Military Engineer Services Tender
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.
Costs
EMD
₹ 76,000Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Certain Internal Electric Repairs Works, Re-wiring And Replacement Of Other Connected Items, Accessories, Light Fittings, Dbs In Mh Area And Amc Units
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_668981_1Bid Award Id
ViewTender No
GE/JULL/ET-46/2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
All as per ser item No. 2.00 above but for one socket outlet 5 Amps on independent board complete all as specified
150
-
-
All as per ser item No. 2.00 above but for one socket outlet 5 Amps on same board controlled with other switch complete all as specified
50
-
-
All as per ser item No. 2.00 above but with 2.5 Sqmm (nominal area) FRLS cable for one 3 Pin 15 Amp socket on independent board including one 2.5 Sqmm copper conductor multi stranded green colour PVC insulated unsheathed FRLS cable 1100 volts grade as earth wire connected to common earth and earth dolly with all accessories complete all as specified and directed by Engineer-in-Charge.
200
-
-
Material and labour for point wiring with 1.5 Sqmm, PVC insulated but unsheathed, stranded copper conductor single core FRLS cable, IS-694 marked, drawn through existing metallic/PVC concealed conduit including replacement of modular metal flush mounting box with white cover plate with frame of suitable modules, brass screws including 1.5 Sqmm stranded copper conductor PVC insulated FRLS cable green in colour as continuous earth conductor connected to common earth and earth dolly with all accessories complete all as specified and directed for one light point/exhaust fan/bell controlled by one switch SP one way
125
-
-
Ditto, All as per ser item No. 7.00 above but for One light point controlled by two Nos, 2-way switches complete all as specified.
5
-
-
Ditto, All as per ser item No. 7.00 above but for one socket outlet 5 Amps on independent board complete all as specified
50
-
-
Ditto, All as per ser item No. 7.00 above but for one socket outlet 5 Amps on same board controlled with other switch complete all as specified
25
-
-
All as per ser item No. 7.00 above but with 2.5 Sqmm (nominal area) FRLS cable for one 3 Pin 15 Amp socket on independent board including one 2.5 Sqmm copper conductor multi stranded green colour PVC insulated unsheathed FRLS cable 1100 volts grade as earth wire connected to common earth and earth dolly with all accessories complete all as specified and directed by Engineer-in-Charge.
50
-
-
Supply and fixing in replacement white modular switch 6 Amp, AC, one way, one module complete all as specified and directed
Make:- ABB/Schneider/Legrand/Havells
650
-
-
Supply and fixing in replacement white modular switch 6 Amp, AC, two way, one module complete all as specified and directed
10
-
-
Supply and fixing in replacement white modular switch 16 Amp, AC, one way, one module with indicator complete all as specified and directed
250
-
-
Supply and fixing in replacement white modular bell push switch 6 Amp, AC, one module, complete all as specified and directed
20
-
-
Supply and fixing in replacement white modular socket 6 Amp 250 V AC, 2 in1 socket with shutter combined two module complete all as specified and directed
275
-
-
Supply and fixing in replacement white modular socket 6/16 Amp 250 V AC, twin socket combined two module complete all as specified and directed
250
-
-
Supply and fixing in replacement white modular fan regulator AC, step type, 4/5 steps min, two module complete all as specified and directed
220
-
-
Supply and fixing in replacement white modular mini MCB 16 Amps 250 V AC, one module complete all as specified and directed
40
-
-
Supply and fixing in replacement white modular dummy plate one module complete all as specified and directed
100
-
-
Material and labour for point wiring for one light/ fan/ bell point controlled by one switch, SP, one way with 1.5 Sqmm, PVC insulated , unsheathed, stranded copper conductor single core FRLS cable, IS-694 marked, drawn through in and including non metallic rigid PVC concealed conduit , medium grade, ISI marked 20mm dia or higher complete with all PVC conduit accessories such as socket, elbow, junction box, bell mouth, reducer, bend and flexible conduit etc including cutting chases in wall for laying of conduit and making good to all disturbed surfaces and matching the same with adjoining specifications, sunken pressed steel terminal switch box as specified with 3mm thick plastic laminated sheet top cover fixed with brass/cadmium plated steel screws and cup washers including 1.5 Sqmm stranded copper conductor PVC insulated FRLS cable green in colour as continuous earth conductor connected to common earth and earth dolly with all accessories complete all as specified and directed.
