Haryana Vidyut Prasaran Nigam Limited Tender

... More
The HVPNL has issued a formal invitation for competitive bids for the Haryana Vidyut Prasaran Nigam Limited project, for Creation Of 220 And 66 Kv Composite Transmission Line In Manesar And Rewari Area. in Panchkula, Haryana. The bid opening date for this tender is 30-12-2024 and the last date for bid submission is 25-03-2025. Interested bidders for Haryana Vidyut Prasaran Nigam Limited tender can download the important documents here to check the tender amount, scope of work, eligibility criteria and technical requirements.

Haryana Vidyut Prasaran Nigam Limited - HVPNL Tender

Works
Energy, Oil and Gas
Electrical and Electronics
Electrical Works
Eprocure
Opening Date30 Dec 2024
Closing Date25 Mar 2025
Tender AmountRefer Documents 
Notes
Download

AI Insights

Work Experience Requirements
... View More
The required prior work experience for the bidder is executing Turnkey Contracts of similar nature over the last 5 years. The bidder should provide a list of Turnkey Contracts executed as Prime contractor of similar nature over the last 5 years, along with details of other works in hand and contractual commitments. Additionally, the bidder should provide performance certificates issued by the Utilities, if applicable. Regarding the value and percentage of similar works completed, the bidder is required to provide proof of total annual turnover of Turnkey Contracts & supply of material & equipment of similar nature over the last 5 years. However, no specific monetary values or percentages are mentioned.

Costs

  • EMD

    ₹ 85,28,000
  • Document Cost

    ₹ 11,800
  • Tender Fee

    ₹ 1,180

Summary

Creation Of 220 And 66 Kv Composite Transmission Line In Manesar And Rewari Area.

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
iii) 220kV M/C 'MB' type Tower (KRR Design) classified as - Dry

4

-

-

... More
i)  220kV MB+12 mtr. type Special extension M/C tower(KRR Design)

1

-

-

... More
iv) Circuit Plate (set of 2)

45

-

-

... More
OPTICAL Interface Card S16.1 SFP (the quantities will be decided at the time of detail engineering)

8

-

-

... More
Conductor accessories for ACSR Zebra conductor i) Mid Span Compression Joint

59

-

-

... More
Hardware Fittings for ACSR Zebra conductor i)     Single suspension string

201

-

-

... More
ii) +3 mtr. Extn. only

1

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete (HSR Ref.No. 6.30.1)

810

-

-

... More
Construction of penetration macadam over prepared Base by providing a layer of compacted crushed coarse aggregate using chips spreader with alternate applications of bituminous binder and key aggregates and rolling with a smooth wheeled steel roller 8-10 tonne capacity to achieve the desired degree of compaction as per technical clause 505 of MORTandH specifications (HSR Ref.No. 17.28.1)

1080

-

-

... More
Detailed survey including GPR (Ground Penetration Radar survey), Laying, Testing & Commissioning of 66kV XLPE cable, 1200 sqmm Aluminium Milliken Conductor in Tre-foil formation with one spare cable for each circuit (12+4) including loops and riser in flat formation including Joint Bays, Manholes etc. and Civil works complete in all respect, on through rate basis as per technical specification in Open Cut/Directly Buried Method. (Tentative route length including loops and risers on both cable termination monopoles = 1320+25+25 = 1370 m) Note:- All the work for laying of cables till its commissioning shall be carried out under the supervision of the cable manufacturer and a certificate in this regard shall be issued by the concerned TS wing of HVPNL.

21920

-

-

... More
iii) 0.4 Sq. inch. Size ACSR Zebra Conductor

0.67

-

-

... More
i) +6 mtr. Extn. Only

11

-

-

... More
ii) +3 mtr. Extn. Only

1

-

-

... More
iv)  220kV M/C MD Type KRR Design with +3m extn. and Aux- cross arm (Set of 6)

1

-

-

... More
Supply and Installation of Cable Cleats and other miscellaneous material like all terminal connectors, clamps, Nuts & bolts etc for mounting of cables at cable termination monopoles as per technical specification

1

-

-

... More
c)    66kV D/C DC Type Tower(HSEB Design)

1

-

-

... More
d)    66kV S/C SA+0 Type Tower (HSEB Design)

12

-

-

... More
Supply, Erection, Testing & Commissioning of Outdoor End Termination kit for termination of cable on cable termination monopoles with all accessories as per technical specification suitable for above cable as per bidder’s standard design

16

-

-

... More
Conductor: AL-59 conductor size equivalent to ACSR Zebra

34.3

-

-

... More
ii) Dismantlement of existing ACSR Panther conductor complete with H/W fittings, insulators of the line and their transportation & proper stacking at designated Dedicated Store of HVPNL.

