Airports Authority Of India Tender
Know all about the latest MP tenders along with the tender details and downloadable document on BidAssist. Here, on this page, we shall help you search for every MPtender posted on the official website of mptenders.gov.in according to authority, district, etc. Be it an irrigation tender or MP PWD tender, and we will tell you how to bid for these and more.
Airports Authority Of India - AAI Tender
Aerospace and Defence
Eprocure
Opening Date11 Jun 2024
Closing Date1 Jul 2024
Tender Amount₹ 2,55,59,496
Costs
EMD
₹ 5,11,190Document Cost
₹ 1,120Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_AAI_197553_1Bid Award Id
ViewTender No
AAI/BPL/ENGG(E)/NIT-02/2024-25Tender Authority
Airports Authority Of India ViewPurchaser Address
-Website
http://https://www.aai.aero/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Provision of additional hour required for operations due to delay in flight, emergency, major maintenance works. Beyond the scope of item no. 1 on daily basis.
Un-skilled
50
-
-
Inspection, servicing and testing of 3 Pole, 1250A, 33 KV, HT Vaccum circuit Breakers (4 Nos. VCB ) (Make: ABB) installed at ESS Block at new ATS complex Bhopal Airport, including carrying out the following tests & preventive maintenance alongwith submission of the test reports.
(a) General inspection (b) Wiring check including control circuit and indications.
(c) IR test between poles to poles, between poles to earth in closed condition and between pole to pole in open condition. (d) Continuity of power contacts.
(e) Continuity of auxiliary contacts.
(f) Resistance measurement of tripping coil.
(g) Closing, tripping and inter- locking testing.
(h) Tripping through relay operation.
2
-
-
Calibration of 33 KV HT panel of relays of C&S make (01 Over current relay + 01 Earth fault relay + 01 Master trip relay) complete by digital relay testing set of the Airport ESS Block including relay co-ordination etc. - 4 Nos.
2
-
-
Inspection, servicing and testing of 3 Pole, 800A, 11KV, HT Vaccum circuit Breakers (2 Nos. VCB ) (Make: Crompton Greaves) installed at Old power house at Bhopal Airport, including carrying out the following tests & preventive maintenance alongwith submission of the test reports.
(a) General inspection (b) Wiring check including control circuit and indications.
(c) IR test between poles to poles, between poles to earth in closed condition and between pole to pole in open condition. (d) Continuity of power contacts.
(e) Continuity of auxiliary contacts.
(f) Resistance measurement of tripping coil.
(g) Closing, tripping and inter- locking testing.
(h) Tripping through relay operation.
2
-
-
Calibration of 11 KV HT panel of relays of Crompton Greaves make (01 Over current relay + Earth fault relay, type-CGI 14 N) complete by digital relay testing set of the Airport power house including relay co-ordination etc. - 2 Nos.
2
-
-
Inspection, servicing and testing of 4 Pole, 1250A, 440V, LT Air circuit Breakers (5 Nos. ACB ) (Make: L&T) installed at ESS Block at Bhopal Airport, including carrying out the following tests & preventive maintenance alongwith submission of the test reports.
(a) General inspection (b) Wiring check including control circuit and indications.
(c) IR test between poles to poles, between poles to earth in closed condition and between pole to pole in open condition. (d) Continuity of power contacts.
(e) Continuity of auxiliary contacts.
(f) Resistance measurement of tripping coil.
(g) Closing, tripping and inter- locking testing.
(h) Tripping through relay operation.
2
-
-
Inspection, servicing and testing of 4 Pole, 1250A, 440V, LT Air circuit Breakers (4 Nos. ACB ) (Make: ABB) installed at ESS Block at Bhopal Airport, including carrying out the following tests & preventive maintenance alongwith submission of the test reports.
(a) General inspection (b) Wiring check including control circuit and indications.
(c) IR test between poles to poles, between poles to earth in closed condition and between pole to pole in open condition. (d) Continuity of power contacts.
(e) Continuity of auxiliary contacts.
(f) Resistance measurement of tripping coil.
(g) Closing, tripping and inter- locking testing.
(h) Tripping through relay operation.
2
-
-
Inspection, servicing and testing of 4 Pole, 2500A, 440V, LT Air circuit Breakers (2 Nos. ACB ) (Make: ABB) installed at ESS Block at Bhopal Airport, including carrying out the following tests & preventive maintenance alongwith submission of the test reports.
(a) General inspection (b) Wiring check including control circuit and indications.
(c) IR test between poles to poles, between poles to earth in closed condition and between pole to pole in open condition. (d) Continuity of power contacts.
(e) Continuity of auxiliary contacts.