150
-
-
Ditto, All as per ser item No. 21.00 above but for one light point controlled by two Nos. 2-way
switches complete all as specified
5
-
-
Ditto, All as per ser item No. 21.00 here-in-before but for one socket outlet 5 Amps on independent board complete all as specified
50
-
-
Ditto, All as per ser item No. 21.00 above but for one socket outlet 5 Amps on same board controlled with other switch complete all as specified
30
-
-
Ditto, All as per ser item No. 21.00 above but with 2.5 Sqmm (nominal area) FRLS cable for one 3 Pin 15 Amp socket on independent board including one 2.5 Sqmm copper conductor multi stranded green colour PVC insulated unsheathed FRLS cable 1100 volts grade as earth wire connected to common earth and earth dolly with all accessories complete all as specified and directed by Engineer-in-Charge.
30
-
-
Supply and fixing in replacement switch piano flush type, 5 Amps, AC single pole, one way complete all as specified.
230
-
-
Supply and fixing in replacement switch piano flush type, 5 Amps, AC single pole, two way complete all as specified.
10
-
-
Supply and fixing switch piano flush type, 15 Amps, AC single pole, one way complete all as specified.
30
-
-
Supply and fixing in replacement socket out let 5 Amp, flush type complete all as specified.
80
-
-
Supply and fixing in replacement Socket outlet multi purpose 2 in 1, 3 pin, 5 & 15 Amps, flush type complete all as specified
30
-
-
Supply and fixing bell push switch flush type 5 Amps, SP, complete all as specified
5
-
-
Supply and fixing in replacement Bell electric AC (Ding Dong) 240 volt SP complete all as specified
10
-
-
Supply and fixing in replacement Lamp holder insulated body with back plate suitable for batten fittings complete all as specified.
40
-
-
Supply and fixing in replacement for ceiling rose surface type bakelite 65 x 50 mm three terminal complete all as specified.
450
-
-
Supply and fixing in replacement electronic step regulator for fan socket Size, single phase, 2 module including connection complete all as specified.
50
-
-
Supply and fixing in replacement energy saving LED batten with polycarbonate diffuser comprising with aluminium housing, 4 ft, 20 W, 6500 K, power factor more than 0.95, IP-20 class-l protection with inbuilt LED driver, system luminous efficacy 110 lm/w, complete all as specified and directed
Make of ser item No. 36 to 48:- Philps/CG/Bajaj/Havells
800
-
-
Supply and fixing in replacement energy saving LED batten with polycarbonate diffuser comprising with polycarbonate housing, 2 ft, 10 W, 6500 K, power factor more than 0.95, IP-20 class-l protection with inbuilt LED driver, system luminous efficacy 100 lm/w, complete all as specified and directed
10
-
-
Material and labour for LED driver 36 watt suitable for 2' x 2' LED light fitting 36 watt complete compatible for existing light fitting all as specified and directed
40
-
-
Supply and fixing in replacement energy saving recess mounting deep drawn LED luminaire with clamp, 36W, 6500 K suitable for POP/ Grid ceiling of size 60 cm x 60 cm including necessary fixing arrangements/add altn of ceiling, having power factor more than 0.90, IP-20 class-II protection with high efficiency LED electronic driver, system luminous efficacy 100 lm/w complete all as specified and directed.
160
-
-
Supply and fixing in replacement energy saving suspended LED luminaire, 34/36W, 6500 K, size 60 cm x 60 cm, with hanging string wire having power factor more than 0.90, IP-20 class-II protection with high efficiency LED electronic driver, system luminous efficacy 100 lm/w complete all as specified and directed.
