Water Corporation Of Odisha Tender
Search from a pool of business opportunities related to Odisha tenders on the online platform of BidAssist. Be it an Odisha PWD tender or a civil aviation tender, one can find every tender Odisha government, as well as PSUs and other organizations, post online. Every tender, active or achieved, is sourced from the eProcurement Odisha website and thus carries full credibility.
Water Corporation Of Odisha - WATCO Tender
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date10 Jul 2024
Closing Date19 Jul 2024
Tender Amount₹ 1,85,05,000
Costs
EMD
₹ 1,86,000Document Cost
₹ 11,800Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_WATCO_103553_1Bid Award Id
ViewTender No
WATCO (W)-02(5)/2024-25 Dtd.05.07.2024Tender Authority
Water Corporation Of Odisha ViewPurchaser Address
-Website
http://http://watcoodisha.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supply of DI Pilot Altitude Flow Valve of Double CHAMBER(Globe Type) with orfice plate for purpose to close valve at a maximum water level of ESR & to open to refill the ESR when the water level in the ESR at lowers. Altitude Control Valve should be worked at minimum pressure 1kg/cm2. An altitude control valve controls the level of a tank. The altitude valve will remain open while the tank is not full and it will close when the tanks reaches its maximum level. The opening and closing of the valve will work without external power source (electric, pneumatic or man power), it will work automatically,The body, Spool, & cover will be DI ASTM A-536 standard, Spring, steam, Jam Nut, Cover bolt & cover washer should be SS, DI /SS Diaphragm plate, Nytril/Nylon diaphragm, Bronze cover bushing, Seat plate & ring. The Approved Make : (VAG/SINGER/CLA/BURMAD-700/DOROT-S300)with 2 nos solenoid including cost of material with all taxes transporataion to Site/Storage with insurance.
-
-
-
150mm Nominal dia
1
-
-
Supply of double chamber DI Control valve (globe type) with solenoid , hydraulic operated with stem amd Positioner for feed back switch, selonoid valve, integral orifice plate assembly, differential control, reverse flow control, restriction orifice Body PN-1.6 can be integrated with PLC pannel for operation with a minimum Pressure in upstream 0.2 kg/cm2 to a maximum pressure of 8 kg/cm2 of The Approved Make : CLA,DOROT S-300,SINGER,BERMAD-700,VAG , AVK to control water supply including cost of material with all taxes transporataion to Site/Storage with insurance.
-
-
-
200mm dia PN16 Flow Control Valve with 2 nos solenoid
4
-
-
Installation charges
-
-
-
200mm dia PN16 Flow Control Valve with 2 nos solenoid
4
-
-
Supply, installation & commissioning of PLC Panel with technical specification i,e. Enclosure:800x800x2100mm-01 No with double door & lock, CPU should have 1 MB program memory with extended memory slut, Redundand-24VDC, SMPS 10Amp along with 24V DC SPD,IO count as DI-16, DO-20, AI-20, AO-08 & MODBUS-10 subsystem shall be of same series as CPU, 10" Panel Mounted HMI, Modem should have support MQTT Protocol by default, 24volt DC Industrial switch with minimum 6 eathernate, 4 SFP Port each AI shall be equiped with sutitable signal isolator of 20 Nos & surge protection device 20 nos LIU Isolater, 230Volt AC/230volt AC torroidal transformer, 1KVA 230V AC industrial grade UPS of 8 hrs backup to charge 3 nos 12 VDC 65 AH Battery ,DP MCB of Adequate current capacity, LED tube light 10" 5 watt,door limit switch, Fan 6" with louver, 4 sqmm straight through terminal & fuse terminal 90 nos, with PE & EE. The Approved : (PLC Make Siemens, Schnider, Phoenix, ABB, Mitsubishi Phoenix, Siemens, Schnider. Isolater Masibus, Rishabh, Multispan. SPD-Phoenix, Mersen, Dehn UPS- Vertive, Hitachi, High Rail, AVO, Eathernate switch- Siemense, Moxa, Phoenix) including cost of material with all taxes Site/Storage with all taxes transportation to site/ storage with insurance.Programme to be handed over with upload & download facilities for departmental use.
1
-
-
Supply,Installation & Commissioning of SCADA software (Make-Schiender/Simens/Fox) with Graphical processor visualisation Advanced alaram management,historical and Real time trending,Built-in-reporting,Stastical process control,Multithreaded citect VBA and Cicode programming language with 500 Tag SCADA Software (Make- Schneider, Siemens),1KVa online Ups with 30Min batery backup- 1Nos,CPU Having Preloaded win-10 Proffessional, I3-10gen 2.4 Ghz Prrocessor, DDR4 8gb Ram, 500 gb 7200 Rpm HDD-1 Nos ( Make- HP,DELL,LENOVO),USB based keyboard - 1Nos,USB based Optical Mouse- 1Nos,43'' LED monitor - 1Nos,A4 size laserPrinter - 1Nos,Wooden Computer table - 1 Nos, Preparation of P&I diagram, Creation of Multi visualization screen for Process control, alarm managenent, Historical and realtime process trend, Daily reporting etc complete as per requirement & direction of Engineer - in - Charge (Including license key)
1
-
-
Power connection charges deposit to TATA Power & commissioning at site.
