Delhi State Cancer Institute Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Costs
EMD
Refer DocumentsDocument Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_DSCI_207185_1Bid Award Id
ViewTender No
04/EE(E)/DSCI/2021-22Tender Authority
Delhi State Cancer Institute ViewPurchaser Address
-Website
http://http://www.dsci.nic.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Air Qty. = 5000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW. ,Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 2500 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 1750 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 5500 CFM , Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm ,Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
2
-
-
Air Qty. = 3500 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
3
-
-
Air Qty. = 2000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW, Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor,
1
-
-
Air Qty= 2200 CFM ,Static Pressure= 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor= Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor
1
-
-
Air Qty = 10000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 3.7 KW., Fan Dia = 910mm (Approx.)Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 4000 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
6
-
-
Air Qty. = 1500 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 3000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
4
-
-
Supply,installation,testing and commissining of direct driven Tube axial flow fans suitable for installing in any position in Horizontal or vertical with adjustable pitch blade, MS / high duty GSS long Casing , cast aluminium alloy impeller complete with TEFC Sq. Cage Induction type IE 2 motor suitable for 415 volts ± 10%, 50Hz ± 3 %, 4 Pole, three phase A.C supply of class "F" insulation motor's winding with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep with 25 mm slack at Outlet etc..The fans shall be as per specifications & tender drawing of following capacity:-
1
-
-
Air Qty. = 7250 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.).Flow Direction: Impeller to Motor.
2
-
-
Air Qty. = 6350 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 3.7 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 5000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 2500 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 1750 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 5500 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
2
-
-
Air Qty. = 3500 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
3
-
-
Air Qty. = 2000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.)Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 2200 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
1
-
-
Air Qty.= 10000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm ,Motor = Not exceed 3.7 KW., Fan Dia = 910mm (Approx.)Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 4000 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
7
-
-
Air Qty. = 1500 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
1
-
-
Air Qty. = 3000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor
3
-
-
Supply,installation,testing and commissining of direct driven Tube axial flow fans suitable for installing in any position in Horizontal or vertical with adjustable pitch blade, MS / high duty GSS long Casing , cast aluminium alloy impeller complete with TEFC Sq. Cage Induction type IE 2 motor suitable for 415 volts ± 10%, 50Hz ± 3 %, 4 Pole, three phase A.C supply of class "F" insulation motor's winding with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep with 25 mm slack at Outlet etc..The fans shall be as per specifications & tender drawing of following capacity:-
-
-
-
5000 CFM / 20 MMWG / 2.2 KW (Admin Block) Flow Direction: Impeller to Motor
7
-
-
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
-
-
-
Thickness 0.63 mm sheet
90
-
-
Thickness 0.80 mm sheet
90
-
-
Thickness 1.00 mm sheet
25
-
-
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
-
-
-
Thickness 0.63 mm sheet
90
-
-
Thickness 0.80 mm sheet
85
-
-
Thickness 1.00 mm sheet
15
-
-
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU room
-
-
-
Damper
8
-
-
Actuator
8
-
-
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
6
-
-
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
6
-
-
Supplying & fixing of 18 G thick Aluminium extruded powder coated Fresh / Exhaust air weather protected louvers with bird screen type i.e. louvers blade shall be at 45° inclination with blade pitch 40 mm (with Aluminium frames if required) for ventilation with 12G GI wire mesh. as per specification and sizes will be as per tender drawing mentioned.
5
-
-
Supply,Installation, testing & commissioning of Gravity shutters made of 18G GI frame work & 22G GI blades with galvanised spindles & brass bushes. Blades shall be maximum 6” wide edges will be sealed with felt or flexible vinyl. The blades shall be pivoted using steel pivot pins and linked to open for 90 degrees without rattling and llow leakage closing mechanism and suitable for wall mouting / Duct Mounted with necessary framework.