10
-
-
Supply and fixing in replacement energy saving surface mounting deep drawn LED luminaire, 34/36W, 6500 K, size 60 cm x 60 cm, having power factor more than 0.90, IP-20 class-II protection with high efficiency LED electronic driver, system luminous efficacy 100 lm/w complete all as specified and directed.
40
-
-
Supply and fixing in replacement energy saving recess mounting deep drawn LED luminaire with fixing clamp, 18W, 6500 K, size 30 cm x 30 cm, having power factor more than 0.90, IP-20 class-II protection with high efficiency LED electronic driver, luminous efficacy 120 lm/w, complete all as specified and directed.
10
-
-
Supply and fixing in replacement energy saving surface mounting deep drawn LED luminaire, 18W, 6500 K, size 30 cm x 30 cm, having power factor more than 0.90, IP-20 class-II protection with high efficiency LED electronic driver, luminous efficacy 120 lm/w, complete all as specified and directed.
10
-
-
Supply and fixing in replacement energy saving bulk head luminaire with Polycarbonate diffuser LED integral fitting 10 watt (Min), 6500K, IP-66, connecting and testing, complete all as directed and specified.
10
-
-
Supply and fixing in replacement energy saving pressure die-cast aluminium luminaire with heat resistant glass and suitable optics for uniform distribution of light 35 watt LED for bldg security lights with high efficiently electronic driver, having IP-66 protection, surge protection min 4 KV power factor more than 0.9 complete operative on AC supply, pre-wired and including mounting bracket, fixing clamps connection and testing complete all as specified
10
-
-
Supply and fixing in repairs/ replacement LED Flood lights, IP 66 High power LED min 3 to 4 watt, Flood light with pressure die-cast aluminium housing complete with all accessories of 50 W LED, efficiency 100 Lm/watt, with secondary optics modular Lenses provided with casing and caping to minimize glare and for better distribution of light complete all as specified and directed
10
-
-
Supply and fixing in repairs/ replacement LED Flood lights, IP 66 High power LED min 3 to 4 watt, Flood light with pressure die-cast aluminium housing complete with all accessories of 90 W LED, efficiency 100 Lm/watt, with secondary optics modular Lenses provided with casing and caping to minimize glare and for better distribution of light complete all as specified and directed
10
-
-
Supply and fixing LED post top light for 360 degree indirect light with polycarbonate diffuser and IP-65 protection, 25 watt, 230 volt, 50 Hz, complete all as specified and directed
20
-
-
Cutting chases, pinning in. making good to facings where required and pointing in cement mortar 1:3 to cutting chases for concealed conduit submain wiring, etc., and making good with existing surface, cutting width not exc 100mm complete all as specified and directed
500
-
-
Material and labour in repairs Submain wiring with two run of FRLS PVC insulated unsheathed multistranded copper conductor single core 1.5 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including earth continuity copper conductor 1.5 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified.
Note: The cutting chases and civil wk for making conduit as concealed shall be measured and paid separately
150
-
-
Material and labour in repairs Submain wiring with two run of FRLS PVC insulated unsheathed multistranded copper conductor single core 2.5 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including earth continuity copper conductor 2.5 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified. Note: The cutting chases and civil wk for making conduit as concealed shall be measured and paid separately
400
-
-
Material and labour in repairs Submain wiring with two run of FRLS PVC insulated unsheathed multistranded copper conductor single core 4 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including earth continuity copper conductor 4 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified.
1500
-
-
Material and labour in repairs Submain wiring with two run of FRLS PVC insulated unsheathed multistranded copper conductor single core 6 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including earth continuity copper conductor 6 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified.
600
-
-
Material and labour in repairs Submain wiring with two run of FRLS PVC insulated unsheathed multistranded copper conductor single core 10 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including earth continuity copper conductor 10 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified.
300
-
-
Material and labour in repairs Submain wiring with two run of FRLS PVC insulated unsheathed multistranded copper conductor single core 16 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including earth continuity copper conductor 16 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified.