7.2

-

-

... More
Any other item/items left out but required to complete the work

1

-

-

... More
- Wet

5

-

-

... More
i)  220kV MD+9m type Special extension M/C tower (KRR Design)

2

-

-

... More
vi) 66kV M/C 'MD' type Tower (KRR Design) classified as - Dry

5

-

-

... More
Supply of following Tower accessories i) Danger Plate

71

-

-

... More
Surface Drain Surface dressing of the ground including removing vegetation and in-equalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. All kinds of soil (HSR Ref.No. 4.4)

459

-

-

... More
Design, Vetting, Fabrication, Supply & Erection including its Foundation of following Monopoles with foundation at Ground (Raft/Pier/Pile) with all parts like cross arms, bolts & nuts, step bolts, U-bolts, D-shackle, Hanger etc. with RL-2, WZ-5, Normal Span length of 200M for ACSR Zebra Conductor. 66KV M/C MD (30-60D)/DE(0-15D)_BXA@13M Cable Termination Monopole suitable for termination of 66KV D/C 1200 sqmm Single Core Aluminum Conductor Milliken type XLPE Insulated cable (6+2 configuration) with following provisions:- i)  66kV D/C cable termination at bottom double circuit arrangement. ii) 8 No. cables along with 6 No. LAs shall be mounted for D/C cable termination.

2

-

-

... More
c)Vibration damper for conductor

1116

-

-

... More
iii) +6 mtr. Extn. only

1

-

-

... More
iii) +6 mtr. Extn. only

2

-

-

... More
ii) 220kV D/C DB+0 TATA Design Tower

1

-

-

... More
e)    66kV S/C SC+0 Type Tower (HSEB Design)

3

-

-

... More
Transportation & Erection only of Fiber optic Approach cable, 48 fiber (DWSM) along with PLB HDPE Ducts of suitable size & strength and all accessories for 400kV S/Stn., Sohna Road Gurugram (supply not in the scope of successful bidder).

1

-

-

... More
iii) Vibration damper for conductor

1692

-

-

... More
i) 220 kV D/C Gantry (TATA Design) (Rate of construction of only one pit as per Electrical BOQ Part-B Sr.No-2 Civil Foundation only)

1

-

-

... More
Complete Earthing material Set for earthing at all cable terminations, cable joints (as per technical specification)

1

-

-

... More
Detailed survey, supply, laying, testing & commissioning of armored underground Fiber Optic cable (48F) in PLB HDPE Ducts of suitable size & strength along with accessories (as per requirement) in above mentioned sections, installation of joint boxes, interfacing with existing OPGW on through rate basis as per technical specification. From Proposed TL no. 29A to FODP 66kV IE Dharuhera

1.5

-

-

... More
ii) Extra Cross Arm (set of 6)

1

-

-

... More
ii) +6 mtr. Extn. Only

16

-

-

... More
ii)    +3 mtr. Extn. only

1

-

-

... More
ERECTION ONLY OF FOLLOWING WIDEBAND COMMUNICATION RELATED MATERIAL AVAILABLE WITH TS WING, MANESAR AGAINST REC-263 TO BE INSTALLED AS PER REQUIREMENT : Wideband Telecom Equipment (not to be supplied) Base Equipment (Common cards, Cross connect/control cards, optical base cards, power supply cards, power cabling, other hardware and accessories including sub racks, patch cord, DDF etc. fully equipped excluding (ii) below to be installed at 220KV

1

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc. (HSR Ref.No. 6.30.2)

1296

-

-

... More
iii) 220kV M/C 'MD' type +9 , +15 special extention Tower (KRR Design) classified as - Dry

4

-

-

... More
i) 220kV MC type towers (KRR Design)

1

-

-

... More
ii) Aux- cross arm only

1

-

-

... More
iv) Circuit Plate (set of 2)

162

-

-

... More
66kV M/C MC type towers (KRR Design)

2

-

-

... More
Providing and laying of premix sand seal coat premixed in continuous type HMP of appropriate capacity not less than 75 tonnes/ hours using specified fine aggregates and penetration grade bitumen @0.68 kg/sqm laid to specified levels, grade and cross fall complete as per technical clause 511 of MORT&H specifications. (HSR Ref.No. 17.51)

1080

-

-

... More
Supply & Erection / laying of 160 MM HDPE pipe required for various crossings as per detail at sr.no.55 above.