(f) Resistance measurement of tripping coil.
(g) Closing, tripping and inter- locking testing.
(h) Tripping through relay operation.
2
-
-
Inspection, servicing and testing of 4 Pole, 4000A, 440V, LT Air circuit Breakers (1 Nos. ACB ) (Make: ABB) installed at ESS Block at Bhopal Airport, including carrying out the following tests & preventive maintenance alongwith submission of the test reports.
(a) General inspection (b) Wiring check including control circuit and indications.
(c) IR test between poles to poles, between poles to earth in closed condition and between pole to pole in open condition. (d) Continuity of power contacts.
(e) Continuity of auxiliary contacts.
(f) Resistance measurement of tripping coil.
(g) Closing, tripping and inter- locking testing.
(h) Tripping through relay operation.
2
-
-
Dehydration and filtration of transformer oil at AAI site including testing the BDV before and after testing and submission of test reports etc. as required for following Transformers.
500 KVA Transformer (Make: Voltamp)
2
-
-
Dehydration and filtration of transformer oil at AAI site including testing the BDV before and after testing and submission of test reports etc. as required for following Transformers.
630 KVA Transformer (Make: Voltamp)
2
-
-
Supply and topping of transformer oil (Tested).
100
-
-
Painting of following poles in 2 coats by using Aluminium paint of approved make (Asian / Berger) including pole boxes, cleaning of surface etc., as required including rewriting the identification Sl.No. 50 mm Gl pipe pole of length not exceeding 3 Mt.
480
-
-
Painting of following poles in 2 coats by using Aluminium paint of approved make (Asian / Berger) including pole boxes, cleaning of surface etc., as required including rewriting the identification Sl.No. 75 mm Gl pipe pole of length not exceeding 3 Mt.
150
-
-
Painting of following poles in 2 coats by using Aluminium paint of approved make (Asian / Berger) including pole boxes, cleaning of surface etc., as required including rewriting the identification Sl.No. Tubular street light poles of length not exceeding 11 Mt.
170
-
-
Spray Painting of sheet metal enclosures of electrical panels inside the power house, Pump room & ATC building & terminal building including cleaning the surface and one coats of grey or any other color of make (Asian / Berger) including rewriting the identification the circuit, Protecting and covering the electrical accessories during painting and removing after work is over etc., as reqd.
60
-
-
Painting of sheet metal enclosures of electrical equipments such as feeder pillars, distribution boards, electrical panel, frame etc. including cleaning the surface and one coat of grey or any other color of make (Asian / Berger) including rewriting the identification the circuit, Protecting and covering the electrical accessories during painting and removing after work is over etc., as reqd.
30
-
-
Carrying out /Making in-field measurement/testing of intensity, beam spread/coverage, orientation, chromaticity, luminous factor, setting of field alignment, toeing angle, elevation angle as per the requirement of site & ICAO/Civil Aviation Requirement (CAR) Section-4 Aerodrome standard & licensing series ‘B’ Part-I, for inset/ elevated type approach(CAT-I /CAT-II), runway edge, runway end, threshold, PAPI, Touch down zone lights (TDZ), Rwy centre line lights & operational area signage board etc. airfields ground lights at R.B. Airport Bhopal, by using suitable/standard Testing Equipment system / frame Reader, submission of test reports etc. complete as required as per technical specification. (Test will be conducted on every 6 months or as instructed by E-I-C)
(Approx. qty. of fittings: Rwy Edge Light (Elevated) - 162 Nos., Rwy Edge Light (Inset) - 20 Nos., Threshold light 30 - 36 Nos., Threshold light 12 - 12 Nos., End light 30 - 12 Nos., End light 12 - 12 Nos., Rwy centre line lights - 182 Nos., Rwy TDZ lights - 180 Nos., Approach light 30 - 194 Nos., Approach light 12 - 17 Nos., PAPI 30 - 4 Nos., PAPI 12 - 4 Nos., Signages - 55 Nos.)
4
-
-
CPWD Schedule of rates DSR-2022 (Electrical) items of Rs. 4,00,000/- - Chapter 01 to 10 & 14 The rate shall be quoted for this item as per examples given below- • Please refer clause 43 of GTT page No. GTT-10 before quoting rates for this item. • If bidder wants to quote the rates at par with rates of DSR-2022 (E & M), then bidder has to quote 1.00 in the rate column. • If bidder wants to quote the rates 10% above the rates of DSR- 2022 (E & M), then bidder has to quote 1.10 in the rate column. • If bidder wants to quote the rates 10% below the rates of DSR- 2022 (E & M), then bidder has to quote 0.90 in the rate column.
400000
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements