Military Engineer Services Tender

Bidassist is designed as a single destination for all government tenders from across the world in one place. If you require any information or detail about any e-tender the Ladakh government has posted, Bidassist helps a registered bidder to get the same.As BidAssist is a very user-friendly website it will help you find the specific Ladakh etender you're looking for. Read further to learn how to search and bid for etender Ladakh.

Military Engineer Services - MES Tender

Works
Machinery and Tools
Eprocure
Opening Date10 Jun 2024
Closing DateCancelled
Tender Amount₹ 2,30,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Dismantiling of existing structural steel members of any description and refixing of same by welding, riveting or nut and bolt all as required for making addition alteration in existing steel structure. Note:-(work will be executed at a height upto 12 mtr. Rates are inclusive of necessary scaffolding and formwork required to execute the work)

1

-

-

... More
Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for complete all as specified and directed by Engineer–in–Charge.

36

-

-

... More
Dismantling and removal of PUF panels of any description fitted to doors up to 8m in heights

444.84

-

-

... More
S&F Pre–painted (powder coated) Galvalume aluminium zinc coating GI based semi corrugated steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall, fixed with self tapping screws complete all as specified and directed by Engineer–in–Charge. Note:-(work will be executed at a height upto 12 mtr. Rates are inclusive of necessary scaffolding and formwork required to execute the work)

86.91

-

-

... More
S&F roof trusses (framed) trussed, purlins, crane gantries, rails and fastenings and heavy brackets framing (beam, tee, angle, channel, I–section or flat sections) incl distance pieces, cleats etc complete all as specified and directed by Engineer–in–Charge. Note:- ( Welding fabrication and installation under this item will be carried out at a hight of approx 12m. Rates are inclusive of necessary scaffolding and formwork required to execute the work)

1302.72

-

-

... More
M & L cement concrete work in pavement/ hard standing of flexural strength 40 kg/ per square centimeter in field using 400 kg of cement per cubic meter.

40.16

-

-

... More
M & L for forming 12 mm thick expansion joints in 300 mm thick concrete, filled with preformed bitumenous filler and top 30mm primed and sealed with sealing compound grade 'B' complete all as specified and directed by Engineer–in–Charge.

8

-

-

... More
M & L anodised aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing, heavy duty aluminium hinges etc complete all as specified fixed with necessary screws on door or ventilator openings in PUF cladding of design and section complete all as specified and directed by Engineer–in–Charge.

180

-

-

... More
M & L Anodised aluminium window and ventilator shutters, fixed type without sash bar., aluminium section weighing 0.55 kg/m including joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws etc complete all as specified and directed by Engineer–in–Charge.

22.56

-

-

... More
S & F Frosted/Tinted 5.5 mm thick sheet glass, ordinary quality and glazing in square n exc 0.50 sqm in each pane complete all as specified and directed by Engineer–in–Charge.

6.23

-

-

... More
S & F Frosted/Tinted 5.5 mm thick sheet glass, ordinary quality and glazing in square exc 0.50 sqm in each pane complete all as specified and directed by Engineer–in–Charge.

11.88

-

-

... More
Material & Labour for applying two or more coats of 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives @ 1.43 liter/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 liter /10 sq.m over new surfaces. Making camouflage pattern complete all as specified and as directed by Engr-in-Charge. Note:-(work will be executed at a height upto 12 mtr. Rates are inclusive of necessary scaffolding and formwork required to execute the work)

960

-

-

... More
M & L for preparation of old steel surfaece of any description over 10 cm in width or girth and applying one coat of synthetic enamel paint.complete all as specified & as directed by Engr-in-Charge. Note:-(work will be executed at a height upto 12 mtr. Rates are inclusive of necessary scaffolding and formwork required to execute the work)

800

-

-

... More
M & L for preparing dry concrete surface using proper scarifying equipment to remove any loose material, contaminations and laitence to provide a sound gripping surface, cleaning the entire floor area using a powerful industrial vaccum cleaner complete all as specified and directed by Engineer–in–Charge.

90

-

-

... More
M & L for 7mm thick (average) Epoxy flooring over concrete floor: Providing and applying a coat of epoxy resin based primer for concrete surface with sika floor 80@ 0.25 Kg/Sqm Providing and applying chemical and abrasion resistant epoxy resin modified cementetous screed sika floor -82 Epocem wit the following properties:- Chemical Base: Modified epoxy resin solvent free low VOC Thermal Expansion Co- efficient = 17.5*10-6 per C (similar to concrete) accn EN 1770 Carbon dioxide diffusion co-efficent uCO2= 1782 acc klopfer / engelfried method. Water vapur diffusion co - efficient uH2O =177 Acc DIN 52617 Water absorption co-efficient W = 0.06 kg/M2 x h.5 acc DIN 52617 Compressive strength 55 N/mm2 IS 9162-1979 Flexural Strength 10N/mm2 IS 9162-1979 EN 13892-8 Bond strength 1.50 N/mm2 (100% concrete failure) Mixed density : 2.25 Kg/Litre applied at a theoretical coverage rate of 11.25 Kg/m2 /5 mm Providing and applying 2mm thick epoxy, coloured, heavy duty high DFT coating sika floor 264 hc with following properties:- Low VOC solid content 100% by volume and weight compressive stength 50 N/mm2 EN 196-1 Flexural strength 20N/mm2 EN 196-1

90

-

-

... More
S & F 60 mm thick PUF sand witched panel with 0.5 mm thick pre coated galvalume sheets on both side, edges and at all ends of PUF Panel as in cladding to hanger door structure with necessary screws to hold the claddingcomplete all as specified and directed by Engineer–in–Charge.

491.64

-

-

... More
S & F 40mm thick PUF sand witched with 0.5 mm thick pre coated galvalume sheets on both side as in door shutters including mortice lock with handle of design and section complete all as specified and directed by Engineer–in–Charge.

