Public Works Department Tender

... More
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.

Public Works Department - PWD Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date7 Feb 2024
Closing Date7 Mar 2024
Tender Amount₹ 2,90,340 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Carrying charges Diesel, mobile from petrol pump to operator site to continue fuel also power supply.

1

-

-

... More
Providing on hire basis 1.1KV Gr 120sqmm PVC insulated cu wire incl. laying hire basis.

50

-

-

... More
Finishing the end by crimping arrangement of 4x120sqmm.

2

-

-

... More
Hospital Campus - Old & New Sub Station

-

-

-

... More
Servicing, Cleaning, Tightening Checking & Testing with Megger of 1000KVA, 11KV/433V, Dry Type Indoor Distribution Transformer with both the Primary & Secondary Cable end Terminals including Checking & Cleaning Temp. Scanner for Transformer Protection including Cleaning, Checking & Testing of connected incoming & outgoing cables end terminal joints. Clearing different type of impurities such as dry dust, wet dust, metallic dust, oils etc. with the help of vacuum cleaner, blower, duster dry cloth benzene and ammonia or alcohol etc. as directed by EIC.

2

-

-

... More
Charges of following Routine Test of the 1000KVA, 11KV/433V, Dry Type Indoor Distribution Transformer (Unless otherwise specified, the tests shall be carried out in accordance with relevant clauses of IS 2026 (Part 1): 1977 and IS 2026 (Part 3): 1981) a) Measurement of winding resistance; b) Ratio, polarity ; c) Impedance voltage; d) Load losses; e) No-load losses and no-load current; f) Insulation resistance; g) Induced overvoltage withstand at 1.2 times rated voltage for 60 Sec h) Dielectric Test - Separate Source Voltage Withstand

2

-

-

... More
Servicing, Cleaning, Tightening Checking & Testing with Megger of 415 Volts 1600A Cubical Type Floor mounting LT Distribution Panel Board with all the incoming & outgoing ACB & switches with cable terminations & also Bus Coupling & Spring Charge arrangements.

2

-

-

... More
College Campus - Sub station

-

-

-

... More
Servicing, Cleaning, Tightening Checking, Testing and calibration for 3 panel HT Switchgears a) IR value measurement by 5 KV megger. b) Contact resistance measurement by Milli volt drop method by injecting 100A DC. c) Primary injection of CT, artificial fault simulation by primary injection (over current and earth fault for all I/C & O/G panel). d) Tripping test confirmation by all relays at appropriate current & time setting with checking of relay wiring & its tightness e) Checking & rectification of indication circuit with power pack and spring charging mechanism. f) Checking & rectification of operation of all 800Amp VCB both electrical and mechanical. g) Tripping test confirmation of WTI and All Types of Relay Calibration to confirm if the operation of the relay is within the trip time and pick up current tolerances h) Cleaning, servicing and tightness checking of HT Bus-Bar and allied items by air suction blower, CRC / WD 40 and soft cloth. i) Cleaning, servicing and testing of CT & PT with Polarity Test. j) All setting should be as per CT ratio and load pattern and harmonized with CESC HT Switchgear setting. k) All the testing should be comply with the respective IS for preventive maintanance of 11KV Sub-Station.

1

-

-

... More
Servicing, Cleaning, Tightening Checking & Testing with Megger of 750KVA, 11KV/433V, Dry Type Indoor Distribution Transformer with both the Primary & Secondary Cable end Terminals including Checking & Cleaning Temp. Scanner for Transformer Protection including Cleaning, Checking & Testing of connected incoming & outgoing cables end terminal joints. Clearing different type of impurities such as dry dust, wet dust, metallic dust, oils etc. with the help of vacuum cleaner, blower, duster dry cloth benzene and ammonia or alcohol etc. as directed by EIC.

2

-

-

... More
Charges of following Routine Test of the 750KVA, 11KV/433V, Dry Type Indoor Distribution Transformer (Unless otherwise specified, the tests shall be carried out in accordance with relevant clauses of IS 2026 (Part 1): 1977 and IS 2026 (Part 3): 1981) and all the other test as specified inrespective BIS for preventive maintaance. a) Measurement of winding resistance; b) Ratio, polarity ; c) Impedance voltage; d) Load losses; e) No-load losses and no-load current; f) Insulation resistance; g) Induced overvoltage withstand at 1.2 times rated voltage for 60 Sec h) Dielectric Test - Separate Source Voltage Withstand

2

-

-

... More
Servicing, Cleaning, Tightening Checking & Testing with Megger of 415 Volts 1250A Cubical Type Floor mounting LT Distribution Panel Board with all the incoming & outgoing ACB & switches with cable terminations & also Bus Coupling & Spring Charge arrangements as per BIS.

1

-

-

... More
Supply of Metal Body Analogue Insulation Tester (Hand Driven Generator Type), 5000V, 10000 Mega Ohm with Carrying Case for Metal Body, Testing Lead (2mts. Length) -1 pair, High Voltage Lead (2 mts. Length)-1 pair [Make -WACO, Model-WI 5002]

1

-

-

... More
Supply of Heavy Duty Safety Hand gloves set reusable type.(Shock proof upto 33Kv) as per choice of EIC.

4

-

-

... More
S & Laying of 1.1KV grade 4 core 240 sq.mm. XLPE/Ar. AL. cable (Make -HAVELLS /NICCO / Crystal) on the cable tray mostly outside the building and partly inside room as per G.S.

40

-

-

... More
Charges for Preparation of 4 Sets Statutory Drawing / Test Report which is duly approved by DOE, Govt. of West Bengal with arranging Third party testing and for follow up with Directorate of Electricity (DOE) for obtaining approval and charging clearance after carrying out necessary inspection by CESC Ltd. and DOE, and finally charging the system along with arranging and conducting necessary testing by third party. Charges for obtaining of statutary Approval/clearance from DOE and PCB shall also be included here.Servicing, cleaning, testing, and instrument calibration of the following HT, LT Panel VCB & ACB, and Dry-type Transformer, along with busbars, risers, and socket contacts, should be carried out by an approved agency of the Directorate of Electricity, Government of West Bengal and must be in accordance with the instructions of the EIC. All test reports, service reports, and instrument calibration reports, as mentioned above, along with Sub station Drawings incorporating all switch gear (SLD, Block diagram upto LT Panel outgoing) must be submitted in four copies within three days of testing and duly approved by the Directorate of Electricity, Government of West Bengal. If any anomalies are identified, they should be rectified immediately, and any means required for the rectifications should be provided by the agency

1

-

-

... More
Rate should be quoted incl. of all taxes and cess.

-

-

-

... More
Defect Liability period : 1 year

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.