Military Engineer Services Tender
Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date18 Sep 2024
Closing Date12 Oct 2024
Tender Amount₹ 46,50,000
Costs
EMD
₹ 93,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_661352_2Bid Award Id
ViewTender No
8521/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Material and labour for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm thick after laying, stretching and testing the cable complete all as specified and as directed. NOTE :- Punned thickness shall be measurement and paid.
97
-
-
Material and labour for un-reinforced precast concrete cable cover LV type I, flat size 250 mm x 150 mm x 40 mm as protection to underground cable laid dry and flat adjoining each other complete all as specified and as directed.
8000
-
-
Supply, laying, jointing and testing XLPE insulated, armoured heavy duty under ground electric cable with stranded aluminium conductor 1100 voltage grade including taking out/down old existing unserviceable cable all as directed of following sizes. NOTE : Excavation, sand cushioning and bricks shall be measured and paid separately under respective items of BOQ.
-
-
-
Cable of size 6 sq.mm 2 core
50
-
-
Cable of size 10 sq.mm 2 core
50
-
-
Cable of size 16 sq.mm 4 core
50
-
-
Cable of size 25 sq.mm 4 core
50
-
-
Cable of size 50 sq.mm 3.5 core
150
-
-
Cable of size 70 sq.mm 3.5 core
250
-
-
Cable of size 95 sq.mm 3.5 core
250
-
-
Cable of size 120 sq.mm 3.5 core
400
-
-
Cable of size 185 sq.mm 3.5 core
100
-
-
Cable of size 240 sq.mm 3.5 core
100
-
-
Material and labour for XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts earthed, grade cross sectional area 185 sq.mm 3 core complete all as specified and as directed.
100
-
-
Supply, laying, jointing and testing cable XLPE insulated screened PVC bedded galvanized steel strip or wire armored, electric power cables (heavy duty) 11000 volts grade with stranded aluminum conductor of cross sectional area 3 core 95 sq.mm including taking out / down old existing unserviceable cable complete all as specified and as directed.
100
-
-
Material and labour for galvanised steel tube light grade ISI marked for protection of LT UG cable laid in trench / under road / drain and floor including FI clamps, nuts, bolts, washers etc all as required at site fixed in repairs complete all as specified and s directed.
-
-
-
40 mm bore
25
-
-
50 mm bore
25
-
-
80 mm bore
25
-
-
Material and labour for straight through jointing kit heat shrinkable type suitable for XLPE cable size 70 to 150 sq.mm 3.5 core fixed in repairs complete all as specified and as directed.
1
-
-
Material and labour for straight through jointing kit heat shrinkable type suitable for XLPE cable size 185 sq.mm 3.5 core fixed in repair complete all as specified and as directed.
1
-
-
Supply and fix in replacement of unserviceable MCCB 800 Amp 4 pole 50 KA 415 volts, thermal magnetic release and adjustable overload setting, electronic / micro-processor type complete all as specified and as directed.
1
-
-
Supply and fix in replacement of unserviceable MCCB 400 Amps, 4 pole, 36 KA, 415 volts, thermal magnetic release and adjustable overload setting, electronic / micro-processor type complete all as specified and as directed.
2
-
-
Supply and fix in replacement of unserviceable MCCB 250 Amps, 4 pole, 36 KA, 415 volts, thermal magnetic release and adjustable overload setting, electronic / micro-processor type complete all as specified and as directed.
2
-
-
Supply and fix in replacement of unserviceable MCCB 160 Amps, 4 pole, 25 KA, 415 volts, thermal magnetic release and adjustable overload setting, electronic / micro-processor type complete all as specified and as directed.
2
-
-
Supply and fix in replacement of unserviceable MCCB 125 Amps, 4 pole, 16 KA, 415 volts, thermal magnetic release and adjustable overload setting complete all as specified and as directed. MAKE :- C&S Cat No.CSC4N4150 / Legrand Cat No. 420016 or techno commercially equivalent models specified in PS
4
-
-
Supply and fix in replacement of unserviceable MCCB 100 Amps, 4 pole, 16 KA, 415 volts, thermal magnetic release and adjustable overload setting complete all as specified and as directed. MAKE :- C&S Cat No.CSC2N4100 / Legrand Cat No. 420015 or techno commercially equivalent models specified in PS
4
-
-
Material and labour for graded coarse granite aggregate of 40mm grade nominal size without any vegetation or chemical including levelling / spreading surrounding transformer, HT / LT 2 / 4 pole structure and LT / HT panel complete all as specified and as directed.
10
-
-
Supply and fixing MS galvanised chain link fencing, of size 4mm dia and mesh size 150mm x 100mm to any type of standards, rails, straining bolts etc including provision of binding wire for making fencing around the transformer / MES installation including taking down / dismantling old chain link fencing / wire mesh complete all as specified and as directed.