960

-

-

... More
ii) +6 mtr. Extn. Only

1

-

-

... More
Gigabit Ethernet (Layer 2) Interface (min 2 nos)

1

-

-

... More
Painting two coats excluding priming coat with synthetic enamel paint in all shades on new wood work or metallic or plastered or concrete surfaces to give an even shade. (HSR Ref.No. 11.78)

76.6

-

-

... More
ii)   Single suspension pilot string

18

-

-

... More
ii)  +3 mtr. Extn. only

1

-

-

... More
Hardware set for above 48 Fiber OPGW fiber optic (equivalent to Earth wire: 7/3.15mm in all respect) cabling including all cable fittings & accessories except joint box.

5

-

-

... More
Integration of the Equipment with existing network

1

-

-

... More
- Wet

1

-

-

... More
vi) Anti climbing device

71

-

-

... More
Design, Vetting, Fabrication, Supply & Erection including its foundation of 220kV D/C DD type Dead-end Monopole (PD 30° – 60°/0-15° DE)for ACSR Zebra having Bottom Crossarm height 11mtr. The Monopole shall be designed for span length of 175 mtr with foundation (Raft/Pier/Pile) as per Technical specification. The monopoles are specially required for re-arrangement work of existing 220kV D/C Badshahpur-IMT, Manesar line to facilitate underneath crossing with 220kV LILO lines to 220kV S/Stn. 75-A. Therefore, the special provision for continuity of Earthwire/OPGW shall be made through center of the monopoles at any suitable point, for which Electrical clearance from nearby both side conductors at the crossing span shall be ensured at the time of detailed engineering of the monopoles which may necessitate increased length of cross-arms.

2

-

-

... More
Supply, Erection, Testing & Commissioning of 60 kV Polymeric Lightning Arrestor on cable termination monopoles with insulating base, Terminal connectors, surge counter etc complete in all respects as per Latest relevant standard and technical specification of HVPNL.

12

-

-

... More
ii) 220kV M/C 'MA' type Tower (KRR Design) classified as - Dry

5

-

-

... More
ii) Number Plate

38

-

-

... More
Ethernet Interface 10/100 BaseT with Layer-2 switching (min 8 interfaces per card)

2

-

-

... More
ii) 220kV D/C DD+0 TATA Design

1

-

-

... More
Construction of tower foundations as per HVPNL Drgs & Specifications for 0 to 6Mtr. extn. including excavation, concreting, supply and placement of steel reinforcement and backfilling complete in all respect. i) 220kV D/C 'DD' type Tower (TATA Design) classified as - Dry

4

-

-

... More
Dismantlement and repairing of surface drain and road carpet area adjacent along the 8 mtr HT corridor: Excavation for roadway in soil using manual means including carrying of cut earth to embankment site with all lifts and lead up to 50 m, as per technical clause 301 of MORT&H specifications (HSR Ref.No. 17.9.1)

700.4

-

-

... More
i) 220kV MB+9 mtr. type Special extension M/C tower (KRR Design)

1

-

-

... More
Transportation & Erection only Hardware set for above 48 Fiber OPGW fiber optic (equivalent to Earth wire: 7/3.15mm in all respect) cabling including all cable fittings & accessories except joint box (supply not in the scope of successful bidder).

6

-

-

... More
i) +6 mtr. Extn. Only

1

-

-

... More
Mandatory Spares OPTICAL Interface Card/SFP S16.1 SFP (the quantities will be decided at the time of detail engineering)

1

-

-

... More
iii) Dismantlement of existing Earth wire along with Hardware fittings and accessories of line and its transportation, proper stacking at any dedicated store of HVPNL.

