up quick fill arrangement, overflow and drain connections with necessary valves and suitable aluminum inspection ladder, access arrangement for cooling tower interior, anti vibration mountings etc. complete as per specification and as reqd.

-

-

-

... More
Entering water temperature :37.7°C, Leaving water temperature : 33.3°C.Wet bulb approch not exceeding 3.9 deg c

-

-

-

... More
Type of fan : Aerodynamic Propeller .Type of motor : Weather proof (Less than 600 RPM with Single Fan or Less than 1000 RPM with Twin Fan Cooling tower) motor suitable for operation of 450V,3-ph, AC supply and of efficiency class IE3.

-

-

-

... More
Make - Bell/ Advance/ Paharpur

2

1078101

-

... More
Modification / Rectification of RCC / Cement concrete foundation alongwith MS structure of Existing Cooling Tower & Pot strainner as required at site . Rate shall be including one no Existing Cooling Tower for complete overhauling.Damaged Fills to be replaced.

1

257395

-

... More
Make : Paharpur / Advance / Bell

-

-

-

... More
Condenser water/ any iron structure painting with 2 coat redoixde primer & finally 2 coat synthetic enamail paint . Primar : Shalimar/ Berger. Paint : Asian Paints / Berger / ICC

1

62658

-

... More
Double Skinned Floor Horizontal Mounted Air Handling Units

-

-

-

... More
Supply, installation,testing & commissioning of factory fabricated Double Skinned Chilled Water AHU (horizontal floor mounted) fabricated out of 25 mm thick panels consisting of pre plasticized GI casing of thickness 0.8mm outside layer & 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminium finned copper tubes(tube thickness not less than 0.5 mm), 6 row deep cooling coil, blower motor TEFC type suitable for operation on 415volts,3-ph,50Hz AC supply and of efficiency class IE3, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 18G sheet with PUF insulation, 150 mm dial type pressure guage (2 nos), industrial type thermometer (2 nos), auto purge valve whereever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. AHU coil Shall be AHRI / UROVENT Certified. AHU shall be with Thermal break profile & MARV 13 Filter.

-

-

-

... More
15000 cfm, 50 mm static pressure.

4

397732

-

... More
13000 cfm, 50 mm static pressure.

23

368440

-

... More
9500 cfm, 50 mm static pressure.

20

282419

-

... More
4500 cfm, 50 mm static pressure.

2

179250

-

... More
Make - VTS/ Zeco/ Edgetech

-

-

-

... More
Double Skinned Ceiling Suspended Air Handling Units

-

-

-

... More
Supply, installation,testing & commissioning of factory fabricated Double Skinned Chilled Water Ceiling suspended AHU fabricated out of 25 mm thick panels consisting of pre plasticized GI casing of thickness 0.6mm outside layer & 0.6 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with plug fans suitable for operation on 415 Volt 3 phase supply with electric motor of efficiency class IE3 suitable for static pressure as mentioned below, minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminium finned copper tubes(tube thickness not less than 0.41 mm), 4 row deep cooling coil, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, polished stainless steel drain pan made out of 18G sheet with PUF insulation auto purge valve whereever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities.The AHU shall be complete with starter wired remote ON/OFF operation and temperature control

-

-

-

... More
Make - VTS/ Zeco/ Edgetech

-

-

-

... More
1600 cfm, 40 mm static pressure.

2

93285

-

... More
VFD for AHUs

-

-

-

... More
Variable frequency drive for AHU fan including cost of sensors, logic controller including cabling between sensors, logic controller and VFD as reqd. VFD shall be compatible eor operation status indication through BMS.