30
-
-
Material and labour for bus bar chamber, pedestal type of size 75cm x 60cm x 40cm outdoor type, dust and vermin proof, front opening made out of 3.15mm thick MS sheet duly painted and consisting with aluminium bus bar 3 phase and neutral 4 Nos 400 Amps fixed on insulators and one MCCB FP 200 Amps, 25 KA rupturing capacity including necessary foundation fixed in PCC (1:3:6) using 20mm graded stone aggregate including danger plate etc complete all as specified and as directed.
1
-
-
Supply and fix in replacement of unserviceable on load change over switch with enclosure 400 Amps, 4 pole, 415 volts, complete all as specified and as directed.
1
-
-
Material and labour for painting of LT panel outdoor / indoor of any sizes removing existing old paint with the help of sand / emery paper etc., preparing surfaces externally including cleaning etc., applying externally one coat of synthetic enamel paint of approved tint including cleaning and surface dressing upto 25cm depth around 1 mtr of the panels complete all as specified and as directed.
5
-
-
Supply and fix in replacement of aluminium lugs of size 50 sq.mm complete all as specified and as directed.
8
-
-
Supply and fix in replacement of aluminium lugs of size 70 sq.mm complete all as specified and as directed.
8
-
-
Supply and fix in replacement of aluminium lugs of size 95 sq.mm complete all as specified and as directed.
10
-
-
Supply and fix in replacement of aluminium lugs of size 120 sq.mm complete all as specified and as directed.
10
-
-
Supply and fix in replacement of aluminium lugs of size 150 sq.mm complete all as specified and as directed.
10
-
-
Supply and fix in replacement of aluminium lugs of size 185 sq.mm complete all as specified and as directed.
10
-
-
Supply and fix in replacement of aluminium lugs of size 240 sq.mm complete all as specified and as directed.
10
-
-
Material and labour for strengthening and restringing of LT over head ACSR conductor any size in overhead lines including removing and replacement of binding wire from insulators before stringing and rebinding of insulators after stringing complete all as specified and as directed by Engineer-in-Charge.
NOTE : (i) If any insulator required then measured and paid separately.
(ii) If ACSR conductor required then paid separately.
(iii) Four / two wire measures as a each job.
5
-
-
Dismantling of insulators of any size / rating from pole all as directed and specified by Engineer-in-Charge.
20
-
-
Material and labour for pin type porcelain vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washer and one galvanized iron nut, 100mm height, 65mm dia suitable for working pressure 1100 volts including nut bolt complete all as specified and as directed by Engineer-in-Charge.
15
-
-
Material and labour for shackle type porcelain, vitreous, white brown or green insulators 100 mm height 115mm dia including galvanised mild steel straps, washers, insulators bolts, etc suitable for working pressure 1100 volts including nut, bolts complete all as specified and as directed by Engineer-in-Charge.
5
-
-
Dismantling of old jumper, including supply and fixing new jumper connection at out point on LT over head line with suitable size of ASCR conductor 6 / 1 x 2.56mm (weasel) PG Clamps, alkathine sleaves complete of required length not exceeding 2 mtr including testing on completion complete all as specified and as directed by Engineer-in-Charge.
10
-
-
Dismantling of ACSR conductor service feeder 'or' distributor span, jumpers complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Material and labour for LT ACSR conductor drawn of on existing steel tubular pole, including binding wire, jumpers with alkathine pipe, PG clamps etc complete all as specified and as directed. by Engineer-in-Charge.
1
-
-
Material and labour in replacement of existing unserviceable danger notice board with pressed vitreous painted plate fabricated out of 1.6mm thick mild steel sheet vitreous enameled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamp bolts and nuts of approved size LT 20 x 15 cm size complete all as specified and as directed.
10
-
-
Material and labour for earthing complete with 600 x 600 x 6mm thick GI plate electrode buried in ground vertically not less than 2.25mtrs deep below ground level with top edge of the plate not less than 1.5mtrs below ground level with GI strip of size 32mm x 6mm as earthing lead including necessary excavation and earth work (in any of strata) providing charcoal dust, salt mixed with fine sand in continuous layers, PCC (1:3:6 ) type C1 in chamber, precast 50mm thick in cement (1: 2:4) type B.1 with CI frame with cover, 20mm dia bore light grade GI watering pipe funnel etc fixing of GI Pipe 40mm bore protection for earthing strip from earth pit to test point complete and making connection all as specified in electrical plate No 3 and as directed by Engineer-in-Charge.