5
-
-
Supplying, installation testing and commissioning of outdoor type MV panel board of cubicle type , compartmentalised design fabricated from minimum 2 mm thick CRCA sheet having necessary cable alley, powder coated through seven tank precess facility fro prickling and dgreasing, including connections and interconnection as per specifications complete with following accessories as required complete with mountings, interconnections, earthing etc as required. Note: The AC contractor shall provide fire shunt relay contact in his panel wherever necessary along with auto / manual mode selector switch in the outgoing feeder to take fire input signal (Potential Free Contact).Cost shall be included in the panel price quoted by him. Note: The AC contractor shall provide fire shunt relay contact in his panel wherever necessary along with auto / manual mode selector switch in the outgoing feeder to take fire input signal (Potential Free Contact).Cost shall be included in the panel price quoted by him. Incomer: 1 Nos. 63 AMP MCCB TP + NL 25 KA incoming Thermal magnetic with O/L, S/C and E/f protection, 1 No. Digital Multifunction meter and CTs of rating 63/5A. 3 Nos.phase indicating lamps. Main bus bar rated at 100 amps TPN, 25 KA with heat shrinkable sleeve and shall be of aluminium. Outgoing: 7 Nos. 9 Amps MCB DOL Starter for Supply Fan's Motor, over load relay with built in single phasing protection. The compartment shall contain an indicating lamp with MCB for ‘ON’ status. 6 Nos. 9 Amps MCB DOL Starter for Exhaust Fan's Motor, over load relay with built in single phasing protection. The compartment shall contain an indicating lamp with MCB for ‘ON’ status. All outgoing feeder shall have following accessories. 02 Nos. ON/OFF indicating lights with protection switch.
-
-
-
Note: a. Potential free contact shall be provided with necessary modbus protocol compatible to BMS and energy management system.
1
-
-
Emergency Panel for smoke extraction system & Liftwell Pressurization Supplying, installation testing and commissioning of outdoor type MV panel board of cubicle type , compartmentalised design fabricated from minimum 2 mm thick CRCA sheet having necessary cable alley, powder coated through seven tank precess facility fro prickling and dgreasing, including connections and interconnection as per specifications complete with following accessories as required complete with mountings, interconnections, earthing etc as required. Note: The AC contractor shall provide fire shunt relay contact in his panel wherever necessary along with auto / manual mode selector switch in the outgoing feeder to take fire input signal (Potential Free Contact).Cost shall be included in the panel price quoted by him. Incomer: 1 Nos. 160 AMP MCCB TP + NL 25 KA incoming Thermal magnetic with O/L, S/C and E/f protection, 1 No. Digital Multifunction meter and CTs of rating 160/5A. 3 Nos.phase indicating lamps. Main bus bar rated at 200 amps TPN, 25 KA with heat shrinkable sleeve and shall be of aluminium. Outgoing: 26 Nos. 9 Amps MCB DOL Starter for Supply Fan's Motor, over load relay with built in single phasing protection. The compartment shall contain an indicating lamp with MCB for ‘ON’ status. 20 Nos. 9 Amps MCB DOL Starter for Exhaust Fan's Motor, over load relay with built in single phasing protection. The compartment shall contain an indicating lamp with MCB for ‘ON’ status. All outgoing feeder shall have following accessories. 02 Nos. ON/OFF indicating lights with protection switch.
-
-
-
Note: a. Potential free contact shall be provided with necessary modbus protocol compatible to BMS and energy management system.
1
-
-
POWER CABLING Supply, Installation, Testing and Commissioning of following XLPE insulated and PVC sheethed XLPE Power Cable of 1.1 kV grade Al./Cu Coductor Armoured cable of following sizes in existing Cable Tray or Surface mounted with suitable clamps, saddles, fixing bolts including connecting testing and commissioning and complete the work as per drawing and specifications.
-
-
-
3.5C x 95 Sq. mm al. ar. Cable (PANEL SUPPLY)
50
-
-
3.5C x 25 Sq. mm al. ar. Cable (PANEL SUPPLY)
25
-
-
3C x 4 Sq. mm Copper Cable (FOR FAN SUPPLY)
1200
-
-
CONTROL CABLING Supply & Laying ,testing and commissioning of control cum transmission wiring of Copper conductor shielded cable for looping between indoor & outdoor VRF system & to main Central remote controller system
-
-
-
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (for Damper/Actuator)
700
-
-
Earthing Wires. Providing and fixing 6 SWG dia G.I. wire on surface or in recess
for loop earthing along with existing surface/ recessed conduit/
submain wiring/ cable as required.
60
-
-
Cable Trays Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
-
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
60
-
-