7.2

-

-

... More
Mandatory spares: (Telecom equipment) Optical Interface Cards/SFP: S16.1 SFP (the quantities will be decided at the time of detail engineering)

1

-

-

... More
Equipment Cabinet with DDF and all installation accessories

1

-

-

... More
iii) Phase Plate (set of 3)

70

-

-

... More
b)   120 KN

414

-

-

... More
S4.1 SFP (the quantities will be decided at the time of detail engineering)

1

-

-

... More
i) 220kV D/C DD+0 TATA Design ( Terminal tower of 220kV S/Stn. Sector-75A)

2

-

-

... More
Fabrication and supply of tower part with stubs, bolts & nuts, step bolts, U-bolts, hangers, D-shackle etc. of following type of towers. 66kV M/C MA type towers (KRR Design)

19

-

-

... More
iii)  Aux-cross-arm only

2

-

-

... More
Integration of the Equipment with existing network

1

-

-

... More
Pre-Connectorized Optical Fibre Patch Cords (10 Mtrs.)-Pack of six Patch cords

1

-

-

... More
Supply of 66kV XLPE cable, 1200 sqmm Aluminium Milliken Conductor as per technical specification

22880

-

-

... More
i) +3 mtr. Extn. Only

1

-

-

... More
Transportation & Erection only of Joint Box 48F fiber OPGW to OPGW (2way joint Boxes) (as applicable) (Quantity may varies as per drum schedule of OPGW) (supply not in the scope of successful bidder).

2

-

-

... More
Indicative quantity of supply, Erection, Testing & Commissioning of XLPE cable straight through joint kit for each cable complete with all accessories suitable for above 66kV cable (to be decided as per requirement)

32

-

-

... More
Construction of tower foundations as per HVPNL Drgs & Specifications for 0 to 6Mtr. extn. including excavation, concreting, supply and placement of steel reinforcement and backfilling complete in all respect. i) 66kV D/C 'DB' type Tower (KRR Design) classified as - Dry

1

-

-

... More
Transportation & erection of Towers /Gantry in 220kv line work at sr. no (c) from HVPNL DD store Khera/Ballabgarh to Proposed tower locations of line to 220kV S/stn. Sector-75A i)  220kV D/C gantry

2

-

-

... More
Optical Interface Cards/SFP: S4.1 SFP (the quantities will be decided at the time of detail engineering)

4

-

-

... More
Fabrication and supply of following tower parts with stubs, bolts & nuts, step bolts, U-bolts, hangers, D-shackle etc. of following Designs: i) 220kV MA type towers (KRR Design)

5

-

-

... More
Hardware Fittings for AL-59 conductor equivalent to ACSR Zebra (for line work at a)) i)    Single ‘I’ Suspension String

60

-

-

... More
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface Water thinnable cement primer (HSR Ref.No. 11.67.1)

76.64

-

-

... More
Ethernet Interface 10/100 BaseT with Layer-2 switching (min 8 interfaces per card)

1

-

-

... More
Indicative quantity for supply, Erection, Testing & Commissioning of three-phase Link Box without SVL for each cable (to be decided as per requirement)

6

-

-

... More
Tributary cards E1 Interface card (Min. 32 interfaces per card)

4

-

-

... More
iii) +6 mtr. Extn. only

1

-

-

... More
Providing, laying and rolling of open - graded premix surfacing of 20 mm thickness composed of crushed stone aggregates of specified grading premixed in a continuous type of hot mix plant of appropriate capacity not less not less than 75 tonne per hour, with bituminous binder VG - 10 @ 1.46 kg per sqm, laid with Paver Finisher Mechanical and rolling with a smooth wheeled roller 8-10 tonne capacity, finished to required level and grades complete as per technical clause 510 of MORT&H specifications (HSR Ref.No. 17.33.1)

1080

-

-

... More
66kV M/C MB type towers (KRR Design)

12

-

-

... More
i)  +6 mtr. Extn. Only

6

-

-

... More
66kV D/C DB type towers (KRR Design)

2

-

-

... More
i) 220kV MD type towers (KRR Design)

3

-

-

... More
OPGW (24 fiber) (DWSM, G.652D) (equivalent to Earth wire: 7/3.15mm in all respect)

21.12

-

-

... More
Indicative quantity for supply, Erection, Testing & Commissioning of single-phase Link Box without SVL for each cable (to be decided as per requirement)

16

-

-

... More
iii) 66kV M/C 'MA' type Tower (KRR Design) classified as - Dry

14

-

-

... More
Earthing of 60 kV Polymeric Lightning Arrestor & XLPE Cables to be installed on the terminal monopoles (66kV M/C monopoles) including its all allied material.