1
-
-
Material and labour for earthing complete with 600 x 600 x 3.15 mm thick copper plate electrode buried in ground vertically not less than 2.25mtrs deep below ground level with top edge of the plate not less than 1.5mtrs below ground level with copper strip of size 20mm x 3mm as earthing lead including necessary excavation and earth work (in any of strata) providing charcoal dust, salt mixed with fine sand in continuous layers, PCC (1:3:6 ) type C1 in chamber, precast 50mm thick in cement ( 1: 2:4) type B.1 with CI frame with cover, 20mm dia bore light grade GI watering pipe funnel etc fixing of GI pipe 40mm bore protection for earthing strip from earth pit to test point complete and making connection all as specified in Electrical plate No 3 and as directed by Engineer-in-Charge.
1
-
-
Supply and fix earth continuity conductor or main earthing lead of 20mm x 3mm copper strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required fixed in repair complete all as specified and as directed.
40
-
-
Supply and fix earth continuity conductor or main earthing lead GI strip 32mm x 6mm, laid in pipe / fixed on walls or any other position including jointing by tinned GI nuts, bolts and washers as required complete including taking out existing earth wire complete all as specified and as directed.
50
-
-
Material and labour for taking out bottom trolley of HT OCB 11 KV 400 / 800 amps capacity after disconnecting power supply for carrying out servicing and maintenance of operating mechanism, latch assembly, spring mechanism. checking of electrical control wiring of OCB and checking for proper functioning of shunt trip coil, lubricating of all moving parts and checking / cleaning of alignment of moving contacts with fixed contact assembly for proper functioning of operation. Re-assembling of bottom trolley of HT OCB fixed in its original position and testing commissioning for smooth functioning complete all as specified and as directed.
10
-
-
Material and labour for taking out the defects parts from HT OCB while servicing and then supply and replace the following new spare suitable for HT 11KV OCB indoor type Make : ECE / GEC of capacity 400 Amps 3 phase 50Hz all as directed by Engineer-in-Charge
-
-
-
Tripping coil
1
-
-
Moving contact plug
1
-
-
Locking assembly
1
-
-
Closing coil
1
-
-
NO Volt coil 110V DC
1
-
-
PT bushing (without fuses)
1
-
-
PT fuses (11KV/8Amps HT 5 x UTF 11) with stem
1
-
-
PT insulators
1
-
-
Spring catch assembly
1
-
-
Trip push button assembly complete
1
-
-
Catch lever guide
1
-
-
Sleeves for spout bushing
1
-
-
Switch bushing epoxy
1
-
-
Contact copper rod complete 400Amps
1
-
-
Material and labour for maintenance, servicing and repair of Vacuum Circuit Breakers (VCB) / SF6 Breakers HT 11 KV upto 800 Amps 50 cycle breaking capacity 13.5 KA of any make by opening and checking the internal moving and fixed parts, contacts / wiring, cleaning, dusting, decarbonising, tightening loosened parts checking of closing / tripping system, lubricating / greasing all moving parts including replacing worn out parts copper studs, bolts nuts and washers, replacing control wires, vacuum cylinder, bus bar contacts, fixed / moving, HT bush, gasket, bus chamber and when required complete all as specified and as directed.
NOTE :- The items to be replaced shall be measured and paid separately. However minor items such as indicator, push button, selector switch, gasket, wiring cable shall be deemed to be included in the unit rate.
5
-
-
Supply and fix in replacement of old unserviceable PT with new potential transformer OIL Cooled with protective enclosure of ratio 11 KV / 110 V / RT3 / 110V / RT3 Class 1.0 / 3P, Burden 100 VA / 50 VA Voltage Factor 1.2 continuous / 1.5 for 30 seconds. ILV 12/28/75 KVP. Ins class B Ref Std IS : 3156/1992 One end earthed type with one No HRC fuse on HV side.
NOTE :-
Primary Neutral to be solidly earthed including removing of old unserviceable PTs.
1
-
-
Supply and fix in replacement of old unserviceable CT with new CT 11 KV, consisting of CT ratio 100-50 A / 5-5 A for outgoing feeder control relay panel for protection complete all as specified and as directed.
MAKE :- KALPA / INSTRANS / PARAS
1
-
-
Supply and fix in replacement of Master Tripping Relay rating of 24 / 30 / 110 V dc for the existing HT VCB / OCB / RMU 11 KV Panels complete all as specified and as directed.
MAKE :- EASUN REYROLLE / C&S
1
-
-
Supply and fix closing coil / tripping coil for 11 KV 400 Amp VCB 30 / 110 V DC including taking out old unserviceable coil complete all as specified and as directed.
2
-
-
Material and labour for filtration / dehydration of transformer oil through filtration plant to improve the dielectric strength / insulation value of transformer oil upto 50 KV at 2.5mm gap for various capacity of 11 KV / 433 volts step down transformer and HT OCB installed in various location complete all as specified and as directed.
