Development Of Taluk Head Quarter Hospital, Chirayinkeezhu - Renovation Of Existing Heritage Building (sh Electrical Works)

Documents
Don't have sufficient eligibility, BG funds or resources?
We will help you to find the right match for FREE.
BOQ Items
ItemQuantityUnitsRateAmount
... more
Wiring
-- -
... more
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C
62point- -
... more
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
3point- -
... more
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2x1.5 sq.mm + 1x1.5 sq.mm earth wire
259metre- -
... more
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
540metre- -
... more
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
108metre- -
... more
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
5metre- -
... more
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
5metre- -
... more
1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
5metre- -
... more
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
24each- -
... more
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
5each- -
... more
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or inrecess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 ampsmodular switch, connection etc. as required. (For light plugs to be used in non residentialbuildings).
20each- -
... more
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
8each- -
... more
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden blockincluding connection etc as required.
29each- -
... more
Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
66each- -
... more
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standardlength (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc.as required.
24no- -
... more
Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
5each- -
... more
Supplying and fixing brass batten/ angle holder including connection etc. as required.
1each- -
... more
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
30point- -
... more
Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
23each- -
... more
MCB and DB
-- -
... more
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required
1each- -
... more
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required
1each- -
... more
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator 16 way, Double door
1each- -
... more
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
32each- -
... more
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
1each- -
... more
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
22each- -
... more
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required
1each- -
... more
MV Cable laying
-- -
... more
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
15metre- -
... more
MV Cable jointing and end termination
-- -
... more
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2X 35 sq. mm (32mm)
2set- -
... more
Earthing
-- -
... more
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providingmasonry enclosure with cover plate having locking arrangement and watering pipe etc. withcharcoal/ coke and salt as required
2set- -
... more
LMR Items
-- -
... more
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5C X 35sq.mm Al Cable
15metre- -
... more
Supply and drawing and of following unarmoured flexible power cable conductor of best conductivity copper stranded conductor, PVC insulated, 1.1kV grade strictly conforming to IS:1554 (Part-I) 1964 of the following sizes in surface/ recessed medium class PVC conduit and making good the damages colour washing etc as required. and instructed by the engineer in charge. 1Cx10 Sq.mm Copper Flexible Cable
276metre- -
... more
Supply of Linear Surface Mounted LED Batten with a nominal system lumen output of 2000 lumens. System wattage should not exceed 20W. The luminaire shall have a rated system lifetime of 50,000 burning hours at 70. The luminaire should have a color temperature of 6500K and CRI>80. Driver of the luminaire shall have THD < 20% and PF > 0.95. The heat sink should be made of Extruded therma polycarbonate  and the luminaire optics shall have a high efficiency PC diffuser. The light fixture including driver shall comply to IEC and IS. Similar to Wipro Make Model No: LL20-221-XXX-65-NE GR or equivalent.
41each- -
... more
Supplying of Ceiling Suspended Light fixture with suspension chain of approved make, IP44, Aluminium, Synthetics material, Black brushed colour finish, Weather proof, heritage style for car porch / external Lobby, E27 Lamp base and 23 W LED lamp, warm white, crafted antique light fixtures, Lumen output shall be 1570 lm, as directed by the engineer in charge. Similar to Philips Make Model No: 15216/42/16 or equivalent
2each- -
... more
Supplying of Wall Mounted Light fixture of approved make, IP44, Aluminium body material, grey colour finish, Weather proof, heritage style for external surface, E27 Lamp base and 23 W LED lamp, warm white, crafted antique light fixtures, as directed by the engineer in charge. Similar to Philips Make Model No: 15338/54/86 or equivalent
7each- -
... more
Supply of 9W LED Bulk Head - The LED Bulk Head shall have System wattage of 9W. The luminaries should be made of pressure die cast housing LED Bulk head with IP 66 protection and IK 09 impact resistance suitable for surface and wall mounting applications. Philips Make EnduraLED WT202W LED6S NW PSU S2 PC or Equivalent
7each- -
... more
SITC of 12W LED surface mounted Light fixture with all accessories as required. Crompton Model No: LCDSPN-S-12-CDL/Equivalent makes in WIPRO or Philips.