1

-

-

... More
iii) Phase Plate (set of 3)

168

-

-

... More
FODP 48F: Indoor type, rack mounted with FCPC coupling and pig tails (5mtrs. Each)

6

-

-

... More
i) Dismantlement of following design of towers including its transportation: - The dismantlement of tower shall also include dismantlement of Stub concrete upto a depth of 1M (one meter) from Natural Ground level, back filling, compaction and clearing the site of debris as per satisfaction of field office along with their transportation & proper stacking at any dedicated store of HVPNL. a)    66kV D/C DA Type Tower(HSEB Design)

6

-

-

... More
v) Bird guard (set of 3)

76

-

-

... More
Fiber optic Approach cable, 48 fibre (DWSM) along with PLB HDPE Ducts of suitable size & strength and all accessories as applicable for 220kV Mau.

1

-

-

... More
Ethernet Interface 10/100 Base T with Layer-2 switching (Min. 8 interfaces per card)

4

-

-

... More
Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Thermo- Mechanically Treated bars of grade Fe-500D or more. (HSR Ref.No. 6.33.6)

9180

-

-

... More
v) Anti climbing device

35

-

-

... More
b)    66kV D/C DB Type Tower(HSEB Design)

6

-

-

... More
Transportation of following material from DD Store Khera and its erection for stringing on portion of line between TL no. 04 to TL no 29 of LILO of 220kV D/C Sohna Road-Panchgaon (PGCIL) D/C line i) AL-59 conductor size equivalent to ACSR Zebra.

56.2

-

-

... More
ii) Repair sleeves

7

-

-

... More
Providing and fixing at or near ground level precast cement concrete in kerbs, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand), including the cost of required centering, shuttering complete. 1:1½:3 (1 Cement: 1½ coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size). (HSR Ref.No. 6.39.1)

11.68

-

-

... More
v) 220kV M/C 'MD' type Tower (KRR Design) classified as - Dry

3

-

-

... More
Demolishing R.C.C. work by mechanical means and stockpiling at designated locations and disposal of dismantled materials up to a lead of 1 kilometre, stacking serviceable and unserviceable material separately including cutting reinforcement bars (PCC+RCC) (HSR Ref.No. 5.26)

217.96

-

-

... More
66kV M/C MD type towers (KRR Design)

7

-

-

... More
Supply of earthing of Towers/ Gantry i) Pipe type

71

-

-

... More
Detailed survey including GPR (Ground Penetration Radar survey), Laying, testing & Commissioning of 66 kV XLPE cable, 1200 sq mm aluminium milliken conductor in tre-foil formation with one spare cable for each circuit (12+4) inclduing loops and riser in flat formation including joint bays, manholes etc. andcivl works complete in all respect, on through rate basis as per techncial specifciation in trenchless HDD method (Tentative route length =60 m) Note: The erection/ laying of HDPE pipe is to be quote at sr.no.56) below for road crossing only.

960

-

-

... More
Supply and Erection of Warning Tape

2760

-

-

... More
Construction and installation of RCC route/Joint Bay markers as per Drg. No. HCD/TS-1417 complete in all respect including supply of all construction material i.e. cement, steel, aggregates and water or any other type of material required to complete the job etc

62

-

-

... More
- Wet

1

-

-

... More
Indicative quantity for supply, Erection, Testing & Commissioning of single-phase Link Box with SVL for each cable (to be decided as per requirement)

16

-

-

... More
- Wet

2

-

-

... More
Transportation from DD store Khera, HVPNL & Erection of Tower accessories i) Danger Plate

35

-

-

... More
66kV Anti-Fog type Disc Insulator or Silicon Rubber Polymer Insulator strings* i) 70 kN

235

-

-

... More
iii) 220kV M/C MD Type KRR Design.

2

-

-

... More
Joint Box 48 fiber (3 way) OPGW to OPGW (as applicable)

7

-

-

... More
Conductor: ACSR Zebra

78.05

-

-

... More
iv) 66kV M/C 'MB' type Tower (KRR Design) classified as - Dry

9

-

-

... More
Dewatering of subsoil water for lowering of water table to enable excavation of earth, concreting for foundations/stub and backfilling, by boring of tube wells or deploying well point system so that continuous lowering of water table is made till completion of work, without disturbing the soil characteristics. The rate shall include all type of expenditure for required dewatering arrangements and irrespective of type of tower including extensions if any.

