Rajasthan State Road Development And Construction Corporation Limited Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 33,040Document Cost
₹ 590Tender Fee
₹ 500
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_RSRDC_429353_1Bid Award Id
ViewTender No
RSRDCC NIT 301/2024-25 DATED 25.10.2024Tender Authority
Rajasthan State Road Development And Construction Corporation Limited ViewPurchaser Address
-Website
http://http://roads.rajasthan.gov.in/content/raj/roads/en/home.html
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supply & fixing MS powder coated stand suitable for 2.5/3.0/4.0 Tr outdoor type of Split/Ductable/Tower AC. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
3
1349
4047
Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
-
-
-
Un Armoured
-
-
-
4 core x 2.5 Sq.mm
50
232
11600
Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas charging system shall be flushed with high purity Nitrogen Gas to remove carbon content, dirt particles to make sure that there is no chance of mixing any impurity with Refrigerant Gas. Thereafter System shall be tested with Nitrogen Gas at 1.5 Times of working pressure of R410 Refrigerant Gas to ensure leakproof system. Whole system shall be Vacuumed up to 500-micron level which ensures the zero-moisture content level in piping to ensure better cooling efficiency and long life of the system. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
10
1821
18210
Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
-
-
-
20 mm
50
189
9450
25 mm
30
229
6870
Supplying and charging of fresh refrigerant and testing of performance of air conditioner/ fridge/ water cooler of following capacity including capillary and strainer/ filter.
-
-
-
1.5 TR Window/ Split A.C.
5
2407
12035
2.0 TR Window/ Split A.C.
10
3076
30760
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity 99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
-
-
-
50.0 Sq. mm
-
-
-
3.5 core
150
457
68550
70.0 Sq. mm
-
-
-
3.5 core
150
610
91500
95.0 Sq. mm
-
-
-
3.5 core
200
765
153000
120.0 Sq. mm
-
-
-
3.5 core
150
945
141750
150.0 Sq. mm
-
-
-
3.5 core
200
1096
219200
185.0 Sq. mm
-
-
-
3.5 core
150
1415
212250
240.0 Sq. mm
-
-
-
3.5 core
100
1733
173300
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
-
-
-
3.5 x 50.0 sq.mm
6
286
1716
3.5 x 70.0 sq.mm
6
382
2292
3.5 x 95.0 sq.mm
6
601
3606
3.5 x 120.0 sq.mm
6
708
4248
3.5 x 150.0 sq.mm
6
777
4662
3.5 x 185.0 sq.mm
6
1072
6432
3.5 x 240.0 sq.mm
6
1174
7044
Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
-
-
-
(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
-
-
-
(b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts
-
-
-
© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
-
-
-
(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm.
-
-
-
(d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.
-
-
-
(e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
-
-
-
25 mm thick and 3 Mtr. Long
2
7955
15910
Above 35 sq. mm and upto 95 sq. mm fixed with 40 mm x 3 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps.
200
67
13400
Above 95 sq. mm and upto 185 sq. mm fixed with 40 mm x 4 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps.
200
92
18400
Above 185 sq. mm and upto 400 sq. mm fixed with 50 mm x 5 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps.
200
141
28200
P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and two coats enamel paint including cutting, welding, holes etc.of following sizes as required.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
-
-
-
35mm x 35mm x 5mm
50
318
15900
40mm x 40mm x 5mm
50
367
18350
Supply, Fabricating & installing following sizes of Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with rungs at span of 250mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with M.S. suspenders etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
-
-
-
150mm x 50mm x 1.6mm
50
533
26650
300mm x 50mm x 1.6mm
50
826
41300
450mm x 50mm x 2.0mm
50
1460
73000
S & Making Heat shrinkable type Tubular sleeve version outdoor straight through joint for following size of PVC/ XLPE insulated aluminium conductor cable of 1.1 KV grade as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
-
-
-
3/3.5/4 x 25.0 sq.mm-50 sq.mm
4
3231
12924
3/3.5/4 x 70.0 sq.mm-150 sq.mm
4
4918
19672
3/3.5/4 x 185.0 sq.mm-300 sq.mm
4
9006
36024
NON BSR ITEMS
-
-
-
Labour charges for dismantling of exiting electrical panel including disconnect all outgoing & incoming cable and shift to terrace of main building sms hospital jaipur and resifting at ground floor after construction of emerging building. And Cordiant with hospital authority
2
20000
40000
Labour charges for dismantling and re shifting of exiting 'c' class MS pipe for fire Fighting system of size 80mm to 150mm including welding, cutting , panting and scaffolding of main building sms hospital jaipur from ground floor to terrace. And Cordiant with hospital authority
2
20000
40000