7.2

-

-

... More
S&F in repairs 50 mm thick and 300 mm wide sheet / gasket made of rubber or other synthetic material fixed with suitable aluminium beading and screwing to sliding door panel between overlap of the door to protect the het from inside to outside and vice-versa complete all as specified and as directed by Engr-in-charge.

150

-

-

... More
M&L for preparation of previously untreated new description new steel surface of any description over 10 cm in width or girth and applying two coat of synthetic enamel paint over a coat of mordent solution.prime, complete all as supecified & as directed by Engr-in-Chage. Note:- (work will be executed at a height upto 12 mtr. Rates are inclusive of necessary scaffolding and formwork required to execute the work).

53.39

-

-

... More
Excavation in post holes(or similar holes) in hard/dense soil each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubblemixed with earth around, in layers not exceeding 25 cm.

12

-

-

... More
Sch A part-II E/M ITEMS

-

-

-

... More
Dismantling of old unserviceable central heating system including thermic fluid heaters (one working + one standby) , pipings, pumps, ducting, AHUs, grills, diffusers, control panels, LT panels etc. complete all as specified and as directed.

1

-

-

... More
Taking down carefully smoke detectors/heat detectors/light fittings/ Response Indicators from the existing false ceiling , keeping in safe custody and refixing the same on the false ceiling with existing electric connections in the existing position complete all as specified and as directed. Note : (i) All necessary accessories/wires/cables/false ceiling which have been damaged during taking down shall be deemed to be included in the quoted rate. (ii) Serviceable light fittings, fire alarm detector/ sensor, cable shall be refixed at the existing position or at the position as directed and unserviceable light fittings shall be replaced with new ones and the same shall be measured and paid separately under respective item of BOQ all as specified and directed. (Fire alarm detectors - 124 nos., response indicators - 16 nos., highbay lights- 98 nos.) contractor shall install the Fire control panel with minor repair if required and fire sensors , multi sensors, hooter and conneted control wiring after completion of the work. No additional payment will be paid for this work.

1

-

-

... More
Supply, Installation ,commissioning and testing of complete heating plant including boiler uniit, chimney complete with all accessories as per the following. (A) Thermic Fluid Heaters 03 Nos. (2 W +01 S/BY) : Supply, installation, commissioning and testing of pressurised type 3 phase reverse flame horizontal / vertical smoke tube, Thermic fluid heaters (Three Nos) 2 Nos of working and 01 No stand by arrangement ,each of capacities 3,00,000 K Cal/Hr complete in all respect, with standard accessories to meet the required condition of Leh station with temp and humidity criteria for hangar complete in all respect with combustion chamber and equipment , automatic monoblock burner assy, fire tubes, control panel with sequence controller , photocell for frame failure , HT transfer combustion chamber and equipment automatic monoblock burner assy, fire tubes, control panel with sequence controller, photo cell for flame failure, HT transfer electrode blower assy, electrical panel, mounting frames, pressure gauge at inlet and outlet suitable operation on 50HZ three/single phase AC supply compete in all respect to maintain the inside temperature 20+/-2 degree celcius and RH = 50% +/- 10% when the outside temperature drops to (-25) degee celsius i.e Leh winter climatic conditions including following items of work.

1

-

-

... More
The boiler minimum specifications should be as under :- (a) Heater unit:-Heat exchanger ,consisting of closely wound, helical concentric coils double jacketed arranged to give adequate no. of passes on flue gas side & made out of ERW tubes confirming to BS 3059 Pt-I suitable for high temperature all as per manufacturer design and of required head and capacity . (b) Pressure jet burner:-Suitable for Diesel oil firing with stepless modulation mechanism all as per manufacturer design and of required head and capacity. (c) Combustion air fan with drive motor assembly all as per manufacturer design and of required head and capacity. (d) Control Panel : Dust protected pre-wired unit mounted air cooled control panel housing a burner management system , switchgear consisting of contractors, overload relays, fuses and MCB etc.all as per manufacturer design and of required capacity.

-

-

-

... More
(e) The boiler shall be installed in system of (2W+1S). (f) The tenderer should get the plant installed by any of the original equipment manufacturer with recommended makes of compatible components of items. (g)The cap of boiler has been designed for maintaining the inside temp of 20+/-2 degree celcius for an ambient temp dropping to -25 degre celcius. (h)The boiler inner shell be made from carbon steel with dished ends (curved type) with thickness as per boiler design of OEM. (j)Outer shell be made from carbon steel with thickness as per boiler design of OEM. (k) Boiler tube shall be seamless MS tube for quality commensurate with the boiler requirement . (l) The front door shall be openable lined with high grade insulation and refactory (m)High efficient, low noise imported monoblock burner. (n)The boiler shall be insulated with 50mm thick resin bonded fibre glass wool and cladded with 22 guage GI sheet (epoxy painted) or any other thermal insulation as per OEM design.

-

-

-

... More
(o)Pre wired control panel (made from 18 guage CRC sheet ) Main incomer, MCB in/out temperature controller (digital)fault indicating light for water high temp, burner trip,flue temp, with alarm, hour meter for maint schedule etc. (p) 1 set of oil piping from unit to burner . (q) It includes suitable concrete foundation for Boiler . ( B) FLUE GAS CHIIMNEY Supply, installation of mild steel flue gas chimney to accomodate emission of simultaneous running of 02 Nos of Boilers each of cap 3.0 LakhsKcal/Hr made out of 3 mm thick mild steel sheet, minimum 3 mtr above the highest point of plant room as per manufacturer recommendations which ever is higher including connection to each boiler. Note : - (a) The item shall be complete with the mounting/fixing arrangement all as specified by the boiler manufacturer including the dia of the exhaust flue Gas chimney as per the design and specificaton of the boiler installed-01 Nos. (b) The Boilers / hot water generator shall be connected to the chimney. (c) The portion of chimney inside the building shall be insulated with fiber glass insulation wool of density 24 Kg/Cum.The item shall be complete with mounting and fixing arrangement with necessary PCC work complete all as specified and directed. Qty -01 No