49

56635

-

... More
Make : Danfoss/ ABB / Seimens

-

-

-

... More
PLUMBING

-

-

-

... More
Chilled Water Piping with insulation

-

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water plumbing inside the building ( with necessary clamps, vibration isolators and fittings like elbows, tees, reducers, bends, MS flanges but excluding valves, strainers, guages etc) duly insulated with Supplying, laying/fixing, testing and commissioning of following nominal sizes of chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with fire retardant quality expanded polystyrene EPS with 50 mm thickness moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip (as per IS:1322 as amended upto date) at joints repairing of damage to building etc. as per specifications and as required complete in all respect. Note : The pipe of size 150 mm and below shall be MS 'C' Class as per IS : 1239. Pipe size above IS : 3589.

-

-

-

... More
Make - TATA/ SAIL/ Jindal Hissar

-

-

-

... More
Insulation Make - Beard Shell / Astha/ Sterile Packaging

-

-

-

... More
32 mm dia

72

1120

-

... More
40 mm dia

72

1267

-

... More
50 mm dia

100

1680

-

... More
65 mm dia

300

2028

-

... More
80 mm dia

90

2407

-

... More
150 mm dia

36

4355

-

... More
200 mm dia

36

6844

-

... More
250 mm dia

36

8681

-

... More
400 mm dia, 7 mm thick minimum

1

15162

-

... More
Valves & Strainer In Chilled Water Line

-

-

-

... More
Supplying, installing, testing & commissioning of Valves with the large torque rotory type actuator shall be capable of nominal voltage AC/DC 24 V electric signal, transformer duly encased and including necessary control wiring etc. The valves & actuators shall be compatible with Building Automation System as well as manual operation. The valve shall be suitable for following pipe sizes including Nut, Bolt, Washer, Gasket etc. All Valves shall PN 16

-

-

-

... More
Butterfly Valves

-

-

-

... More
Supplying, fixing, testing and commissioning of BUTTERFLY VALVE/ BALL VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified

-

-

-

... More
Note: size from and above 200 mm dia will be gear operated

-

-

-

... More
Make - Advance/ Honeywell/ Zoloto

-

-

-

... More
32 mm dia ( Ball Valve )

8

2613

-

... More
50 mm dia

4

4417

-

... More
65 mm dia

90

5642

-

... More
80 mm dia

8

6466

-

... More
150 mm dia

4

13080

-

... More
200 mm dia

4

24020

-

... More
250 mm dia

1

35544

-

... More
Motorised Butterfly Valves

-

-

-

... More
Supplying, installing, testing & commissioning of Motorized Open / Closed Control Butterfly valves. The large torque rotory type actuator shall be capable of nominal voltage AC/DC 24 V electric signal, transformer duly encased and including necessary control wiring etc. The valves & actuators shall be compatible with Building Automation System as well as manual operation. The valve shall be suitable for following pipe sizes including Nut, Bolt, Washer, Gasket etc. All Valves shall PN 16

-

-

-

... More
Make - Advance/ Honeywell/ Belimo

-

-

-

... More
150 mm dia

4

54491

-

... More
200 mm dia

4

62638

-

... More
250 mm dia

1

91353

-

... More
Balancing Valves

-

-

-

... More
Supplying, fixing, testing and commissioning of BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position confirming to standard specification.

-

-

-

... More
Make - Advance/ Honeywell/ Zoloto

-

-

-

... More
32 mm dia ( Ball Valve )

2

2613

-

... More
50 mm dia

2

10434

-

... More
65 mm dia

43

11282

-

... More
80 mm dia

4

13218

-

... More
150 mm dia

2

34042

-

... More
200 mm dia

2

62958

-

... More
250 mm dia

1

81499

-

... More
Check Valves

-

-

-

... More
Supplying, fixing, testing and commissioning of Non-Return valve with dual plate of CI body SS plates vulcanized NB seal flanged end & PN16 pressure rating of Chilled/ Hot Water circulation including insulation as specified.complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position confirming to standard specification.

-

-

-

... More
Make - Advance/ Honeywell/ Zoloto

-

-

-

... More
150 mm dia

2

13427

-

... More
200 mm dia

2

26070

-

... More
250 mm dia

1

33200

-

... More
Y Strainner

-

-

-

... More
Supplying, fixing, testing and commissioning of Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.MS fabricated "Y" type strainers with removable type bronze screen with 3mm perforation & permanent magent etc.complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position confirming to standard specification.