2

-

-

... More
Tributary cards E1 Interface card (Min. 32 interfaces per card)

1

-

-

... More
Providing and laying in position machine batched and machine mixed design mix M25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineerin-charge. All works up to plinth level (HSR Ref.No. 6.25.1)

174.76

-

-

... More
Ethernet Interface 10/100 Base T with Layer-2 switching (Min. 8 interfaces per card)

1

-

-

... More
Gigabit Ethernet (Layer 2) Interface (min. 2 nos.)

1

-

-

... More
Pre-Connectorized Optical Fiber Patch Cords (10 Mtrs.) -Pack of six Patch cords

1

-

-

... More
Dismantled or replacement/Refitting of street or road light including all respect (M.R)

5

-

-

... More
Joint Box (24 fiber) OPGW to FOAC

5

-

-

... More
Construction of tower foundations as per HVPNL Drgs & Specifications for above 06 Mtr. extn. including excavation, concreting, supply and placement of steel reinforcement and backfilling complete in all respect. ii) 220kV M/C 'MB' type +9,+12 special extention Tower (KRR Design) classified as - Dry

2

-

-

... More
Road Marking with Hot Applied Thermoplastic Compound with Reflectorising Glass Beads on Bituminous Surface Providing and laying of hot applied thermoplastic compound 2.5 mm thick including Reflectorising glass beads @ 250 gms per sqm area, thickness of 2.5 mm is exclusive of surface applied glass beads as per IRC:35 .The finished surface to be level, uniform and free from streaks and holes. (HSR Ref.No. 34.26)

27

-

-

... More
Equipment Cabinet with DDF and all installation accessories

2

-

-

... More
vi) Bird guard (set of 3)

48

-

-

... More
iv) OPGW 24 F

0.34

-

-

... More
Software

1

-

-

... More
iii) +6 mtr. Extn. only

1

-

-

... More
66kV D/C DD type towers (KRR Design)

2

-

-

... More
ii) Number Plate

71

-

-

... More
Detailed Survey

13

-

-

... More
i) +3 mtr. Extn. Only

1

-

-

... More
ii)  120 KN

492

-

-

... More
iii) Vibration damper for conductor

864

-

-

... More
Fiber optic Approach cable, 24 fiber (DWSM) along with PLB HDPE Ducts of suitable size & strength and all accessories

5

-

-

... More
(iv) Hardware Fittings for AL-59 conductor a) Single ‘I’ Suspension String

144

-

-

... More
Fabrication and supply of following tower parts with stubs, bolts & nuts, step bolts, U-bolts, hangers, D-shackle etc. of following Designs: i) 220kV MD type towers (KRR Design) without stubs

2

-

-

... More
Water Bound Macadam Grading I with crushable screenings Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing, rolling with 3 wheeled steel/ vibratory roller 8-10 tonnes in stages to proper grade and camber, applying and brooming requisite type of screening/ binding Materials to fill up the interstices of coarse aggregate, watering and compacting to the required density complete as per technical clause 404 of MORT&H specifications (HSR Ref.No. 17.22.3)

350.21

-

-

... More
iv) 220kV M/C 'MC' type Tower (KRR Design) classified as - Dry

1

-

-

... More
c)Single Tension string

414

-

-

... More
Construction of fencing around the 66kV M/C 'MD' (30-60D)/DE(0-15D_-BXA@13M Cable termination Monopole complete in all respect including excavation,back filling of earth, supply of all fencing & construction material i.e. cement, steel, aggregates and water or any other type of material required to complete the job etc.

40

-

-

... More
Providing and laying in position ready mixed plain cement concrete, with cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, excluding the cost of centering, shuttering and finishing, including cost of curing, admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer-in-charge. All works above plinth and up to floor IV level : M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) (HSR Ref.No. 6.22.1.2)

43.2

-

-

... More
(iii) 220kV Bus Post Insulator

24

-

-

... More
Joint Box (48 fiber) OPGW to FOAC (as applicable)

2

-

-

... More
Hardware set for above 24 Fiber OPGW fiber optic (equivalent to Earth wire: 7/3.15mm in all respect) cabling including all cable fittings & accessories except joint box.

