Works Department Tender
Search from a pool of business opportunities related to Odisha tenders on the online platform of BidAssist. Be it an Odisha PWD tender or a civil aviation tender, one can find every tender Odisha government, as well as PSUs and other organizations, post online. Every tender, active or achieved, is sourced from the eProcurement Odisha website and thus carries full credibility.
Costs
EMD
₹ 30,600Document Cost
₹ 6,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_EICCL_104437_1Bid Award Id
ViewTender No
SE CTC (RandB)-15 of 2024-25Tender Authority
Works Department ViewPurchaser Address
-Website
http://https://www.worksodisha.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Installation ,testing and commissioning of VRV systems in below mention details :-
VRV Out door unit Particulars
2
38000
19000
Installation of Indoor Unit R.F CASSETTE AC with Cordless Remort
Supply of fully factory assembled Variable Refrigerant Volume(VRV)-X type multi unit air condioning system with inverter type outdoor units with individual controller for cooling type operations. The VRV outdoor unit shall be equipped highly efficiency Hermetically sealed all inverter type scroll compressor(s) having at least 6 Pole motor & manufactured by OEM.The outdoor unit needs to be equipped with two compressors. The condenser fan should have minimum External Static Pressure of 78 Pa so as to avoid short cycling of hot air top discharge and refrigerant cooled PCB for enhanced reliability during peak temperature.The Outdoor unit must be capable of Varying the Refrigerant Temperature(VRT) TOP DISCHARGE in order to work more efficiently.Make:-Daikin/MITSUBISHI/OGENERAL
12
54000
4500
Refrigerant gas R410A
56
75600
1350
Supply,installation, testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13 mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping.Make:-Rajco\Mandev.
Suction Line pipe with 19mm thick insulation
41.3 mm
50
128000
2560
34.9mm
20
47000
2350
28.6 mm
20
44200
2210
22.2 mm
16
28800
1800
15.9 mm
105
129150
1230
Liquid Line pipe with 13mm thick insulation
19.1 mm
50
65000
1300
15.9 mm
20
23000
1150
9.5 mm
140
117600
840
Supply, installation, testing & commissioning of 2 core 1 sq.mm shielded copper control cum transmission wiring in PVC conduit between indoor & outdoor.
2 C x 1 sq.mm Cu communication cable
262
61832
236
Supply, installation, testing & Commissioning of following sizes insulated PVC drain pipes insulated with 9mm thick nitrile rubber insulation of following size.
40/32 mm Dia with 9mm Nitrile Rubber Insulation
240
57600
240
VI Pad
12
24000
2000
Supply of CPRI approved 125A Sub panel having following specification 2mm thick sheet ,size:44*12*32 inch ,200A Cu. busbar ,duly treated by 7 tank treatment process, Provision of 1nos 125 A ,4p mccb 25 ka as Incomer,outgoing feeder : 63A FP 10KA MCB 6 NoS, Surge protective device 15KA, Indicators for ON,off ,trip ,MFM indication ,provision for earthing bar,hinges, and other accessories , hinged door must be painted with powder coated in complete as per the direction of Engineer in charge.(Power and Light load sub panel EACH FLOOR)(Make : Schneider/siemens)
2
87678
43839
Supply and fixing of 63A FP MCB rating 240 V/415 V "C" series MCB suitable for lighting and other loads of the following poles in the exiting MCB DB ISI marked complete with connections testing and commissioning etc. (Make-Legrand/ Hager/ Simens/ schneider)
12
41904
3492
Supply and fixing of 4 pole MCCB 125 A,Ics = 100% Icu, 25 KA breaking capacity, adjustableThermal,fixed magnetic type in existing cubicle panel board including drilling holes in cubcle panel, making connections, etc. as required complete in all respect as per direction of Engineer in charge (Make : Schneider (ACTI 9 ) /legrand(Ekinox)/siemens(betaguard)/hager
1
14650
14650
Supply & Fixing of following PVC Aluminium armoured XLPE cables insulated ISI marked .(Make- Havells/ Polycab/ KEI / V-Guard/ Gloster) 3.5Cx70sqmm
127
97028
764