-

-

-

... More
Make - Rapid Cool/ Emerald/ Sant

-

-

-

... More
32 mm dia ( Ball Valve )

2

3289

-

... More
50 mm dia

2

5157

-

... More
65 mm dia

43

6626

-

... More
80 mm dia

4

7903

-

... More
150 mm dia

2

16749

-

... More
200 mm dia

2

28776

-

... More
250 mm dia

1

41387

-

... More
3 Way modulating type Mixing valves with Actuator

-

-

-

... More
Supply, installation, testing & commissioning of 3-way valve modulating type mixing valve complete with electrical motorized actuator (should be compatible with BMS ), heavy duty PN16 ( DZR brass body upto 40 mm NB size & cast iron body above or from 50 mm NB) with control unit made by soft diaphragm nylon coated S.G. iron disk,water sealant lining, stainless steel shaft, control lever with proportionating thermostat & its control wiring,accessories if any like transformer 24V etc.position confirming to standard specification for the following pipe sizes. Note : 24 Volt control transformer of appropriate VA rating along with Incoming and outgoing MCBs shall be provided in the AHU panel. with 3 sides companion flanges. Rates included Thermostat, actuator & necessary conrtol cabling

-

-

-

... More
Make - Danfoss/ Belimo/ Honeywell

-

-

-

... More
25 mm dia

2

15761

-

... More
32 mm dia

1

17575

-

... More
40 mm dia

2

23265

-

... More
50 mm dia

43

27940

-

... More
65 mm dia

4

58260

-

... More
Condensate Drain Piping

-

-

-

... More
Supplying, fixing, testing and commissioning of G.I. 'B' Class medium water pipes for Condensate Drain of following size along with necessary clamps, fittings such as bends, tees etc. adequately supported duly insulated as per Chilled water insulation spec. (for AHU & FCU drain)

-

-

-

... More
25 mm dia

100

998

-

... More
32 mm dia

100

1153

-

... More
65 mm dia

100

2162

-

... More
Ball valve for drain connection 25 mm

60

1806

-

... More
Ball valve for drain connection 40 mm

10

2759

-

... More
Ball Valve for CSU 40mm Dia

8

2759

-

... More
Make - Advance/ Zoloto/ Honeywell

-

-

-

... More
Condenser Water Piping

-

-

-

... More
Supplying,laying/ fixing, testing and commissioning of Condenser water pipes M.S 'Heavy' Class ERW conforming to IS:1239 / 3589 complete of following sizes and materials along with necessary clamps, vibration-isolators, and fittings such as bends, tees etc but excluding strainer and guages etc adequately supported on rigid supports etc as per specification and as required.

-

-

-

... More
150 mm dia

42

2961

-

... More
250 mm dia

90

6227

-

... More
350 mm dia

48

9119

-

... More
Valves & Strainer In Condenser Water Line

-

-

-

... More
Supplying, fixing, testing and commissioning in position of following valves, strainers, guages in the Condenser water plumbing confirming to PN16 pressure rating as the connected piping and adequately supported as per specifications.

-

-

-

... More
Supply, installation, testing and commissioning of Butterfly valves complete with companion flanges, nuts, bolts, gaskets etc. as specified and position confirming to standard specification

-

-

-

... More
Note: size from and above 200 mm dia will be gear operated

-

-

-

... More
150 mm dia

1

10919

-

... More
200 mm dia

4

20600

-

... More
250 mm dia ( Gear Operated )

6

31688

-

... More
300 mm dia ( Gear Operated)

4

37601

-

... More
350 mm dia ( Gear Operated )

3

47340

-

... More
Supply, installation, testing and commissioning of Motorised Butterfly valves complete with (Push Button for ON/OFF arrangement & ON /OFF valve indications). Actuator shall have potential free contacts for status monotoring.The price shall include necessary control wiring etc., position confirming to standard specification

-

-

-

... More
150 mm dia

1

49269

-

... More
200 mm dia

4

55902

-

... More
250 mm dia

4

87497

-

... More
Supplying, fixing, testing and commissioning of BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position confirming to standard specification.