-

-

-

... More
(C) Day Oil Storage Tank Supply , Installation,testing and commissioning of HSD oil day storage tank rectangular mild steel (IS 2062) construction of capacity of 1 cubic meter (volume of tank) complete with inlet, outlet, over flow drain and vent with flame arrestor. tank shall be made out of 4mm thick mild steel sheet and will be provided with supports made out of 50mm dia medium grade pipe to keep tank base at minimum 2500 mm above finished floor level. The tank shalll be provided witth level switches for on - off operaton of transfer pump. Extra high level and extra low level alarm shall be provided along with gauge indicator duly callibrated. Tank and structure shall be painted with synthetic enamel paint of approved colour over one coat of primer complete all as specified and directed by Engr in Charge Qty-03 Nos

-

-

-

... More
(D) Glycol Expansion Tank Supply and installation of overhead Glycol expansion tank of size (volume) 1 cubic meter made out of 5 mm thick mild steel cylindrical tank complete covered with 13 mm closed cell elastometric insulation complete with removable lid, in/out/drain/overflows system mounting arrangement making connections etc complete all as specified and directed. Note: The Glycol expansion tank should be at a staging of 5 meter height in plant room and cost of foundation and staging material i.e Angle iron/ steel/MS chequered pipe/flat/welding etc deemed to be included in the quoted rates.-01 No. ( E) Thermic Fluid ( Glycol) Makeup tank Supply and installation of 2.0 cubic meter (volume) capacity MS tank made out of 5 mm thick mild steel cylindrical/ rectangular with removable lid, in/out/drain/overflows system mounting arrangement making connections etc complete all as specified and directed ISI marked.-01 NO

-

-

-

... More
(F)Transfer gear oil pump fuel (self priming) Supply installation testing and commissioning of self priming rotary gear transfer pumps of capacity 15 LPM at 10 Mtrs head for Kerosene or HSD oil complete with base mounting frame. PCC Foundation including holding down bolts , coupling guard and TEFC flame proof motor 2 HP and other accessories required for commissioning etc complete all as specified and directed- 02 Nos (1 Working +01 Standby). (G) Glycol Based Water circulation pump for Boilers:- Supply, installing , testing and commissioning of pumping system consisting of horizontal suction and delivery pump sets having stainless steel impellers capable of delivering 30 LPS of thermic/ethylene glycol water against 25 meter head at outlet and complete as per specificattion. The system shall comprise of the following. Centrifugal pumps with minimum 75% efficeincy , 30 LPS delivery at 25 mtr head suitable for parallel operation speed 1500 RPM including prime mover squirrel cage inducttion motor with TEFC enclosure and suitable power to drive the pump efficiently with class F insulation , 1500 RPM synchronous speed, operating on 415 +10% volts, 3 Phase , 50 HZ AC supply. (02 working +01 Standby)

-

-

-

... More
(i) Insulation of suitable thickness duly cladded by aluminium sheets off 0.5mm thickness and prroperly clamped to pumpset as per specifications required-01 Lot (ii) Mounting frame with antivibration pads for 03 Nos Pumpsets-01 Lot (ii) RCC cement concrete foundation for the pumping unit as per OEM . Note : (i) Anything missed out above , but required for smooth operation of central heating system is deemed to be included in the quoted rate. (ii) The capacity of pump given are minimum estimated , however on detailed calculation if the capacity needs to be enhanced for achieving the desired conditions in the conditioned space of the hangers as brought at above is deemed to be included in the quoted rate and accordingly contractor is advised to quote their rate. No Deviation order/Special rates /Star Rates in this regard in future shall be admissible.

-

-

-

... More
Bulk Oil Storage Tank Design, supply , installation ,testing and connecting with the system and commissioning of horizontal cylindrical oil storage tank made out of mild steel including connecting to existing day oil storage tank of capacity 1 .0 cum ( cubic meter) volume with following paramaters. (a) Storage capacity (Nominal) : 5.0 cum (b) Shell thickness 5mm( minimum) (c) End plate thickness: 6 mm (Minimum) Note: Tank shall be complete with removable lid with locking arrangement manhole, lifting lug, vent pipe dip stick and inlet, outlet connections and return pipes as per specifications including civil work for installation and staging.

1

-

-

... More
HSD OIL PIPING SYSTEM Supply, installation, testing and commissioning of MS pipes heavy duty for HSD lines confirming to IS 1239 (Part-I) 2004 including clamps, bends, reducers, flanges, nuts, bolts etc. Complete with all respects of following sizes.

-

-

-

... More
40 mm NB

20

-

-

... More
25 mm NB.

30

-

-

... More
S&F Brass ball valves ISI marked 40 mm dia.

1

-

-

... More
S&F Brass ball valves ISI marked 25 mm dia.

4

-

-

... More
S&F Non return valves ISI marked made of gun metal of size 25 mm dia.

2

-

-

... More
S&F Y strainer ISI marked made of gun metal of size 25 mm dia.

2

-

-

... More
THERMIC FLUID/ GLYCOL CHARGE Supplying and filling of mono ethylene glycol/thermic fluid concentrate alongwith the necessary additives and inhibitor as per IS- 5759- 2006 in cognition and sealed in barrels. The freezing temperature shall be below (-) 25 degree centigrade, all specified. However the mode of payment and operations involved for this item shall be as under:- Notes: (a) Mono ethylene Glycol/ Thermic Fluid in concentrated form shall only be measured and paid under this item. (b) Material and labour for filling including first filling required for operation of CHS plant (c) Any other additives and inhibitors as per the requirement laid down in relevant IS shall also deemed to be included in quoted rates. (d) Empty barrels shall be property of MES. (e) Material and labour for mixing ,filling, prepraton of thermic fluid to get total quantity of mixture including first filling requiured for operation of CHS plant and network having 70% quantity of thermic fluid charge available at site and 30% of mono ethylene glycol supplied as above to attain the freezing temperature of mixture as below (-) 25 degress centigrade. The quoted rates shall be deemed to include the above activity work.