118
-
-
Material and labour in repairs Submain wiring with two run of FRLS PVC insulated unsheathed multistranded copper conductor single core 25 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including earth continuity copper conductor 25 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified. .
100
-
-
Material and labour in repairs Submain wiring with four run of FRLS PVC insulated unsheathed multistranded copper conductor single core 10 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including two run of earth continuity copper conductor 10 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified.
100
-
-
Material and labour in repairs Submain wiring with four run of FRLS PVC insulated unsheathed multistranded copper conductor single core 16 Sqmm drawn through in and including PVC rigid non metallic surface or concealed conduit medium grade with all fittings including two run of earth continuity copper conductor 16 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor with green insulation including taking down existing unserviceable/burnt submain complete all as specified.
100
-
-
Supply and fixing in repairs/ replacement PVC rigid non metallic conduit medium grade ISI mark 25mm dia surface or concealed conduit with accessories such as tee, elbow ,bend junction box complete for drawing telephone cable/ TV cable/ Camera cable/ PVC copper wires all as specified.
Note for srl item No. 50.00 to 59.00 : Cutting chasses on walls to be measured and paid separately
150
-
-
Supply and fixing in repairs/replacement Sheet metal enclosure for DBs when MCBs to be used, SPN 12 ways 240 V, with copper bus bar, double door, epoxy/powder coated inside and outside complete all as specified.
25
-
-
Supply and fixing in repairs/replacement Sheet metal enclosure for DBs when MCBs to be used, SPN 8 ways 240 V, with copper bus bar, double door, epoxy/powder coated inside and outside complete all as specified.
10
-
-
Supply and fixing in repairs/replacement Sheet metal enclosure for DBs when MCBs to be used, SPN 4 ways 240 V, with copper bus bar, double door, epoxy/powder coated inside and outside complete all as specified.
10
-
-
Supply and fixing in repairs/replacement Sheet metal enclosure for DBs when MCBs to be used, TPN 4 ways 415 V, with copper bus bar, double door, epoxy/powder coated inside and outside complete all as specified.
3
-
-
Supply and fixing in repairs/replacement Sheet metal enclosure for DBs when MCBs to be used, TPN 8 ways 415 V, with copper bus bar, double door, epoxy/powder coated inside and outside complete all as specified.
3
-
-
Supply and fixing in replacement distribution board iron clad, vertical type, double door with IP-43 Protection suitable for MCCB TP as incommer and MCB SP/TP as outgoing 415 volts 3 phase 50 C/s, 4 way , complete with appropriate size copper bus bar and neutral link complete with one MCCB TP 415 volts 63 Amps rating with rupturing cap 16 KA of the same make as of distribution board & including cutting chases to wall for fixing DB and making good the disturbed wall surface all as specified and directed.
Note : Rates of MCCB deemed to be included in quoted rate.
8
-
-
Supply and fixing in replacement distribution board iron clad, vertical type, double door with IP-43 Protection suitable for MCCB TP as incommer and MCB SP/TP as outgoing 415 volts 3 phase 50 C/s, 8 way , complete with appropriate size copper bus bar and neutral link complete with one MCCB TP 415 volts 100 Amps rating with rupturing cap 16 KA of the same make as of distribution board & including cutting chases to wall for fixing DB and making good the disturbed wall surface all as specified and directed.
Note : Rates of MCCB deemed to be included in quoted rate.
2
-
-
Supply and fixing in repairs/replacement single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 20 amp 240 V 10 KA with plastic cover complete all as specified and as directed.
10
-
-
Material and labour in replacement MCB SP 6 Amps to 32 Amps, 240V with rupturing capacity 10 KA, C Curve complete all as specified
602
-
-
Material and labour in replacement MCB SPN 32 Amps, 240V with rupturing capacity 10 KA, C Curve complete all as specified
20
-
-
Material and labour in replacement MCB SPN 40 to 63 Amps, 240V with rupturing capacity 10 KA, C Curve complete all as specified
25
-
-
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) of triple poles and
current carrying capacity 32Amps in the DB complete all as specified.