-

-

-

... More
150 mm dia

1

31613

-

... More
200 mm dia

2

59030

-

... More
250 mm dia

2

76978

-

... More
Supplying, fixing, testing and commissioning of Non-Return valve with dual plate of CI body SS plates vulcanized NB seal flanged end & PN16 pressure rating of Chilled/ Hot Water circulation including .complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position confirming to standard specification.

-

-

-

... More
150 mm dia

1

11198

-

... More
200 mm dia

2

22500

-

... More
250 mm dia

2

29147

-

... More
Supplying, fixing, testing and commissioning of Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.MS fabricated "Y" type strainers with removable type bronze screen with 3mm perforation & permanent magent etc.complete with companion flanges, nuts, bolts, gaskets etc. as specified. in position confirming to standard specification.

-

-

-

... More
150 mm dia

1

14391

-

... More
200 mm dia

2

25011

-

... More
250 mm dia

2

36989

-

... More
Make : All Valves & stainner in Condenser Line will be same as Chilled Water Line .

-

-

-

... More
Pressure Gauge & Temp. gauge

-

-

-

... More
Supply, installation, testing and commissioning of mercury filled 'V' form thermometer with copper well of approved make conforming to technical specifications.

134

1591

-

... More
Supply, installation, testing and commissioning of common pressure guage with appropriate range with syphon with ball valve and of approved make of dia 100 mm conforming to techinical specifications.

150

2989

-

... More
Make - H.Guru/ Feibig/ Waree

-

-

-

... More
VCD & FD

-

-

-

... More
Motorised Combined Fire & Smoke Damper

-

-

-

... More
Supplying, Fixing, testing and commissioning of UL555 & UL555S listed/classified motorized fire & smoke dampers formed of 16G thick galvanized sheet. Fire dampers are provided in supply air duct / main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. These shall be of multi-leaf type and provided with Spring Return electrical actuator and own thermal trip for air temperature inside the duct. The dampers shall meet the requirements of NFPA 80, 90A, 92, 101 & 105. Dampers shall have a fire rating of 90 min. in accordance with latest edition of UL555 and shall be classified as Leakage Class 1 smoke damper in accordance with latest version of UL555S certified for both vertical & horizontal installation. Each fire/smoke damper shall be AMCA licensed and bear the AMCA seal for air Performance. Pressure drop shall not exceed 5 Pa when tested at 300 m/min face velocity on 600x600 mm size damper. Actuator shall be UL listed. Each damper shall be supplied with factory mounted sleeve of galvanized steel of thickness as per SMACNA and of minimum 400 mm long. Damper Frame shall be hat channel, of 16G galvanized sheet. Damper blades shall be airfoil shaped (equivalent to 14G thickness) using 20G thick galvanized sheet. Electric Actuator of suitable Torque and as approved by UL shall be factory mounted and tested. The actuator shall be suitable for 230V AC supply. The damper shall be equipped with a device to indicate OPEN and CLOSE position of Damper blades through a link mounted on the damper blade. Each damper shall be provided with its own control panel, mounted on the wall and suitable for 230 VAC supply. This control panel shall be suitable for spring return actuator and shall have the following features: • Potential free contacts for AHU fan ON/ Off and remote alarm indication. • Accept signal from external smoke / fire detection system for tripping the electrical actuator. • Test and reset facility. • Indicating lights / contacts to indicate the following status: i Power Supply On; ii Alarm; iii Damper open and close position; iv) Damper size should de as site condition.