22

-

-

... More
(ii) 220kV Silicon Rubber Polymer Insulator strings from HVPNL DD store Khera a)    70 KN

246

-

-

... More
- Wet

1

-

-

... More
Base Equipment (Common cards, Cross connect/control cards, optical base cards, power supply cards, power cabling, other hardware and accessories including sub racks, patch cord, DDF etc. fully equipped excluding (ii) & (iii) below to be installed at 66kV IE Dharuhera and 66kV Dharuhera

2

-

-

... More
Accessories for AL-59 conductor equivalent to ACSR Zebra i) Mid Span Compression Joint

23

-

-

... More
Indicative quantity of supply, Erection, Testing & commissioning of 1 x 240mm2, Copper conductor PVC insulated, Unarmored, 3.3kV Sheath Bonding cable (to be decided as per requirement)

400

-

-

... More
v) 66kV M/C 'MC' type Tower (KRR Design) classified as - Dry

1

-

-

... More
Transportation & Erection only for OPGW (48 fiber) (DWSM, G.652D) (supply not in the scope of successful bidder) (equivalent to Earth wire: 7/3.15mm in all respect) on following portions: - (i)    Tower No. 1 to Gantry of 400kV Sohna Road S/Stn., (400kV Sohna Road Line) = 339M (ii)   Tower No. 21A to Tower No. 7 = 830M (iii)  Tower No. 13 to tower No. 29 = 3069M (iv) Tower No. 29 to Tower No. 30 = 121M (v)  Tower No. 30 to Tower No. 46 = 2542M

5.31

-

-

... More
220kV DD type TATA Design Towers (Required for re-arrangement work of existing 220kV D/C Badshahpur-IMT, Manesar line to facilitate underneath crossing with 220kV LILO lines to 220kV S/Stn. 75-A).

2

-

-

... More
Joint Box 48F fiber OPGW to OPGW (2way joint Boxes) (as applicable) (Quantity may varies as per drum schedule of OPGW)

1

-

-

... More
i) +3 mtr. Extn. Only

3

-

-

... More
Furnishing bore log data

13

-

-

... More
ii) +6 mtr. Extn. Only

1

-

-

... More
OPGW (48 fiber) (DWSM, G.652D) (equivalent to Earth wire: 7/3.15mm in all respect)

4.71

-

-

... More
Dismantlement of following material for re-arrangement work of existing 220kV D/C Badshahpur-IMT, Manesar line to facilitate underneath crossing with 220kV LILO lines to 220kV S/Stn. 75-A. The dismantlement shall also include its transportation and proper staking at any dedicated store of HVPNL. i) 220kV D/C DA+0 TATA Design Tower

1

-

-

... More
Indicative quantity for supply, Erection, Testing & Commissioning of three-phase Cross bonding Link Box with SVL for each cable (to be decided as per requirement)

6

-

-

... More
ii) 66kV D/C 'DD' type Tower (KRR Design) classified as - Dry

1

-

-

... More
Joint Box 24F fiber OPGW to OPGW (2way joint Boxes) (as applicable) (Quantity may varies as per drum schedule of OPGW)

7

-

-

... More
b) Repair sleeves

13

-

-

... More
iv)  Double Tension string

24

-

-

... More
Gigabit Ethernet (Layer 2) Interface (min 2 nos)

1

-

-

... More
Dismantlement of existing earthwire (7/3.15mm) of 220kV Badshahpur-Panchgaon line along with its fittings and accessories of line and its transportation, proper stacking at any dedicated store of HVPNL, for facilitating the erection of OPGW on existing line by the successful bidder

15

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform (HSR Ref.No. 6.30.3)

405

-

-

... More
iv) Double Tension string

72

-

-

... More
ii) 120 kN

621

-

-

... More
ii)    Single suspension pilot string

34

-

-

... More
Network manager System craft Terminal: Hardware

1

-

-

... More
iii)  Single Tension string

300

-

-

... More
Tributary cards: E1 Interface card (Min. 32 interfaces per card)

2

-

-

... More
ii)  +3 mtr. Extn. only

2

-

-

... More
Gigabit Ethernet (Layer 2) Interface (min. 2 nos.)

2

-

-

... More
i)  220kV MB type towers (KRR Design)

4

-

-

... More
ii) Repair sleeves

18

-

-

... More
b) Single suspension pilot string

108

-

-

... More
i)  220kV MD+15m type Special extension M/C tower (KRR Design)

2

-

-

... More
220kV Silicon Rubber Polymer Insulator strings i)   70 KN

78

-

-

... More
Tributary cards: E1 Interface card (Min.32 interfaces per card)

1

-

-

... More
(v) Conductor accessories of AL-59 conductor a) Mid Span Compression Joint

44

-

-

... More
iii)   Single Tension string

621

-

-

... More
- Wet

3

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.