Indian Institute Of Technology Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Indian Institute Of Technology - IIT Tender
Electrical Cables And Wires
Electrical and Electronics
Eprocure
Opening Date11 Jun 2024
Closing Date10 Jul 2024
Tender Amount₹ 16,16,862
Costs
EMD
₹ 32,338Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_IITKG_811104_1Bid Award Id
ViewTender No
IIT/IW/EM/NIT/06/2024-25Tender Authority
Indian Institute Of Technology ViewPurchaser Address
-Website
http://http://www.iitkgp.ac.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required .
Preferred Make ( FRLS Wire,1.1 kV):- Finolex/RR Kabel/Polycab/Havells/KEI
Preferred Make ( MMS Pipe):- Presto plast/Precision/AKG /Anchor /Equivalent approved by Engineer-in Charge
-
-
-
2 X 1.5 sq mm + 1 X 1.5 sq mm for E.C.C
200
-
-
2 X 2.5 sq mm + 1 X 2.5 sq mm for E.C.C
200
-
-
2 X 4 sq mm + 1 X 4 sq mm for E.C.C
100
-
-
2 X 6 sq mm + 1 X 6 sq mm for E.C.C
50
-
-
2 X 10 sq mm + 1 X 6 sq mm for E.C.C
50
-
-
2 X 16 sq mm + 1 X 6 sq mm for E.C.C
30
-
-
4 X 4 sq mm + 2 X 4 sq mm for E.C.C
30
-
-
4 X 6 sq mm + 2 X 6 sq mm for E.C.C
30
-
-
4 X 10 sq mm + 2 X 6 sq mm for E.C.C
20
-
-
4 X 16 sq mm + 2 X 6 sq mm for E.C.C
20
-
-
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required.
Preferred Make (MMS Pipe):-Presto plast/Precision/AKG /Anchor /Equivalent approved by Engineer-in Charge
-
-
-
20 mm
20
-
-
25 mm
20
-
-
40 mm
20
-
-
Supplying and drawing following sizes of FRLS PVC insulated 1.1 kV grade copper conductor
single core cable in the existing surface /recessed steel / PVC conduit as required.
Preferred Make (Wire):- Finolex/RR Kabel/Polycab/Havells/KEI/Equivalent approved by Engineer-in Charge
-
-
-
2 X 1.5 sq mm +1 X 1.5 sq mm for E.C.C
20
-
-
2 X 2.5 sq mm +1 X 2.5 sq mm for E.C.C
20
-
-
2 X 4 sq mm +1 X 4.0 sq mm for E.C.C
20
-
-
2 X 6 sq mm +1 X 6.0 sq mm for E.C.C
10
-
-
Supplying and fixing metal box of following sizes on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.ISI Approved.
-
-
-
75 mm X 75 mm X 60 mm deep
5
-
-
100 mm X 100 mm X 60 mm deep
5
-
-
150 mm X 150 mm X 60 mm deep
5
-
-
180 mm X 100 mm X 60 mm deep
5
-
-
200 mm X 125 mm X 60 mm deep
5
-
-
Supplying and fixing following sizes / modules ,GI box along with modular base & cover plate for modular switches in recess etc as required.
Preferred Make:- Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/
Equivalent approved by Engineer-in Charge.
-
-
-
1 or 2 Module
5
-
-
3 Module
6
-
-
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc as required.
Preferred Make:- Crabtree Athena range/Hager Insysta/Legrand Myline range/MK (Wraparound Plus)/
Equivalent approved by Engineer-in Charge.
-
-
-
5 /6 Amps Switch
1
-
-
15 /16 Amps Switch
10
-
-
3 pin 5 /6 Amps Socket Outlet
1
-
-
6 pin 15 / 16 Amps Socket Outlet
5
-
-
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required Preferred Make:- Crabtree/Hager Insysta/Legrand Myline range/MK/Equivalent approved by Engineer-in Charge.
2
-
-
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Preferred Make:-Anchor/SSK/Equivalent approved by Engineer-in Charge.
40
-
-
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on Wall Surface as required incl. S+F of 1 X 10 SWG GI wire for E.C.C making holes and manding good the damages to original finish incl painting.( Cable Dept supply)
-
-
-
Upto 35 sq mm (clamped with 1 mm thick saddle)
60
-
-
Above 35 sq mm and upto 95 sq mm (clamped with 25 X 3 mm MS flat clamp)
32
-
-
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on Cable Tray along with S+F of 10 SWG GI wire as earth wire as required.
-
-
-
Upto 35 sq. mm (clamped with 1mm thick saddle @ 3 sets per metre.)
1144
-
-
Above 35 sq. mm and upto 95 sq. mm (clamped with 25 X 3mm MS flat clamp @ 3 sets per metre.)