30

15256

-

... More
Make - Trox/ Greenheck/ Systemair

-

-

-

... More
Fusible link Fire Damper

-

-

-

... More
Supplying, Fixing, testing and commissioning of UL555 listed/classified fusible link type fire dampers formed of 16G thick galvanized sheet. The damper shall be closed in the event of fire as required and as per specifications. These shall be of multi-leaf type and provided with own thermal trip for air temperature inside the duct. The dampers shall meet the requirements of NFPA 80, 90A & 101. Dampers shall have a fire rating of 1.5 Hrs. in accordance with latest edition of UL555 certified for both vertical & horizontal installation and tested to close under dynamic air flow condition. Each fire/smoke damper shall be AMCA licensed and bear the AMCA seal for air Performance. Pressure drop shall not exceed 10 Pa when tested at 300 m/min face velocity on 600x600 mm size damper. Each damper shall be supplied with factory mounted sleeve of galvanized steel of thickness as per SMACNA and of minimum 400 mm long. Damper Frame shall be hat channel, of 16G galvanized sheet. Damper blades shall be 3V shaped using 16G thick galvanized sheet. Fusible link as approved by UL shall be factory mounted. Size of Damper shall be as per site condition.

20

13757

-

... More
On/Off spring return type Actuator with Control Panel

-

-

-

... More
Make - Trox/ Greenheck/ Systemair

-

-

-

... More
Volume Control Damper

-

-

-

... More
Supply, installation, testing and commissioning of multiblade volume control damper formed of 16G Galvanized sheet. Damper for ducts to be provided with suitable links and quadrants for control of volume of air. Pressure drop shall not exceed 5 Pa when tested at 300 m/min face velocity on 600x600 mm size damper. Damper blades shall be 3V shaped using 16G thick galvanized sheet.

1

13175

-

... More
Make - Trox/ Greenheck/ Systemair

-

-

-

... More
Damper Actuator

-

-

-

... More
Supply, installation, testing and commissioning of Motorised Spring Return Actuator for devices upto 0.8 sq. metre with control panel &Smoke detector.The price shall include control cabling inter-locking / wiring / connection for tripping of AHU fan motor. Complete control & power wiring for fire dampers & it's inter-locking with fire alarm panel shall be included in the scope of work including necessary step down transformers etc. as may be required .

80

10205

-

... More
Make - Belimo/ Siemens/ Honeywell

-

-

-

... More
ELECTRICAL

-

-

-

... More
Pump Panel

-

-

-

... More
Supplying, installing testing and commissioning of MV Panel Board suitable for Top entry cable termination for 3 phase, 415 V, 50 HZ supply with 1250 A Aluminium busbar, fabricated from minimum 2mm thick CRCA sheet powder coated through seven tank process facility for prickling and degreasing, powder coat painting, complete with following mountings, having RS 485 communicating ports and inter connections etc.as required.

1

357349

-

... More
Note: All MCCB shall have Ics = 100% Icu

-

-

-

... More
Incomer : 1 Nos.

-

-

-

... More
1000 Amp MCCB TP + NL 36 KA with microprocessor release

-

-

-

... More
1 No.Ammeter with ASS and CTs of rating 1000/5A.

-

-

-

... More
1 No.Voltmeter with VSS rating.

-

-

-

... More
Digital multifunction meter suitable for displaying and recording voltage, current, pf, KW, KVAr, KWhr etc and compatible for communication with BMS compatibility.

-

-

-

... More
3 Nos.phase indicating lamps

-

-

-

... More
Outgoing

-

-

-

... More
6 Nos. 100 Amps. MCCB TP+NL 36 KA outgoing for condenser water pump and secondary pumps

-

-

-

... More
2 Nos. 150 Amps. MCCB TP+NL 36 KA outgoing for condenser water pump and secondary pumps

-

-

-

... More
8 Sets.of star delta starters (one or two starters as the case may be depending on number of cooling tower fans) for cooling tower fan motor

-

-

-

... More
Note: 1. All starters shall be provided with O/L relay with auto reset contact, single phasing preventor, ON/ OFF push button, indicating lamps, auxilliary relays for trip indication with reset push button. 2. In case the cooling tower is provided with 2 nos fans the panel should be provided with starters suitable for same. 3. Each outgoing feeder shall be provided with 3 nos CTs of appropriate rating with digital Ammeter and S/S.