1
-
-
Supply, Installation, Testing & Commissioning of 1KVA Online UPS with external battery type, Having Double conversion IGBT based online UPS system with builtin Isolation Transformer, Input 150-250VAc 1Phase,50Hz, output: 230 VAC,1Phase,50Hz. . All completed as per electrical specification and as per direction of EIC. To be installed in existing PLC pannel of Department.
1
-
-
Supply, Laying,testing,glanding & termination of control Cable including Supply of All materials T&P and Labour Etc. All completed as per electrical specification and as per direction of EIC of approved make lap.
-
-
-
Supply of 2.5 sqmm x 4 Core CU. Armourded cable (lapp make)
1200
-
-
Supply of 2.5 sqmm x 7 Core CU.Armourded cable (lapp make)
1200
-
-
Supply of 2.5 sqmm x 4 Core CU.Armourded. Shielded cable automation (lapp make)
1000
-
-
19 mm DC Gland
40
-
-
2.5 mm CU socket
60
-
-
Laying of HDPE pipe by HDD method using HDD machine upto 90mm dia including hire charge of HDD machine, operator, POL, Lubricant etc complete in all respects, including all labour and materials complete as per specification and directions of Site Engineer /Engineer-in-Charge.
1000
-
-
CABLE TRENCH: Excavation in unpaved areas of earth in work sites for conventional cable trenches for a depth upto 0.9 metres or bellow to the water Pipeline including backfilling the trench, job complete in all respects, including all labour and materials complete as per specification and directions of Site Engineer /Engineer-in-Charge.
1
-
-
HDPE PIPE: Supply and Laying of 40MM dia HDPE pipe (Make: Supreme/equvalent) in cable trench as per specification and directions of Site Engineer / Engineer-in-Charge.
1
-
-
Supply and Installation of pre-fabricated GRP Joint Box with Iid size 600 x 600 x 600 mm for OFC loop and termination as per telecom specification and directions of Site Engineer / Engineer-in Charge.
2
-
-
OFC: Supply and Laying of 12core armoured Optical fibre cable (OFC :fiber glass with F-G 62.5/125micron, 2.6DB/KM F600) to various sites through HDPE pipe /in AIR ( pole to pole ), prelaying testing of each cable drum for each fibre and taking the OTDR traces, submission of OTDR traces (in hard as well as soft copy) to Engineer-in-charge/ Site Engineer.
1000
-
-
Supply and Installation of OFC jointing kits as per drawings, specifications and directions of Engineer-in-charge/Site Engineer.
10
-
-
Supply, Installation, Testing Wiring & Commissioning IP 66 rated Metal outdoor Flowmeter display panel- having 16A Dp RCBO 30Ma-1Nos, 6A DP MCB-2 Nos, 2A SP MCB-2NOS, 24VDC 5A Power supply module-1 Nos, complete with all inter connection with copper wire with coper lugs. - All switchgear and controlgear make- Siemens,schneider,ABB,L&T,LEGRAND. All completed as per electrical specification and as per direction of EIC.
2
-
-
Supply, installation of convential earthing with crystalline conducting material for Back Fill Compound & installation of Maintenance Free Earthing Electrode with ISI mark G.I. Pipe dia 50mm as Secondary electrode with wall thickness of 2.6mm and the primary earthing electrode will be 25mm x 6mm hot dipped galvanized strip filled with a highly conductive & non-corrosive compound in between the primary earthing & the secondary earthing. A solid G.I. Base plate of 300 x 300 mm seals the unit at the bottom. Ground filling compound will be provided in 25kg per bag - 2nos. Excavation of earth pit refilling, Precast RCC chamber with lid etc. all complete as per the site requirement.
2
-
-
Supply & fixing of Pressure transmeter 15mm bore (transducer) to be installed in delivery main with following technical specification i,e. Range up to 7 kgf/cm2,Type-Sensor, Power Supply-24 DC, Out put-4 to 20mA, Make-WIKA-S-10 with cock , short piece.
4
-
-
Supply & installation of SS body diaphragm type Pressure gauge of 0-7kgf/sqcm of 150mm dial with s.s snubber, 15mm 3way s.s gauge cock, ss steel stem etc complete
4
-
-
Supply of Level indicator with digital display to be installed at UGR with following specification
Range= 0 to 8 mtr Type =Radar Power Supply=24V DC Out Put=4-20mA Make=E&H/ABB/VEGA.
