Military Engineer Services Tender
View complete overview of Lakshadweep MES Tender
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date20 Dec 2023
Closing Date18 Jan 2024
Tender Amount₹ 15,00,000
Costs
EMD
₹ 30,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_MES_633581_1Bid Award Id
ViewTender No
8381/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Taking down old unserviceable cable after meggor test from existing position and Supply and fix strandard aluminium conductor with 1100 volts grade heavy duty UG cable XLPE insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed LT UG cable 25 sqmm 4 core complete all as specified and as directed by Engineer-in-Charge.
100
-
-
Taking down old unserviceable cable after meggor test from existing position and Supply and fix strandard aluminium conductor with 1100 volts grade heavy duty UG cable XLPE insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed LT UG cable 50 sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Taking down old unserviceable cable after meggor test from existing position and Supply and fix strandard aluminium conductor with 1100 volts grade heavy duty UG cable XLPE insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed LT UG cable 95 sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
50
-
-
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 depth and getting out soft/loose soil for laying cables/pipes/erection of poles etc complete all as specified and as directed by Engineer-in-Charge.
100
-
-
Returning filling in, with excavated soils incl. spreading, levelling, watering and well ramming in layers n.exc. 25 Cms. complete all as specified and as directed by Engineer-in-Charge.
69
-
-
Removing excavated material/ surplus soil not exceeding 50 M and depositing where directed at a level n.exc. 1.50M above the starting point, complete all as specified and as directed by Engineer-in-Charge.
31
-
-
Supply and spreading in trenches for sand cushioning with two layer, first layer of 80mm thick before laying of cable and second layer of 150mm thick after laying of cable in trenches/ducts for cable including consolidation of each layer complete all as specified. Note: Thickness of sand cusioning shall be measured after punning complete all as specified and directed by Engr-in-Charge.
30
-
-
supply and Laying unreinforced precast concrete cable cover class LV 1 flat size of size 250x150x40 mm for LT Cable all sizes complete all as specified and directed.
2700
-
-
Material and labour for cutting the existing hardstanding not less than 25cm in deep and 45cm in width for laying of underground cable through GI pipe and making good the disturbed surfaces complete.
15
-
-
Supply and fix GI tubing 50 mm dia light grade ISI marked laid in trenches complete with all accessories such as Tees union , bend ,elbow nipple reducer etc as required for protection of UG Cable on floor, Pole etc complete all as specified and directed .
10
-
-
Supply and fix in replacement of MCCB 63 A, 16 KA, 4 Pole ,415 V, 50 Hz of capacity including all connections complete all as specified and as directed by Engineer-in-Charge.
3
-
-
Supply and fix in replacement of MCCB 100 A, 25 KA, 4 Pole ,415 V, 50 Hz of capacity including all connections complete all as specified and as directed by Engineer-in-Charge.
3
-
-
Supply and fix in replacement of MCCB 160 A, 36 KA, 4 Pole ,415 V, 50 Hz of capacity including all connections complete all as specified and as directed by Engineer-in-Charge.
3
-
-
Supply and fix in replacement of MCCB 250 A, 36 KA, 4 Pole ,415 V, 50 Hz of capacity including all connections complete all as specified and as directed by Engineer-in-Charge.
2
-
-
Supply and fix in replacement of MCCB 400 A, 36 KA, 4 Pole ,415 V, 50 Hz of capacity including all connections complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Material and labour for painting of existing LT panels by using two coats of synthetic enamell paint after removal of the rusted portions complete all as specified and as directed by Engineer-in-charge.
6
-
-
Material and labour for repair to existing LT panels front and rear doors of locking arrangements by using suitable hinges complete all as specified and as directed by Engineer-in-charge.
6
-
-
Taking down high mast light fittings manually from 12m height steel pole and disconnectioning the SS rope and replace the unserviceable parts such as , double drum winch, 5mm diameter SS wire rope 5 runs, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial , outdoor stand mounted feeder pillar box and made the High Mast light fully functional and raising the hight Mast light fittings in its original postion and testing complete all as directed by Engineer in charge.
(i) Cost of miscelleneous items which are not mentioned above but are required for satisfactory completion deemed to be included in the rate quoted by the contractor. (ii) Oiling/greasing for chain/ rope, motor rewinding, Auto/Manual function of Timer panel etc. deemed to be included in the unit rate.
(iii) LED flood lights,Timer, Aviation light, Cable will be measured and paid separately under the relevant items of this schedule.
2
-
-
Supply and fixing LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed by Engineer-in-charge.
4
-
-
Supply and fix inreplacement of Aviation obstruction light including all connections complete all as specified and directed by Engineer-in-charge.
2
-
-
Supply and fix inreplacement of Timer switch with power contactor for high mast light complete all as specified and directed by Engineer-in-charge.
2
-
-
Supply and fix inreplacement of 5 Core Copper cable of size 2.5 Sqmm for high mast light fittings complete all as specified and directed by Engineer-in-charge.
90
-
-
Supply and fix inreplacement LED bollard lighting of 8W energy saving and environmental friendly long life aesthetically designed aluminium landscape IP 65 luminare for diffused lighting with high power LED as light source including all connections complete all as specified and directed by Engineer-in-charge.
8
-
-
Supply and fixing in replacement of LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engineer-in-charge.
12
-
-
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection
with impact and corrosion resistant complete with driver and lamp complete all as specified and as directed by Engineer-in-charge.
4
-
-
Material and labour for fixing FRP composite poles burial type 8.5 mtr length including GI single arm bracket with fixing arrangements, excavation and earthwork, PCC cable connections including disconnecting and removing the unserviceable /corroded street light steel tubular poles complete all as specified and as directed by Engineer-in-charge.
Note : Earth work, PCC will be measured and paid under respective items of the schedule.
3
-
-
Material and labour for complete removal of existing paint of steel tubular poles length up to 9 mtr including prepration of outer surface and applying two coats of aluminium paint over a coat of red oxide primer and two strip of blue colour paint of size 30 cm width from bottom of pole height 30 cm, including numbering to pole with base paint of yellow colour and Black for numbering which shall not be less than 100 mm in height and 10 mm in width complete all as specified and as directed by Engineer-in-charge.
8
-
-
Material and labour for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron or steel earth lead wire 4 mm dia size by mean of nut/bolt and washer of galvanized iron or steel all as shown in electrical plate no 3 of SSR part I 2020 including necessary excavation and earth work GI pipe 20mm dia medium grade ISI marked for watering and GI 15mm dia medium grade ISI marked pipe for protection of GI earth wire on wall etc, PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to DB as indicated including testing complete all as specified and as directed by Engineer-in-charge.
2
-
-