-

-

-

... More
AHU Panel

-

-

-

... More
Supply, installation, testing and commissioning of Cubicle type wall/ floor mounted front operated panel board made of 2mm thick CRCA sheet duly treated in 7 tank process and powder coat painting with 100 Amp TPN Copper busbar suitable for operation on 415 Volt, 3 ph, 50 c/s supply conforming to the specifications. (Each starter shall be provided with necessary contactors, O/L relay, single phase preventor, ON/OFF push button & indication, space for VFD & necessary auxilliary contacts for remote operation and indication)

-

-

-

... More
Note: The AC contractor shall provide necessary relay/ contactor in the panel wherever necessary along with auto / manual mode selector switch in the outgoing feeder for AHU Fan to take fire input signal (Potential Free Contact).Cost shall be included in the panel price quoted by him.

-

-

-

... More
Incomer

-

-

-

... More
Incomer - 1 No 40 Amp TPN MCB, 10 KA with phase indicating lamp and instrument fuse.

-

-

-

... More
Outgoing

-

-

-

... More
1 No 40 Amp TPN MCB with by pass starter for AHU and space for VFD, ON/OFF push button and indicating lamps.

-

-

-

... More
2 Nos 16 Amp SPN MCB for power supply to actuator mechanism of fire damper, control transformer etc as required.

-

-

-

... More
Note : The rate should include cost of Power & control cabling in the AHU room on existing ladder type tray.The panel shall be provided with necessry relays to accepr fire signal and should be BMS compatible.

51

10460

-

... More
Make : EAP / AC Power / Zen Power / Balaji Electro Control/ or any CPRI approved

-

-

-

... More
Earthing

-

-

-

... More
Supply, installation, testing & commissioning of GI earth stripshot deep galvanised for interconnecting the earthing stations/panels/ DBs etc. of the following sizes in built up trenches /surface/wall complete with holes & fixing, jointing / terminating accessories as required.

-

-

-

... More
8 SWG GI Wire

1000

41

-

... More
25 x 3mm GI. Earth Strip

50

151

-

... More
50 x 6mm GI. Earth Strip

50

178

-

... More
Termination

-

-

-

... More
Cable termination

1

198038

-

... More
BMS SYSTEM

-

-

-

... More
20” LED Monitor with 1 TB HD , 8 GB RAM, Intel i7 processor, 2.66 GHz, 64 bit, windows 7 professional version licensed software – HP / DELL / Lenovo with 1KVA On/Line UPS with Voltage stabilizer & with 15 min. battery back up.

1

154233

-

... More
Supervisory Controller

1

87632

-

... More
Hardware dongle protected graphical software with required data-point license for the project.The license shall include two numbers concurrent web-client and automatic SMS-ing & Email-ing feature. The software shall comply to "BACnet Rrevision-10" for management station and the device profile of “BACnet Advanced Operator Workstation (B-AWS)

1

403107

-

... More
System backup software (firmware) and programing tools to be handed over time to time and finally before commissioning

-

-

-

... More
 A4 type Laser Printer – Canon / HP

1

53503

-

... More
BMS for Plant Room

-

-

-

... More
32bit microprocessor based Direct Digital controller or BACnet Building Controller (B-BC) complying to BACnet Revision 10 and supporting peer to peer communication with other DDCs or the Managemement Station or the hand-held operator terminal on true BACnet over Ethernet / IP basis. The controller shall support BACnet object types like - Load COntrol, Accumulator Pulse Converter, Event Log, Structured view etc. The analog input reading feature of the DDC shall comply to minimum 1microamps resolution. The digital outputs shall support max 4A resisitive or 2A inductive. It shall be possible to caluculate volt-free counter inpus upto 25Hz. The DDC shall support "UNIVERSAL INPUT OUTPUT" that can take care of passive sensors, active sensors, binary inputs, counters, analog output, and 24VDC binary outputs. A/D resolutions for universal inputs shall be 16bits and D/A resolution of analog outputs shall be 10bits. The controller shall be freely programmable with D-MAP programming language following CEN standard 1131 and all function blocks available in the programming library shall be made linked graphically in the management station software. Hi Side Controller should be suitable with monimum 200 I/O Points and meets as per I/O Summary Requirement.

1

452726

-

... More
Resistance type immersion temperature sensors for Chiller and Condenser In & Out and CT out

16

4002

-

... More
Water Flow Switches In Chiller & Condenser Outlet & In Decoupler Line shall be paddle type .

8

12979

-

... More
Outside Temp & RH Sensor

1

25814

-

... More
Tanks,Water Supply pumps etc

-

-

-

... More
LO / HI Level Switch

3

16473

-

-

-

-

... More
DCC controllers with DDC Panel for 1 Nos AHU Unit as per I/O summary mentioned in specification

51

74497

-

... More
Differential pressure Transmitter ( 0-200 Pa - 4-20mA) across the Air Handling Unit filters, for indicating the filter status / Belt Trone .

51

3486

-

... More
Duct Mounted combined Temperature and Humidity Sensor (for AHU )

51

23004

-

... More
Third Party System Integration

-

-

-

... More
Controller for 3rd party integration over MODBUS RTU OVER RS485.. The DDCs shall be peer to peer communicable without help of any master controller so that even in case of failure of any master controller the individual DDCs shall be able to talk to each other on the basis of BACnet reference. Refer IO summary for the number of soft points to be considered

1

96396

-

... More
Make : Schinder / Seimens / Johnson Control / Honneywell

-

-

-

... More
WIRING

-

-

-

... More
Supplying, installing, testing and commissioning of 1.5 Sq. mm 2 Core CU arm, FRLS quality PVC sheathed cables.

3000

128

-

... More
Supplying, installing, testing and commissioning of 1.5 Sq. mm 4 Core CU arm, FRLS quality PVC sheathed cables.

1500

162

-

... More
Supplying, installing, testing and commissioning of 1.5 Sq. mm 6 Core CU arm, FRLS quality PVC sheathed cables.

1000

172

-

... More
Supplying, installing, testing and commissioning of 1.5 Sq. mm 8 Core CU arm, FRLS quality PVC sheathed cables.

500

278

-

... More
Supplying, installing, testing and commissioning of 1.5 Sq. mm 2 Core signal cables.

1500

128

-

... More
Supplying, installing, testing and commissioning of 1.5 Sq.mm. 3 Core communication cables

200

155

-

... More
Supplying, installing, testing and commissioning of Cat 6 Communication cable

1000

85

-

... More
Supplying, installing, testing and commissioning of Heavy Guage PVC Rigid conduits of 25 mm dia complete with Bend & all accessories.

3000

95

-

... More
Make : PolyCab / KEI / RR / Havels

-

-

-

... More
Operation & maintenance (routine, preventive and comprehensive) of the high side & low side of the air-conditioning plant including all materials & manpower comprising of all the machinary, equipments installed in the AC Plant room including cooling towers and IBMS systems in Three shifts up to five years after commissioning and handing over as required as per maintenance schedule. Manpower details - 1. Supervisor - 1 No. 2. Operator cum technician (skilled) - 2 No. (including BMS operator) 3. Helper (Semi skilled) - 3

-

-

-

... More
1 st Year to 5th Year

5836636

1

-

... More
Less: Cost for Dismantleing and Buy back of existing equipment (Chiller, Pump, Cooling Tower, Pipes, Valves etc.)

6000000

1

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.