1
-
-
for UGR
-
-
-
Supply & installation of industrial Hooter for emergency situation like (over flow of water & contamination of water) and duly programmed with PLC logic etc.
1
-
-
Supplying all materials,labour and T&P and constructing RCC chamber as per P.H. specification and design all complete including RCC Cover Slab (per each) (Size- 3.00 x 2.00 mtr)
2
-
-
Installation of 82.50 KVA DG with mandotary spare including commissioning.
1
-
-
G.I. Cable tray 150 x 50 x 50 mm(1.20mm)
423
-
-
120 sqmm Al armoured Cable XLPE, 11 kv grade
184
-
-
Boosting pump mandatory spare (Mechanical seal with close coupling including base plate)
2
-
-
Supply of DI Float control Valve of Double CHAMBER(Globe Type) with orfice plate for purpose to close valve at a maximum water level of ESR & to open to refill the ESR when the water level in the ESR at lowers. Altitude Control Valve should be worked at minimum pressure 1kg/cm2. An altitude control valve controls the level of a tank. The altitude valve will remain open while the tank is not full and it will close when the tanks reaches its maximum level. The opening and closing of the valve will work without external power source (electric, pneumatic or man power), it will work automatically,The body, Spool, & cover will be DI ASTM A-536 standard, Spring, steam, Jam Nut, Cover bolt & cover washer should be SS, DI /SS Diaphragm plate, Nytril/Nylon diaphragm, Bronze cover bushing, Seat plate & ring. The Approved Make : (VAG/SINGER/CLA/BURMAD-700/DOROT-S300)with 2 nos solenoid including cost of material with all taxes transporataion to Site/Storage with insurance.
2
-
-
Flat Board
1
-
-
Supply fitting fixing of 8mm thick , 200mm dia MS pipe with epoxy paint & necessary specials (25mm thick machined flange,S.S 202 grade nut bolt & spring washer, 5mm thick black rubber insertion etc.) including cutting & welding towards fitting fixing of Sluice valve, Flow meter with RCC chamber,Control valve, including cost of all materials,laabour etc all complete as per direction of EIC, at identified location but excluding cost of valves & meter. Header main with valve (5 sets)
1
-
-
SS Dismantling Joint 200mm
8
-
-
Electro mechanical Pressure Gauge with display (E & H, emmerssion)
2
-
-
VFD of 37 kw ,Control Panel with distribution & Head main panel of approved make. (Control technic,ABB)
6
-
-
Inline Pump sets 40 HP (Ground foss,Xilam) head-45 mtr, Discharge-156 mtr cu/hr
4
-
-
3 phase Actuator - 200mm dia, (Inch type) (Auma make, model- E-pack)
4
-
-
Yard Lighting with cable,jointer box,earthing in each location of light post. (approved make)
1
-
-
S.S grade-316, Display Board (approved Size)
1
-
-
Controlling unit consist of mechanical joint 2 nos, Globe Valve, Basket strainer & woltman type meter including 100mm dia (6.30mm thick) with flange (20mm thick) m.s. piping with enclosure.
25
-
-
Remote terminal unit panel of 8 D.I., 8 D.O., & 4 A.I. with necessary protection & wiring.(Phonix,ABB,Simens)
25
-
-
Provision for supply testing and commissioning of chemical feed pump 0 to 100 in proportion to 4 to 20 mA signal.100 SPM@75Hz and 67 SPM @50Hz Motor frequency range=15 to 75 Hz Auto/manual, Remote, while running or at rest,5:1 Turn down ratio, Over and above there will be provision for manual stroke variation. The disch piping and fitting starting from the pump flange upto the tank nozzle including VFD 3 phase input and 415 volt 3 phase output and will have a rating of 3 HP. Inverter will receive a signal of 4 to 20 mA signal with electric installation etc. all complete
1
-
-
Installation charges of chemical feed pump with storage tank & accessories including all piping arrangement and hire charges of Hydra etc all complete & commissioning.
1
-
-
Supplying of control panel with VFD for running of chlorine dosing pump and motor etc compatible with SCADA & PLC system etc all complete as per direction of Engineer-In-charge
2
-
-
Supply and installation of Online Chlorine, Turbidity & PH analyser with following technical specification:-( E & H / Trios,Chemitech,aqudax) with MQTT protocol for data transmission.
1
-
-
Chlorine Sensor with RS485 Modbus output
-
-
-
Battery (4x 19AH)
-
-
-
5 Micron Cartridge Filter
-
-
-
4G Modem with GSM/ Ethernet / Fibre Output
-
-
-
FRP / Stainless steel Enclosure
-
-
-
Flow cell for Chlorine & Turbidity Sensor
-
-
-
Turbidity Sensor with RS 485 Modbus output
-
-
-
PH Sensor
-
-
-