9each- -
... more
Supply of ceiling fan of 1200mm sweep, including the down rod of standard length (upto 30 cm.). (Havels make ES 50 White or as per direction of the engineer in charge, Crompton, Riveria or equivalent).
17each- -
... more
Supplying Ceiling Fan of 1200mm sweep, 3 Blade, Dust resistant coating with espresso brown colour paint finish, HPLV motor for superior air delivery even at low voltage, not less than 230 Cu.Mtr/Min Air delivery, 390 RPM, Espresso Brown Color including the down rod of standard length (upto 30 cm), Blade set, Canopy set, Shackle Kit and Twisted wire. Similar to Havells Make, Model: ENTICER ART HERITAGE EDITION or equivalent.
7each- -
... more
Supply and fixing of ceiling fan extra down rods of different length as per the requirement including wiring the rod with 1.5 Sqmm FRLS PVC insulated copper conductor single core cable etc as required as per the direction of engineer in charge with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
20metre- -
... more
Supply of exhaust fan of 250mm sweep in the existing opening, including making good the damage, connection, testing, commissioning etc. as required, including all accessories as required for complete installation including shutter etc complete as required.(Havells, Ventil Air DX White or equivalent)
5each- -
... more
Supplying, fixing, testing and commissioning following four pole, 415 volts, residual current circuit breaker with overload protection (RCBO) of the following rating and sensitivity current in the existing MCB TPN horizontal/vertical DB's complete with connections, etc. as required and instructed by engineer in charge 32A 30mA FP RCBO
1each- -
... more
Supplying, fixing, testing and commissioning following four pole, 415 volts, residual current circuit breaker with overload protection (RCBO) of the following rating and sensitivity current in the existing MCB TPN horizontal/vertical DB's complete with connections, etc. as required and instructed by engineer in charge 40A 100mA FP RCBO
1each- -
... more
Supplying, fixing, testing and commissioning following double pole, 240 volts, residual current circuit breaker with overload protection (RCBO) of the following rating and sensitivity current in the existing MCB SPN DB's complete with connections, etc. as required and instructed by engineer in charge. 40A 100mA DP RCBO
1each- -
... more
Supply, fixing, testing and commissioning of following rating, breaking capacity and pole, type MCCB in existing Vertical Distribution Board with spredear links, terminal connections and all accessories as required making all necessary connections etc as required and instructed by engineer in charge. 63 Amp 25kA FP MCCB with Thermal - Magnetic Release
1each- -
... more
Supply Installation Testing and Commissioning of pop up box suitable for fixing 1 No 6A socket with switch & 1 No of network point fixed in recess and also including UTP CAT 6 socket for network point including all accessories as required for complete installation as directed by engineer in charge and making good all damages made for installation.
2each- -
... more
Supply and fixing of following DP 230V, isolators in sheet steel powder coated enclosure with door interlock facility on surface confirming to IEC 60947-3 complete with all accessories, connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 40A DP Isolator with enclosure
1each- -
... more
Supply, installation, testing and commissioning of following rating SP/TP C curve MCB, 16kA as per IS/IEC 60898-12002 in the existing MCB VDB/HDB including all connections and interconnections as required and as instructed by engineer in charge.- 40A SP MCB
3each- -
... more
Supply, installation, testing and commissioning of following rating SP/TP C curve MCB, 16kA as per IS/IEC 60898-12002 in the existing MCB VDB/HDB including all connections and interconnections as required and as instructed by engineer in charge.- 40A TP MCB
2each- -
... more
Supply, installation, and commissioning of 1 Nos. 5 kva single phase UPS in and out with surge protection system with 30 min backup battery @ 5 kva load matching the VAH of 8064 (SMF battery of reputed approved make), Input pf >0.95, double conversion technology with input 230V, 50Hz single phase, output 230V, 50Hz three phase, SN MP card for network monitoring, BMS compatibility etc. It shall be 100% generator compatible, with Efficiency > 92% and output power factor 0.8 or above, Eco mode Efficiency 98% and including all accessories etc as required. The system shall comply to IEC /EN 62040-1 and relevant IS standard. The acoustic noise at 1m of the system should be 62dB. The system shall comply to IEC /EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3 and relevant IS standard. and ROHS certified product. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic & manual bypass switch. The system shall have IGBT rectifier and inverter.
1set- -
... more
Supply and laying the following sizes of earthing bare copper/strips on cable tray or wall surface or in ground including necessary clamps (each clamp not exceeding 60 cm) and bolts etc as required for complete installation as instructed by engineer in charge 25 x 3 Cu strips tinned at the joints
1metre- -
... more
Supply and laying the following sizes of earthing bare copper/strips on cable tray or wall surface or in ground including necessary clamps (each clamp not exceeding 60 cm) and bolts etc as required for complete installation as instructed by engineer in charge. Copper wire No.8 SWG
30metre- -
... more
Information Outlet RJ 45 - Supply, fixing, fluke testing and commissioning of CAT6 Information Outlets (Key stone) with Shuttered Face plate, Single port, white, jack, suitable PVC / GI Modular Box etc. including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
23no- -
... more
CAT 6 Cable - Supplying and drawing of Category 6 cable consists of 4 pairs of solid insulated copper 23 AWG, surface/ recessed medium class PVC conduit through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge and making good all damages made for installation.
413metre- -
... more
OFC Cable - Supplying and drawing of 6 core SM armoured Optical Fibre Cable (OFC) through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge and making good all damages made for installation.
13metre- -
... more
Patch Cable - User Side - Supply, fixing, testing and commissioning of CAT6 Patch Cable - 2 Meter length etc. of approved make as required for complete installation.<br>
23no- -
... more
Patch Cable - Hub Side - Supply, fixing, testing and commissioning of CAT6 Patch Cable - 1 Meter of approved make as required for complete installation.<br>
23no- -
... more
Information Outlet RJ 11 - Supply, fixing, testing and commissioning of RJ11 Information Outlets (Key stone) with shuttered Faceplate, single port, white, jack, suitable PVC / GI Modular Box etc. including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
11no- -
... more
Cable - Supplying and drawing of following pair telephone cable consists of 0.5 mm dia FR, PVC Compound annealed copper conductor, unarmored telephone cable in surface / recessed medium class FRS PVC conduit through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge and making good all damages made for installation. 2 Pair Telephone Cable
203metre- -
... more
Krone Box - Supply, erection, testing and commissioning of following pair krone Box with mounting frame, enclosure of ISI grade with lockable front cover with all accessories required for fixing the box with all accessories required for complete installation in wall as directed by the Engineer in charge. 20 pair
1no- -
... more
Supply, installation, testing and commissioning of Basic user phone with necessary connection as required for complete installation as directed by the engineer in charge
11no- -
... more
Supply, Installation, Testing and installation of Cat - 6, shuttered type, 24 port fully loaded patch panel with necessary cable manager for routing the cable inside rack with all accessories required for complete installation as required as directed by the engineer in charge.
1no- -
... more
Supply, Installation, Testing and installation of Cat - 6, 24 port 10/100/1000 Mbps, layer 2, POE, switch with rack mounting brackets, input connector shall be as per IEC-320-C14 with all accessories required for complete installation populated with 1G single SFP module for uplink as required as directed by the engineer in charge. The switch should be capable to provide suffient power budjet to IP cameras as per the requirement.
1no- -
... more
Supply, installation, testing and commissioning of 4U Rack with Front glass door, Rear Perforated door with handle Lock & key. Front/Rear 4U mounting angles, top, bottom open, RAL 9005, including necessary exhaust/circulation fan with all accessories required for complete installation as directed by the engineer in charge.