4
-
-
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) of triple poles & neutral and current carrying capacity 32Amps in the DB complete all as specified.
6
-
-
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) of triple poles & neutral and current carrying capacity 63 Amps in the DB complete all as specified.
Make for Sr item No. 60 to 73 Schneider/Legrand/ABB/Siemens
6
-
-
Refixing of serviceable light fitting any type retrieved from srl item No.1 and make electric connections for functional all as specified and directed.
120
-
-
Material and labour in replacement earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI strip 32mm x 6mm in and including GI pipe 40mm bore light grade as protection pipe (from top of earth plate up to the body of equipment) by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm bore of GI pipe light grade with funnel and wire mesh, PCC chamber of size 300 x 300 x 300mm (top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate and angle iron frame including necessary excavation/ earth work in any type of soil/rock, test point of GI strip and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.(cost of protection pipe up to 7.5metres from earth electrode will be included in the unit rate quoted by the contractor) complete all as specified and directed
4
-
-
Material and labour for earthling complete with & including copper earth plate of size 600 x 600 x 3.15 mm thick, buried vertically in ground to a depth not less than 2.25 metre below ground level, with lop edge of earth plate not less than 1.5 below ground level connected to copper earth strip 20x3mm thick connected soldered and riveted to earth plate by means of nuts, bolts , check nuts & washers, of galvanized iron or steel all as Shown in electrical plate No. 3 of MES SSR Part- I (2009) and connected to panel board, all as specified and testing on completion including provn of earth strip protected by 25 mm dia light grade GI pipe upto 7.5 meter from electrode to earth terminal point Feeder Pillar box including provn of the earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of not less than 15 cm in alternate layers of charcoal and salt on all sides of earth plate GI light grade watering pipe of 20mm dia with funnel with wire mesh including all necessary excavation & earth work in any type of soil, returning filling in, removal of surplus soil to a distance 50 metre, PCC 1:3:6 type C-1 as in earth chamber, 50 mm thick RCC cover using cement concrete 1:2:4 type B-0 reinforced with & including 8 mm dia mild steel TMT bar @ 100 mm c/c Both way with suitable handle for lifting arrangement & including form work complete all as specified & shown on drawings & directed
2
-
-
Material and labour for earthling complete with & including galvanized earth plate of size 600 x 600 x 6 mm thick, buried vertically in ground to a depth not less than 2.25 metre below ground level, with lop edge of earth plate not less than 1.5 below ground level connected to galvanized earth wire 4mm dia connected soldered and riveted to earth plate by means of nuts, bolts , check nuts & washers, of galvanized iron or steel all as Shown in electrical plate No. 3 of MES SSR Part- I (2009) and connected to panel board, all as specified and testing on completion including provn of earth wire protected by 15 mm dia light grade GI pipe upto 7.5 meter from electrode to earth terminal point Feeder Pillar box including provn of the earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of not less than 15 cm in alternate layers of charcoal and salt on all sides of earth plate GI light grade watering pipe of 20mm dia with funnel with wire mesh including all necessary excavation & earth work in any type of soil, returning filling in, removal of surplus soil to a distance 50 metre, PCC 1:3:6 type C-1 as in earth chamber, 50 mm thick RCC cover using cement concrete 1:2:4 type B-0 reinforced with & including 8 mm dia mild steel TMT bar @ 100 mm c/c Both way with suitable handle for lifting arrangement & including form work complete all as specified & shown on drawings & directed.
Notes:- On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone at without any extra cost by contractor
6
-
-
Material and labour in repairs for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20x3mm copper strip complete wire all as specified and directed.
20
-
-
Material and labour in repairs for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron complete wire all as specified and directed.
20
-
-
Material and labour for Earth continuity conductor or main earth lead fixed on wall on batten or recess or chases or burried in ground or drawn in conduit / pipe or fixed to pole or any other indicated as required on ground for 25x3.15 mm aluminium strip complete all as specified and as directed.
60
-
-
Evaluation Notes How It Works ?
Potential Partner