564.3
-
-
Laying of cable as below after Cutting Floor/Pavement/Wall and making holes incl embedding the cable at an average depth as below and mending good the damages to original finish incl S+F of 1 X 10 SWG wire for ECC (Cable Dept Supply)
-
-
-
From 2.5 sq mm to 35 sq mm at an average depth of 75 mm in floor/ pavement/wall etc.
20
-
-
Above 35 sq mm to 95 sq mm at an average depth of 100 mm in floor/ pavement/wall etc.
20
-
-
Supplying and making End Termination with brass compression gland and lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 kV grade as required.
Preferred Make:-ARUN/Dowells/3M /Equivalent approved by Engineer-in Charge
-
-
-
2 X 6 sq mm
10
-
-
2 X 10 sq mm
10
-
-
2 X 16 sq mm
10
-
-
4 X 10 sq mm
10
-
-
4 X 16 sq mm
10
-
-
3.5 X 25 sq mm
10
-
-
3.5 X 35 sq mm
5
-
-
3.5 X 50 sq mm
5
-
-
3.5 X 70 sq mm
5
-
-
3.5 X 95 sq mm
5
-
-
Earthing with G.I. Earth Plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc.for any type of soil (Morrumed/boldered soil) with charcoal/ coke and salt as required.
4
-
-
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.All Joints should be done after 4"over lapping of the strips and by welding only.
200
-
-
Supplying and Fixing Earth Busbar of G.I.Flat 25 mm X 6 mm on wall having clearance of 6 mm from wall incl. providing drilled holes on busbar complete with G.I. blots, nuts, washers, spacing heavy duty insulators etc as required.
4
-
-
Providing and fixing Hot dipped 6 SWG dia GI wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required for GI pipe earthing & others.
200
-
-
Supply and Fixing medium gauge Gi pipe (ISI-Medium) protection for cable entry including bending the pipe to the required shape complete as required with laying of wire/cable through pipe.
Preferred Make:-Medium size TATA/Bansal/Jindal/Equivalent approved by Engineer-in Charge
-
-
-
25 mm
5
-
-
40 mm
5
-
-
Supplying and fixing DP sheet steel Enclosure on surface/recess along with 25/32 Amps,415 V "C" curve DP MCB complete with connection, testing and commissioning etc.as required. Preferred Make:- Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge
20
-
-
Supplying and fixing TPN sheet steel Enclosure on surface/recess along with 16/25/32 Amps,
415 V "C" curve TPN MCB complete with connection, testing and commissioning etc.as required.
Preferred Make:-Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge
2
-
-
Fixing only 240V SPN/415V TPN Sheet Steel Main Switch or DP/TP/FP sheet steel enclosure or SP/TP Industrial Plug,Socket directly on surface / recessed /on flat iron legs on wall along with required DP/TP/FP MCB including necessary connection, testing as required. (Enclosure/Main switch / Industrial Socket : Department supply ).
10
-
-
Supplying and fixing following way, Single Pole and Neutral, IP- 43, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) Preferred Make:-Legrand/Hager/L&T/ABB/Equivalent approved by Engineer-in Charge
-
-
-
6 Way , Double door
1
-
-
Supplying and fixing of following ways surface/ recess mounting, Horizontal type, IP-43,415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 Amps, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. Preferred Make:-Legrand/Hager/L&T/Siemens/ABB/Equivalent approved by Engineer-in Charge
-
-
-
4 Way (4 + 12), Double door
1
-
-
Supplying and fixing of following ways surface/ recess mounting, Vertical Type,IP-43, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 Amps, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TP DB is normally used where 3 phase outlets are required.) Preferred Make:-Legrand/L&T/Hager/Siemens/Equivalent approved by Engineer-in Charge
-
-
-
4 Way (4 + 12), Double door
1
-
-
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB Incomer IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provisionfor earthing attachment Up to 160A
-
-
-
4 Way Double door Enclosure
Preferred Make:- Legrand /Hager/L&T/Siemens/ABB/Equivalent approved by Engineer-in Charge
1
-
-
8 Way Double door Enclosure Preferred Make:- Legrand /Hager/L&T/Siemens/ABB/Equivalent approved by Engineer-in Charge
1
-
-
12 Way Double door Enclosure Preferred Make:- Legrand /Hager/L&T/Siemens/ABB/Equivalent approved by Engineer-in Charge
1
-
-
Supplying and fixing 5 Amps to 32 Amps rating, 240/415 V,10 kA,“C” curve,miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Preferred Make:- Legrand/Hager/L&T/Siemens/Schneider/ABB/Equivalent approved by Engineer-in Charge
-
-
-
Single Pole
10
-
-
Double Pole
10
-
-
Triple Pole
5
-
-
Triple Pole and Neutral
5
-
-
Supplying and fixing 40 Amps to 63Amps rating, 240/415 V,10 kA,“C”curve, Miniature
Circuit breaker suitable for inductive load of following poles in the existing MCB DB or in
enclosure complete with connections, testing and commissioning etc. as required. Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABB
Equivalent approved by Engineer-in Charge
-
-
-
Single Pole
10
-
-
Double Pole
10
-
-
Triple Pole
5
-
-
Four Pole
5
-
-
Supplying and fixing 100 Amps rating, 240/415 V, 10 kA, “C” curve, Miniature Circuit Breaker suitable for inductive load of following poles in the existing MCB DB or in enclosure complete with connections, testing and commissioning etc. as required. Preferred Make:-Legrand /Hager/L&T/Siemens/Schneider/ABB/Equivalent
approved by Engineer-in Charge
-
-
-
TriplePole
1
-
-
Four Pole
1
-
-
Supplying and fixing of Molded Case Circuit Breaker,415 Volt, of Breaking capacity 25 kA/35kAwith Icu = Ics (for 1 sec),adjustable overload setting (Thermal Magnetic) with two sets copper spreader terminals suitable for inductive load of following poles in the existing MCB/MCCB DB or in enclosure complete with connections, testing and commissioning etc. as required.