1no- -

NIT No.- NIT/INKEL/KIIFB/2019-20/035 - Development of Taluk Head Quarter Hospital, Chirayinkeezhu - Renovation of Existing Heritage Building (SH: Electrical Works) NOTICE INVITING TENDER Name of work: Development of Taluk Head Quarter Hospital, Chirayinkeezhu - Renovation of Existing Heritage Building (SH: Electrical Works) e - Tender processing fee: Rs. 2,975/- including GST (Rupees Two Thousand Nine Hundred and Seventy Five only) Last date of submission of Tender : 17/09/2019 upto 3.00 p.m. Date of opening of Eligibility Documents : 19/09/2019 at 3.00 pm INKEL Ltd. 7/473ZA – 5 & 6, 2 nd Floor, Ajiyal Complex, Kakkanad, Cochin, Pin: 682030 (Kerala) Phone: 0484 2978101 Email: tenders @inkelkerala.com NIT No.- NIT/INKEL/KIIFB/2019-20/035 - Development of Taluk Head Quarter Hospital, Chirayinkeezhu - Renovation of Existing Heritage Building (SH: Electrical Works) NOTICE INVITING TENDER e – Government Procurement (e- GP) Tender No – NIT/INKEL/KIIFB/2019-20/035 dated 03/09/2019 The Managing Director, INKEL Limited. invites on behalf of Government of Kerala (Dept. of Health and Family Welfare), online Item rate bids for the work detailed below from Electrical Contractors having valid Class B Contract License issued by Kerala State Electrical Inspectorate. Name of work Development of Taluk Head Quarter Hospital, Chirayinkeezhu - Renovation of Existing Heritage Building (SH: Electrical Works) Location of work Chirayinkeezhu Estimated Cost of the Work Rs. 8,69,885/- Brief description of work Supply, Installation, Testing & Commissioning of all Electrical works for Development of Taluk Head Quarter Hospital, Chirayinkeezhu - Renovation of Existing Heritage Building Bid Security Rs. 50,000/- Bid submission fee (Tender fee) Rs. 2,975/- Period of completion 45 days Classification of Bidder Electrical Contractors having valid Class B Contract License issued by Kerala State Electrical Inspectorate. Last date and time for submission of bids 17/09/2019 at 3.00 pm Date and time of opening of tender 19/09/2019 at 3.00 pm Bid documents including the Bill of Quantities (BoQ) can be downloaded free of cost from the e- Government Procurement (e-GP) Website www.etenders.kerala.gov.in. All bid documents are to be submitted online only and in the designated cover(s)/ envelope(s) on the e-GP website. Tenders/ bids shall be accepted only through online mode on the e-GP website and no manual submission of the same shall be entertained. Late tenders will not be accepted. A bid submission fee shall be remitted online during the time of bid submission. The hard copies of certificates and documents, as detailed in clause 4.4 of Part-I Instructions to the Bidders, shall be submitted subsequently after online submission of bids in a separate cover by registered post/speed post/courier post/by hand before the date and time of opening of technical bid. NIT No.- NIT/INKEL/KIIFB/2019-20/035 - Development of Taluk Head Quarter Hospital, Chirayinkeezhu - Renovation of Existing Heritage Building (SH: Electrical Works) Price Bid shall only be submitted through online. Details regarding remittance of Bid Submission Fee and Bid Security, Bid preparation and submission are mentioned in the bid document. The bids shall be opened online on 19/08/2019 at the office of INKEL Limited, Kakkanad in the presence of the Bidders / their authorized representatives who wish to attend at the above address. If the tender opening date happens to be on a holiday or non-working day due to any other valid reason, the tender opening process will be done on the next working day at same time and place. Online Tenders/ bids are to be accompanied with a preliminary agreement executed in Kerala stamp paper worth Rs.200/-. Tenders/ bids received online without the details mentioned in clause 4.4 of Part-I Instructions to the Bidders will not be considered and sha

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.