4200

-

-

... More
(f) The water for prepration of mixture will be supplied by MES without any extra charges for this item (only). The water shall be supplied at a point decided by GE and quoted rates shall be deemed to include for transportation of same from take off point.

-

-

-

... More
Hot glycol based Circuit Piping Supply, Installation, testing and commissioning of "C"class mild steel hot water piping conforming to IS: 1239 (Part-I) 2004 with all necessary fittings like bends, tees, reducers, flanges, supports and duly insulated with fiber glass wool insulation with suitable thickness.as per given below. The joints shall be sealed with 50 mm X 1 mm thick self adhesive tape complete as per specifications.

-

-

-

... More
(i) 80 mm NB with 50 mm thick fiber glass insulation.

250

-

-

... More
(ii) 50 mm NB with 50 mm thick fiber glass insulation

250

-

-

... More
(iii) 25 mm NB with 50 mm thick fiber glass insulation.

80

-

-

... More
Note: (a) Pipe outside/inside the building shall have cladding of 0.5 mm thick aluminium sheets over 50 mm fiber glass insulation and as per specification.

-

-

-

... More
Valves Supply, installation, testing and commissioning of following PN-1.6 valves,ISI marked, strainers gauges in the water piping duly insulated to the same specifications as the connecting piping and adequately supported as per specification and drawings . The water circuit with all fittings and insulation with cladding as per the drawings and specifications.

-

-

-

... More
(i)Butterfly valve of size 80 mm dia.

10

-

-

... More
(ii)Check Valve of size 80 mm dia.

2

-

-

... More
(iii) Check Valve of size 50 mm dia.

5

-

-

... More
(iv) Y-Strainer of size 80 mm dia.

2

-

-

... More
(V) Balancing Valve of size 80 mm dia.

5

-

-

... More
Three-Way Modulating Valve Supply, Installing, testing and commissioning of complete control for AHUs comprising of a set of 3- way modulating proportional linear type valve 80 mm dia for AHUs having manual override facility with Proportionate thermostat and wiring for interconnection with 1.5 sq.mm copper conductor multicore armoured cable suitable for Heating /Cooling complete as per specifications and as required.

5

-

-

... More
AIR HANDLING UNITS/AIR WASHER UNIT Supplying, installation, testing and commissioning of factory built floor mounted water double skin type Air Handling Units/AIR WASHER UNIT of Capacity minimum 25000 CFM made of 25mm thick panels consisting of G.I. Casing of thickness 0.8 mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower suitable for static pressure as detailed below, Humidifier for maintaining the desired relative humidity of heating space, cooling coil section with mechanically bonded aluminium finned copper tubes ( tube thickness not less than 0.5 mm ) cooling coil, filter section with pre filter 90% efficiency and down to 10 micron, direct drive package with flame proof TEFC drive motor suitable for 415+10% volts, 50 Hz, 3 phase, A.C. supply, drain connections, with stainless steel drain pan duly insulated , and necessary vibration isolation arrangement etc. complete as per specifications and drawings of following capacities. AHU 6 ROW COIL, FILTER BANK1-MERV 7, FILTER BANK2- MERV 14, 25000 CFM SUPPLY AIR FAN, STATIC PRESSURE OF FAN 65 MM OF WG at Outlet

4

-

-

... More
(i) The capacity of AHU given are minimum estimated, however on detailed calculation if the capacity needs to be enhanced for achieving the desired climating condition mentioned in the contract, is deemed to be included in the quoted rate and accordingly contrator is advised to quote their rate.

-

-

-

... More
AIR HANDLING UNITS/AIR WASHER UNIT Supplying, installation, testing and commissioning of factory built floor mounted water double skin type Air Handling Units/AIR WASHER UNIT of Capacity minimum 5000 CFM suitable for outdoor application made of 25mm thick panels consisting of G.I. Casing of thickness 0.8 mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower suitable for static pressure as detailed below, Humidifier for maintaining the desired relative humidity of heating space, cooling coil section with mechanically bonded aluminium finned copper tubes ( tube thickness not less than 0.5 mm ) cooling coil, filter section with pre filter 90% efficiency and down to 10 micron, direct drive package with flame proof TEFC drive motor suitable for 415+10% volts, 50 Hz, 3 phase, A.C. supply, drain connections, with stainless steel drain pan duly insulated , and necessary vibration isolation arrangement etc. complete as per specifications and drawings of following capacities. AHU 6 ROW COIL, FILTER BANK1-MERV 7, FILTER BANK2- MERV 14, 5000 CFM SUPPLY AIR FAN, STATIC PRESSURE OF FAN 65 MM OF WG at Outlet

1

-

-

... More
(i) The capacity of AHU given are minimum estimated, however on detailed calculation if the capacity needs to be enhanced for achieving the desired climating condition mentioned in the contract, is deemed to be included in the quoted rate and accordingly contrator is advised to quote their rate.

-

-

-

... More
Ducting work Supply, installation and testing of Site fabricated GI sheet metal ducts as per IS: 655 and IS:277 in accordance with the approved shop drawings and as required by the specifications.