Preferred Make:- Legrand /Hager/L&T/Siemens/Schneider/ABB
Equivalent approved by Engineer-in Charge
-
-
-
125 Amps, Four Pole
1
-
-
160 Amps, Four Pole
1
-
-
Supplying & Fixing of Four pole terminal for extention of existing electrical cable as where required of following rating, Preferred Make- approved by EIC.
-
-
-
Up to 40 Amp
20
-
-
Above 40 Amp to 100 Amp
10
-
-
Above 100 Amp to 250 Amp
2
-
-
Above 250 Amp to 400Amp
1
-
-
Supplying and Installing following size of perforated Hot Dipped Galvanized Iron Cable Tray ( Galvanisation thickness not less than 50 microns) STRAIGHT THROUGH with perforation not more than 17.5%, in convenient sections, jointed with connectors, suspended from the ceiling with G .I .Suspenders including G.I. bolts & nuts, etc as required.Preferred Make:- ISI marked/ Approved by Engineer-in -charge
-
-
-
300 mm width X 50 mm depth X 1.6 mm thickness
511.9
-
-
225 mm width X 50 mm depth X 1.6 mm thickness
143
-
-
150 mm width X 50 mm depth X 1.6 mm thickness
41
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
10
-
-
Supplying and Installing following size of perforated Hot Dipped Galvanized Iron Cable Tray ( Galvanisation thickness not less than 50 microns) BENDS with perforation not more than 17.5%, in convenient sections, jointed with connectors, suspended from the ceiling with G.I.Suspenders including bolts & nuts, etc as required.Preferred Make:- ISI marked / Approved by Engineer-in -charge
-
-
-
300 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
225 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
150 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
1
-
-
Supplying and Installing following size of perforated Hot Dipped Galvanized Iron Cable Tray ( Galvanisation thickness not less than 50 microns) hot dip GI cable trays REDUCERS with perforation not more than 17.5%, in convenient sections, jointed with connectors, suspended from the ceiling with G.I.Suspenders including bolts & nuts, etc as required.Preferred Make:- ISI marked /Approved by Engineer-in -charge
-
-
-
300 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
225 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
150 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
1
-
-
Supplying and Installing following size of perforated Hot Dipped Galvanized Iron Cable Tray ( Galvanisation thickness not less than 50 microns) TEE with perforation not more than 17.5%, in convenient sections, jointed with connectors, suspended from the ceiling with G.I .Suspenders including bolts & nuts, etc as required.Preferred Make:- ISI marked /Approved by Engineer-in -charge
-
-
-
300 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
225 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
150 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
1
-
-
Supplying and Installing following size of perforated Hot Dipped Galvanized Iron Cable Tray ( Galvanisation thickness not less than 50 microns) CROSS MEMBERS with perforation not more than 17.5%, in convenient sections, jointed with connectors, suspended from the ceiling with G.I.Suspenders including bolts & nuts, etc as required.Preferred Make:- ISI marked /Approved by Engineer-in -charge
-
-
-
300 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
225 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
150 mm width X 50 mm depth X 1.6 mm thickness
5
-
-
100 mm width X 50 mm depth X 1.6 mm thickness
1
-
-
Supplying & fixing of LED Surfafe down Light fixture having dimension of 312 mm X 312 mm ,supply voltage 220-240 Volt,Lumen ≥ 2310 ,Efficacy ≥ 105 Lm/Watt,Power Factor ≥ 0.95,CCT _ 4000 K,CRI ≥ 80,THD ≤ 10%,IP 20.with high surge protection separate driver All the luminaires should be warranted for 2 years at site with free of cost.Permanent numbering of LED luminaires are mandatary during installation at site. Preferred Make:- Philips model no Cirrus Mini Pro SM 200C LED1CS 4000 FSL OD WH /Equivalent of Havells/Bajaj/Jaquar/Wipro/LT/Equivalent approved by Engineer-in Charge
85
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements