Indian Institute Of Science Tender
... More
The IISC has issued a formal invitation for competitive bids for the Indian Institute Of Science project, for Lighting Protection System For Main Building At Iisc in Bengaluru Urban, Karnataka, with an estimated contract value of Rs. 17,95,056. The bid opening date for this tender is 13-05-2025 and the last date for bid submission is 02-06-2025. Interested bidders for Indian Institute Of Science tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Indian Institute Of Science - IISC Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date13 May 2025
Closing Date2 Jun 2025
Tender Amount₹ 17,95,056
Costs
EMD
₹ 44,876Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Lighting Protection System For Main Building At Iisc
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_IISC_859879_1Tender No
IISc/Tender-ELE-02/2025-26Tender Authority
Indian Institute Of Science ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply installation testing and commissioning of roof conductor holder for ridge tiles:Adjustable width from 185-260 mm, Bottom part made of non-rusting stainless steel (V2A), Infinitely adjustable conductor holder, Conductor holder of polyamide, Fast installation using wing screw The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
50
1
50
... More
Supply installation testing and commissioning of 1 mtr vertical air system with mounting accessories • Suitable for high wind loads with Interception Rod Holder
• Material : Copper
• Diameter of rod: 15 mm, • Complies to the requirement of IEC 62561-2 The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
9
1
9
... More
Supply installation testing and commissioning of cross universal Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 made of SS. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2 Nos/expansion piece)
The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
37
1
37
... More
Supply installation testing and commissioning of expansion piece with connector for equalizing temperatrure related length changes . Necessary on conductors length at every 20 meter: 856 CU Flexible flat copper braid bond The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
16
1
16
... More
Supply installation testing and commissioning of Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 made of SS. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece). The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
33
1
33
... More
Supply installation testing and commissioning of Earthing Clip suitable to bond the air terminal/pipe/handrail of Ø 3/8 - 6" with 8-10mm dia round conductor.Clip element, bolts and tightening strap made of rust proof stainless steel (VA)
The rates shall include the dismantling of existing lightning arrestor systeml, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
5
1
5
... More
Supply installation testing and commissioning of Bridging cable: From flexible copper cable 16 mm², Coating: black, chlorinated India rubber mixture, With 1 mounting hole Ø 10.5 mm per attachment side, With 2 mounting holes Ø 7.3 mm per attachment side, For applications outside or inside suitable. The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
50
1
50
... More
Supply installation testing and commissioning of Connector, Rd 8−10 mm with pressure trough with 1 fix contact clamping screw, nut and serrated washer Including pre-mounted pressure sump, steel Conforms to the requirements according to DIN VDE 0185-305 (IEC 62305)
The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
50
1
50
... More
Down Conductor System:Supply installation testing and commissioning of 8 mm 100 microns coated Copper Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
260
1
260
... More
Supply installation testing and commissioning of conductor holder - Stainless steel Conductor holder:With Bottom section and conductor holder stainless steel (V2A)Bottom section with Ø 8.5 mm slot. Conductor holder @ 1 meter distance.
The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
260
1
260
... More
Supply installation testing and commissioning of Test Joint coppper Connector: Quick installation using hexagonal bolt M10X30 made of SS. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece). The rates shall include the dismantling of existing lightning arrestor system, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
12
1
12
... More
Supply installation testing and commissioning of Lightning counter - To count number of lightning strike & it can record the date and time of the lightning incident also tested according to VDE 0185-561-6 (IEC 62561-6). Usable both inside and outside due to its protection class of IP65. Direct mounting on the conductor or the PE conductor of the surge protection device. Long lifespan of the internal lithium batteries with LCD display. The rates shall include the dismantling of existing lightning arrestor terminal, suppply and installation of new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
1
1
1
... More
Earthing : Supply installation testing and commissioning of of 10 mm 250 microns Copper coated Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305).
The rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc. Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
320
1
320
... More
Supply installation testing and commissioning of Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 made of SS. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece).
The rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc.
Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
50
1
50
... More
Supply installation testing and commissioning of conductor holder - Stainless steel Conductor holder: With Bottom section and conductor holder stainless steel (V2A)Bottom section with Ø 8.5 mm slot. Conductor holder @ 1 meter distance.
The rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc. Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
12
1
12
... More
Supply installation testing and commissioning of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. The rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc. Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
2
1
2
... More
Supply installation testing and commissioning of UL Listed & CPRI Tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 14mm with copper coating thickness of 250micron tested as per IEC 62561-2 .
The rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc. Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
12
1
12
... More
Supply installation testing and commissioning suitable size Universal clamp made of SS to connect rod with flat conductor The rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc. Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
12
1
12
... More
Supply installation testing and commissioning of Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested. The rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc. Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
12
1
12
... More
Supply installation testing and commissioning of Heavy duty earth champer with the capacity of 5000kg load bearing capacity to ensure the safety of earthing system. The earthing system shall be ingerated with earth suface inclusing all materials and acessories etc. completeThe rates shall include the dismantling of existing earthing for lightning arrestor system, suppply and installation of earthing for new lightning arrestor system as mentioned above which includes all the resourses of manpower material and equipment, removal of required earth, pavers, Granite stones or any other materials and redo the same as per original for completion of works etc. Make:LPI/Indelec/OBO Bettermann/APS/DEHN/Furse/Erico/JMV/CAPE
12
1
12