-

-

-

... More
(a) 20 Gauge thickness

900

-

-

... More
(b) 18 Gauge thickness

850

-

-

... More
Note: (i) The contractor has to get duct layout drawings approved from Accepting officer before executing the duct work . (ii) The duct height shall not exceed 4.0 meter from FFL to avoid any stratrification of heated air to ensure uniform distribution of heated air in the conditioned space .(iii) The cost of mounting and installation of ducts at designated height includes cost of suspenders, supports,clamps ,fasteners etc is deemed to be included in the quoted rates .(iv) The quantities of ducts specified are tentative and can vary according to the duct layout submitted and approved and will be paid accordingly to the acutal executed quantity and as per above quoted rate.

-

-

-

... More
Duct Insulation Supply, installation, testing and commissioning of fire retardant nitrile insulation material of thickness 19 mm of thermal conductivity as per specification (Joint shall be sealed with self adhesive tape) including Aluminum clading sheet wrapped all around of 5 mm thickness min.

1750

-

-

... More
Duct Insulation internal Supply, installation, testing and commissioning of fire retardant nitrile insulation material of thickness 13 mm of thermal conductivity as per specification (Joint shall be sealed with self adhesive tape) from inside the duct near AHU to damp the vibrations and to make the duct sound proof.

50

-

-

... More
Supply Air Grilles / Diffusers Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air Grilles/Diffusers with volume control dampers in accordance with the approved shop drawings and specifications.

30

-

-

... More
Fresh Air Intake/Exhaust Air Louvers Supply, installation, testing and balancing of Powder coated/Anodized extruded aluminium construction inlet air louvers with bird screen and volume damper for fresh air as per specifications and atleast 50 mm deep made of GI construction.The blades shall be inclined at 45 degree on a 40 mm blade pitch to minimize water ingress all as specified.

10

-

-

... More
Fire Dampers Supply, fixing, testing and commissioning of fire dampers in supply air ducts / main branch and return air path as & where required of required sizes including control wiring. The spring return action shall be built mechanism and not externally mounted.

20

-

-

... More
MAIN LT PANEL Supply, testing and commissioning of Outdoor type free standing infront operated fully compartmentalized extendable on both sides outdoor weather & dust vermin proof L.T. Panel board suitable for 3 Phase 4 wire, 415 Volts, 50 Hz, AC supply system housed with incoming and outgoing feeders, bus bars, change over switches, interconnections etc , factory fabricated with indoor cubicle type totally enclosed .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminium bus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.. All MCCBs panel should be single Tier for easy cable termination.Cable termination space should be adequate to safely gland and terminate AL/CU cables for the given current ratings with Form B seperation for Incoming MCCB feeders and For Outgoing MCCB feeders.

1

-

-

... More
The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of 100 mm ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry. (i) INCOMING : a) MCCB , Four pole, 400 Amps Icu =36 KA at 415 volts with micrprocessor release with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc-01 Nos b) Bus Bar TPN electrolytic Aluminium extensible type as main bus bars of minimum 600 A capacity (As per capacity of corresponding incoming / Bus couplers), and auxilliary bus bars of suitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 36kA . (c). Metering Section - Suitable rated Digital Ammeter in amps-01 No along with resin type CTs as per design ratio with necessary CT shorting link- 03 Nos , digital volt meter in Volts- 01 No , RYB indicating Lamps-03 Nos , Suitable Load mangaer to have a parameters like KW,KWH,KVA,A,V,PF,KVAR,Active and Reactive componentof the power - 1 No .

-

-

-

... More
(ii) OUTGOING : (a) MCCB, Four pole, 160 Amps, Icu =16 KA at 415 volts with thermal magnetic release - 01 No with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and fixed magnetic setting and Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc. (For AHU Panel 1 serving 3 AHUs) (b) MCCB Four pole 125 Amps Icu =16 KA at 415 volts with thermal magnetic release - 01 No (O/G) with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and fixed magnetic setting and Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc. (For AHU Panel 2 serving 2 AHUs) (c) MCCB Four pole 63 Amps Icu =16 KA at 415 volts with thermal magnetic release - 04 No (3 w+01 S/By) with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and fixed magnetic setting and Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc. (For 3 Nos Boilers Panel)

-

-

-

... More
(d) MPCB 3.2- 6.3 A TP with thermal and magnetic release 415 volts 50 Hz with breaking cap of 100 KA with indicating lamp : On-Trip-Stop with suitable Ammeter along with necesary CTs etc- 02 Nos ( For Gear Pumps) (e) DOL Starter complete with 4 Pole contractor along with OLR in S.S Enclosure suitable upto 2 HP Motor with relay range of 2.4 to 4.0 Amp for Diesel Pump- 0 2 Nos (All starter should be complete in all respect with TDR ,O/L, S/C and Phase sequence corrector relay etc complete in all respect and as specified ). (For Gear Pumps) (f) MPCB 6.3 - 10 A TP with thermal and magnetic release 415 volts 50 Hz with breaking cap of 100 KA with indicating lamp : On-Trip-Stop with suitable Ammeter along with necesary CTs etc- 03 Nos (for hot water Circulation Pumps). (g) ASD (Automatic Star Delta) Starter suitable upto 7.5 HP Motor with 4 Pole contactors ,OLR and electronic star delta timer in S.S enclosure with relay range of 5.5 to 8 Amps for AHUs -03 Nos(All starter should be complete in all respect with TDR ,O/L, S/C and Phase sequence corrector relay etc complete all as specified) for 3 Nos Hot water circulation pumps.

-

-

-

... More
Note: (i) Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections. (ii) Earthing all components, frame etc. to a common internal earth bar. (iii) Painting all sheet metal works support structure etc. (iv) All accessories & supporting structure (Hot Dip Galvanised). (v) All Load Managers to have parameters like KW, KWH, KVA, A, V, PF, KVAR, Active & Reactive component of power as specified in the schematic. (vi)The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm. (vii) The panel shall be prewired, ready for External Cable termination. (viii) All Gland Plate's shall be 3 mm thick removable type. (ix) All the CT's shall be cast resin type, with necessary CT shorting link. (x) The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations. (xi) The panel Incomers/Outgoings shall have Potential free Contact.

-

-

-

... More
(xii) 3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals. (xiii) All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings) (xiv) Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site. (xv) Complete Digital / Electronic interlocking should be provided in the panel for sequence operation of the system to ensure proper safety (xvi) Suitable sufficient arrangement of LEDs light and provision of blower fans should be provided in the panel.

-

-

-

... More
Supply, testing and commissioning of Indoor type free standing infront operated fully compartmentalized extendable on both sides indoor type weather & dust vermin proof L.T. Panel board suitable for 3 Phase 4 wire, 415 Volts, 50 Hz, AC supply system housed with incoming and outgoing feeders, bus bars, change over switches, interconnections etc , factory fabricated with indoor cubicle type totally enclosed .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminium bus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.. All MCCBs panel should be single Tier for easy cable termination.Cable termination space should be adequate to safely gland and terminate AL/CU cables for the given current ratings with Form B seperation for Incoming MCCB feeders and For Outgoing MCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of 100 mm ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry.

1

-

-

... More
1.Incoming:- (a) MCCB, Four pole, 160 Amps, Icu =16 KA at 415 volts with thermal magnetic release - 01 No with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and fixed magnetic setting and Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc. (b) Bus Bar TPN electrolytic Aluminium extensible type as main bus bars of minimum 300 A capacity (As per capacity of corresponding incoming / Bus couplers), and auxilliary bus bars of suitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 36kA . (c). Metering Section - Suitable rated Digital Ammeter in amps-01 No along with resin type CTs as per design ratio with necessary CT shorting link- 03 Nos , digital volt meter in Volts- 01 No , RYB indicating Lamps-03 Nos , Suitable Load mangaer to have a parameters like KW,KWH,KVA,A,V,PF,KVAR,Active and Reactive componentof the power - 1 No .

-

-

-

... More
2. OUTGOINGS (a) MPCB 14-20 A TP with thermal and magnetic release 415 volts 50 Hz with breaking cap of 100 KA with indicating lamp : On-Trip-Stop with suitable Ammeter along with necesary CTs etc- 03 Nos ( 2 Nos working 0+ S/By) for 2 Nos of AHU (b) ASD (Automatic Star Delta) Starter suitable upto 20 HP Motor with 4 Pole contactors ,OLR and electronic star delta timer in S.S enclosure with relay range of 5.5 to 8.8 Amps for Hot water Circulation Pump -02 Nos (All starter should be complete in all respect with TDR ,O/L, S/C and Phase sequence corrector relay etc completein all respect and specified ) (c) MPCB 11 - 20 A TP with thermal and magnetic release 415 volts 50 Hz with breaking cap of 100 KA with indicating lamp : On-Trip-Stop with suitable Ammeter along with necesary CTs etc- 02 Nos ( 01 W+01 S/By) for AHU of 5000 CFM - 02 No (d) DOL Starter complete with 4 Pole contractor along with OLR in S.S Enclosure suitable upto 7.5 HP Motor with relay range of 11.0 to 18.0 Amp for AHU- 0 1 Nos (All starter should be complete in all respect with TDR ,O/L, S/C and Phase sequence corrector relay etc complete in all respect and as specified ).

-

-

-

... More
Note: (i) Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections. (ii) Earthing all components, frame etc. to a common internal earth bar. (iii) Painting all sheet metal works support structure etc. (iv) All accessories & supporting structure (Hot Dip Galvanised). (v) All Load Managers to have parameters like KW, KWH, KVA, A, V, PF, KVAR, Active & Reactive component of power as specified in the schematic. (vi)The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm. (vii) The panel shall be prewired, ready for External Cable termination. (viii) All Gland Plate's shall be 3 mm thick removable type. (ix) All the CT's shall be cast resin type, with necessary CT shorting link. (x) The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations. (xi) The panel Incomers/Outgoings shall have Potential free Contact.

-

-

-

... More
(xii) 3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals. (xiii) All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings) (xiv) Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site. (xv) Complete Digital / Electronic interlocking should be provided in the panel for sequence operation of the system to ensure proper safety (xvi) Suitable sufficient arrangement of LEDs light and provision of blower fans should be provided in the panel.

-

-

-

... More
Supply, testing and commissioning of Indoor type free standing infront operated fully compartmentalized extendable on both sides Indoor weather & dust vermin proof L.T. Panel board suitable for 3 Phase 4 wire, 415 Volts, 50 Hz, AC supply system housed with incoming and outgoing feeders, bus bars, change over switches, interconnections etc , factory fabricated with indoor cubicle type totally enclosed .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminium bus bars as mandatory as conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suiatbale for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.. All MCCBs panel should be single Tier for easy cable termination.Cable termination space should be adequate to safely gland and terminate AL/CU cables for the given current ratings with Form B seperation for Incoming MCCB feeders and For Outgoing MCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of 100 MM ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry.

1

-

-

... More
1.Incoming:- (a) MCCB Four pole 125 Amps Icu =16 KA at 415 volts with thermal magnetic release - 01 No (I/G) .It should be with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and fixed magnetic setting Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc. (b) Bus Bar TPN electrolytic Aluminium extensible type as main bus bars of minimum 300 A capacity (As per capacity of corresponding incoming / Bus couplers), and auxilliary bus bars of suitable capacity with heat shrunk coloured sleeves and i/c SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 36kA . (c). Metering Section - Suitable rated Digital Ammeter in amps-01 No along with resin type CTs as per design ratio with necessary CT shorting link- 03 Nos , digital volt meter in Volts- 01 No , RYB indicating Lamps-03 Nos , Suitable Load mangaer to have a parameters like KW,KWH,KVA,A,V,PF,KVAR,Active and Reactive componentof the power - 1 No .

-

-

-

... More
2. OUTGOINGS (a) MPCB 14-20 A TP with thermal and magnetic release 415 volts 50 Hz with breaking cap of 100 KA with indicating lamp : On-Trip-Stop with suitable Ammeter along with necesary CTs etc- 03 Nos ( 2 Nos working 0+ S/By) for 2 Nos of AHU (b) ASD (Automatic Star Delta) Starter suitable upto 20 HP Motor with 4 Pole contactors ,OLR and electronic star delta timer in S.S enclosure with relay range of 5.5 to 8.8 Amps for Hot water Circulation Pump -02 Nos (All starter should be complete in all respect with TDR ,O/L, S/C and Phase sequence corrector relay etc completein all respect and specified ) Note: (i) Main Aluminum busbars with 0.8Amps/sqmm current density & all internal wiring with copper FRLS wires and connections. (ii) Earthing all components, frame etc. to a common internal earth bar. (iii) Painting all sheet metal works support structure etc. (iv) All accessories & supporting structure (Hot Dip Galvanised). (v) All Load Managers to have parameters like KW, KWH, KVA, A, V, PF, KVAR, Active & Reactive component of power as specified in the schematic. (vi)The panel shall be with Galvanized MS mounting base frame & the height shall not exceed more than 2100mm.

-

-

-

... More
(vii) The panel shall be prewired, ready for External Cable termination. (viii) All Gland Plate's shall be 3 mm thick removable type. (ix) All the CT's shall be cast resin type, with necessary CT shorting link. (x) The panel shall be in convenient sections suitable for transportation, erection & have sufficient space for Incoming & Outgoing cable terminations. (xi) The panel Incomers/Outgoings shall have Potential free Contact. (xii) 3 mm thick acrylic sheet shall be provided on the top of all outgoing termination sections, for protection against live terminals. (xiii) All the panel Incomers & Outgoings shall be tagged with aluminum anodized engraved name plates (Detailed tag of the feeders will be given during the final approval of panel drawings) (xiv) Vendor shall arrange to configure / check / set all the meters once the panel is completely installed & in operation at site. (xv) Complete Digital / Electronic interlocking should be provided in the panel for sequence operation of the system to ensure proper safety (xvi) Suitable sufficient arrangement of LEDs light and provision of blower fans should be provided in the panel.

-

-

-

... More
Power Cabling Supply, installation testing and commissioning of complete cable work using XLPE insulated PVC sheathed steel tape/ wire armoured underground aluminium/copper conductor cables of following sizes for electric supply from main panel in AC plant room to various loads including Supplying and making end termination with brass double compression glands and aluminium lugs including interconnections from starters to motors on existing cable trays/supports as required as per specifications.

-

-

-

... More
4 core x 25 Sqmm -copper armoured cable ( ISI marked)

300

-

-

... More
3 core x 10 Sqmm -copper armoured cable ( ISI marked)

100

-

-

... More
3 core x 4 Sqmm -copper armoured cable ( ISI marked)

50

-

-

... More
Control Cabling Supply, installation, testing and commissioning of complete cable work using PVC insulated PVC sheathed copper control cables of 6CX1.5 Sqmm sizes to various equipment including interconnections from electric supply to equipments on existing cable trays / supports as required including end termination on both sides as per specifications and as required.

1

-

-

... More
Cable Tray Fabrication and installation of following size of perforated GI cable tray, including horizontal and vertical bends reducers, tees, cross members & cable tray cover for protection of cable and other accessories as required and duly suspended from the ceiling with MS suspenders including painted etc.as required.

-

-

-

... More
300 mm wide x 1.6 mm thick

30

-

-

... More
150 mm wide x 1.6 mm thick

300

-

-

... More
Supply and fixing LED light fitting 1x120 Watt flameproof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three coreflexible copper conductor cable with suitable size

42

-

-

... More
Taking down carefully and shifting of voltage stabilizer complete in new elect panel room after carefully disconnecting the electric cables for re-use complete all as specified and as directed by Engr-in-Charge.

1

-

-

... More
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 32 x 6 mm GI earth strip by means of bolts, nuts, check nuts and washers of galvanized standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following: (a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm. (d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing

25

-

-

... More
Notes: (i) On testing after completion of earthing, if the desired earth resistance is not less than 5 ohm obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.The unit rate includes GI pipe up to 7.5m for protection of earth lead. (ii) If there is a requirement of grid Earthings to achieve the desired earth resistance, as directed by Eng-in-charge, then inter connecting of different earthings shall be done at no Extra cost

-

-

-

... More
Providing & fixing 25mmx4mm GI strip on surface or in recesses for earth connections etc complete as required.

300

-

-

... More
Providing & fixing 32mmx6mm GI strip on surface or in recesses for earth connections etc complete as required.

200

-

-

... More
Supply and fixing of MCCB incommer Distribution Board ( Vertical Load line DB) double Door made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating and IP 43 & IK 09 protection, surface mounting, VTPN 04 way, 240 volts with bus bar rating 200 Amps, dust and vermin proof suitable for incorporation of MCB’s and isolators etc and making all necessary connections complete all as directed.

5

-

-

... More
S&F MCCB Four pole 63 Amps Icu =16 KA at 415 volts with thermal magnetic release - 01 No (O/G) .It should be with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and Class II front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc

5

-

-

... More
Supply and fixing MCB TPN 32 Amp, 415V ,10KA, 'C' curve of 4 poles and current carrying capacity in the DB complete with connection testing and commissioning all as specified and as directed by Engineer-in-charge.

5

-

-

... More
Supply and fixing Miniature circuit breaker (MCB) SPN 32 Amp rating 240V, 10KA 'C' curve of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning all as specified and as directed by Engineer-in-charge.

20

-

-

... More
Supply and fixing Miniature circuit breaker (MCB) SP 240V, 10 KA 'C' curve of current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning all as specified and as directed by Engineer-in-charge.

20

-

-

... More
Supply & Fixing of Steel tubing light grade galvanised of size 80mm dia laid in trench or fixed to wall/pole for cable protection, complete all as specified & directed.

10

-

-

... More
Material and labour for point wiring in steel conduit unsheathed multistrand copper conductor cable of 1.5 sqmm single core FRLS for one light/fan point controlled by one flame proof switch including continuous earth continuity copper earth wire of same size connected to common earth dolly complete all as specified and directed by Engr-in-charge. Note : (a) wiring shall be done by using proper colour coding.

40

-

-

... More
All as per item No 2.35 here-in-above but using 2.5 sqmm wire for 15 Amps flame proof socket

10

-

-

... More
S&F Switch flame proof rotary type with termination box in LM6, 16 Amps, single pole 250 volts.

10

-

-

... More
M&L Sub-main wiring with two single core 2.5 Sqmm (nominal area) PVC insulated copper conductor FRLS, multi-stranded, unsheathed 1100 volts grade in steel conduit including 2.5 Sqmm copper conductor cable FRLS as earth wire, complete all as specified. NOTE : 3-Run of 2.5 Sq mm copper conductor cable & 01 Run of steel conduit with necessary accessories shall be measured as One Unit.

1000

-

-

... More
All as per item ser No 2.38 here in above but using PVC casing & caping

350

-

-

... More
All as per item ser No 2.38 here in above but using 04 Sqmm wire.

500

-

-

... More
All as per item ser No 2.38 here in above but using 04 Sqmm wire and PVC casing & caping.

200

-

-

... More
Supply,laying,jointing and testing, fixing to wall using clamps/pole/floor or in air or passing through pipes /ducts / road/path/drain, laid in trenches, 1100 volts grade heavy duty electric cable XLPE insulated,screened ,PVC bedded, galvanised steel wire or wire armoured with electric power cable 1100 volts grade with stranded aluminium conductor of size 3.5 core 150 sqmm ISI marked ( IS - 7098 Part-1) and its latest amendments complete all as specified and as directed by Engr-in-Charge.

200

-

-

... More
Supply,laying,jointing and testing, fixing to wall using clamps/pole/floor or in air or passing through pipes /ducts / road/path/drain, laid in trenches, 1100 volts grade heavy duty electric cable XLPE insulated,screened ,PVC bedded, galvanised steel wire or wire armoured with electric power cable 1100 volts grade with stranded aluminium conductor of size 3.5 core 95 sqmm ISI marked ( IS - 7098 Part-1) and its latest amendments complete all as specified and as directed by Engr-in-Charge.

100

-

-

... More
Excavation in trenches in hard/dense soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of cables and getting out of excavated material complete all as specified and directed by Engineer-in-Charge.

54

-

-

... More
Material and labour for sand cushioning below and around cable in trenches with rever sand all as specified .

16.2

-

-

... More
M&L for un-reinforced precast concrete cable cover, class LV, type 1, flat of size 250 x 150 x 40 mm for cable protection complete all as specified and as directed by EIC

1111

-

-

... More
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed by Engineer-in-Charge.

31.86

-

-

... More
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed by Engineer-in-Charge.

22.14

-

-

... More
Supply ,Installation,testing and commissioning of the following accessories for remote operation of leaves of existing hanger motorised door from both ends inculding control system,wire/cable motors,gear mechanism,safety arrangement for motoriszed operation etc.The arrangement shall include the following accessories apart from other accessories required for smooth and efficient operation of the hanger doors. (i) 3 Phase squirrel cage induction motor ,1450 rpm,50 HZ of power 3 HP(min)-01No. (ii) Gear box to ensure door movement of speed 8 to 10 mpm as part of drive transmission between motor and drive wheel-01 Job. (iii) Control Panel to be mounted at the extreme end of the door opening inside the hanger building to ensure electric operation of master leaf of the hanger door. Note: (a) The operator shall keep the open or close by pressing push button to provide the arrangement to automatically open/close the door through the the control power cut on/ off throuh limit switches. (b) An emergency STOP button (STAY-PUT-TYPE) shall also be provided on the control panel.

4

-

-

... More
(c) The door control panel shall be provided with a flashing light with annuciation during closing/opening of the door. (d) In case of power failure the doors to be operated manually by disengaging in the gear box. (e) All necessary arrangements for movement of the door including gear box, cable for electric supply to motor, travelling copper cable ( 4 Sqmm x 4Core) including provision of hanging arrangement and control panel incl control wiring and any other arrangement/ accessories required for functioning of motorized sliding doors and as directed above to be deemed to be included in the quoted rates. (f) The contractor is advised to visit the site and see the arrangment of hanger door leaves so that proper design of motorized operated door system can be done at their end. (g) The lumpsum quoted rate is deemed to include all arrangement /equipments for satisafctorily operations including safety arrangenment and shall include three years maintenance for satisfactory operations. (h) The lumpsum quoated rate is deemed to include taking down of the old motor, gear box, control pannel etc and all other accessories and shifting to the store yard of MES for the safe custody all as directed by engineer in charge.

-

-

-

... More
Suppy & Fixing of Fire Alarm Sounders / Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of + 5 DB, 1000 m range complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
Suppy & Fixing of Fire Detectors/ sensor Complying with and type certified to EN - 45 Addressable type multisensor detector with heat and smoke combination with base with self built intelligence as per IS: 11360 complete all as specified and directed by Engineer-in-Charge.

10

-

-

... More
Suppy & Fixing of annunciating device, Addressable manual call point resettable type complete all as specified and directed by Engineer-in-Charge.

2

-

-

... More
S&F Switch flame proof rotary type with termination box in LM6, 06 Amps, single pole 250 volts.

40

-

-

... More
Total amount of schedule A part-III schedule of credit of RS 566041.00 for retrived material on srl page no 28 of tender document in PDF format which will be deducted offline during acceptance of tender.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.