NOTE :- (a) The contractor will take shut down orders in working before commencement of the work from Engineer-in-Charge. (b) The contractor shall ensure no wastage of existing transformer oil. (c) The contractor solely responsible for any damages to the transformer / HT OCB during the process of oil filtration. He is responsible for making good any damage to the transformer / HT OCB at his own cost without any extra cost to the department. (d) The contractor shall ensure that the conservator tank are full to its level before starting the dehydration.
3000
-
-
Supply and filling of new transformer oil confirming to IS 335-1963 as amended and die electric strength not less than 60 KV for topping up / replacement of unserviceable transformer oil complete all as specified and as directed.
MAKE :- Electrol / Castrol
200
-
-
Supply and fix HT spout bushing for VCB HT 11 KV, set of three current transformer / busbar side including taking out old unserviceable bushing complete all as specified and as directed.
3
-
-
Supply, fixing, testing and commissioning of Vaccum Interrupter Bottle for the existing HT 11 KV VCB including taking out old unserviceable Vaccum Interrupter Bottle complete all as specified and as directed.
3
-
-
Supply and fix Push Buttons (Black) for the existing HT VCB / OCB / RMU 11 KV panels for including taking out old unserviceable Push Buttons complete all as specified and as directed.
20
-
-
Supply and fix RED, YELLOW, GREEN, BLUE, AMBER and WHITE LED Indication Lamps Range (24 - 240 V AC/DC) for the existing HT VCB / OCB / RMU 11 KV panels for including taking out old unserviceable lamps complete all as specified and as directed.
10
-
-
Supply and fix Trip-Neutral-Close (TNC) Switch, fixing with the existing HT VCB/OCB 11 KV panel for including taking out old unserviceable TNC Switch complete all as specified and as directed.
1
-
-
Supply and fix of Multi Data Meter, measuring Voltage, Current, PF, HZ, KWH, KVAH, KVARH for out going various feeders to different Labs including complete wiring, testing complete all as specified and as directed.
3
-
-
Material and labour for replacement of Digital volt meter 11 KV 3 phase range of accuracy 0.5 complete all as specified and as directed.
1
-
-
Material and labour for replacement of Digital Ampere meter 11 KV 3 phase range of accuracy 0.5 complete all as specified and as directed.
1
-
-
Supply and fix DC power pack 230 V AC Input and output 110 / 30 V DC for energizing tripping and closing coil installed in VCB/OCB complete testing including taking down old unserviceable DC power pack complete all as specified and as directed.
5
-
-
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sq.mm complete all as specified and as directed.
3
-
-
Supply, installation, connecting electrically and commissioning switch air break, gang operated, triple pole mounted on insulators 15 Nos and steel frame with operating mechanism in worked from ground level, drop out fuse, for current rating 400 Amps and working voltage 11000 volts including taking down old unserviceable switch air break, gang operated complete all as specified and as directed.
2
-
-
Material and labour required for locating fault in U/G HT/LT cable by using fault detector machine including transportation and by carring out high voltage test all as directed by Engr-in-charge
3
-
-
Material and labour for servicing of four pole, structure complete including replacement of unserviceable jumper, sleeve vice type connector GI Clamps 'T' connector run connector run through clamps, bolts nuts washer connecting lugs / thimbles knife, contacts applying petroleum jelly to the moving as well fixed contacts, tightening all the connection for its smooth functioning and preparing old painted surface of the structure such as poles, cross arms, bracing and supports clamps back plate complete painting of one coats of anti corrosive aluminium paint complete all as specified and directed. Marking the pole No/feeder name with black enamel paint complete all as specified and as directed. NOTE : No Extra payment will be made for the spares required to keep the four pole structure in satisfactory functioning state throughout contract period other then given in schedules
1
-
-
Material and labour for preventive maintenance / repairs to transformer step down 11 KV / 0.433 KV of any type 250 to 1000 KVA of any make including cleaning the transformers externally thoroughly with lint free cloth, tightening the HT / LT terminal nuts, opening the top cover and replacing the perished gasket of top cover, replacing sight glass, replacing silica gel, replacing the worn out copper alloy nuts and tighting the earth terminals complete all as specified and as directed.
7
-
-
Supply only rubber hand gloves suitable for 11 KV complete all as specified and as directed.
2
-
-
Material and labour for repair / replacement of mild steel work for MS cable tray HV / LV type fixed on wall / bridge type with necessary support as per site requirement and duly painted with two coats of synthetic enamel paint over a coat of red oxide at E-type and CASDIC sub stations complete all as specified and as directed by Engineer-in-Charge
50
-
-
Material and labour for repair to foundations of transformers / RMUs using PCC 1:2:4 type B1 (using 20mm graded crushed stone aggregate) complete all as specified and as directed.
1
-
-
Supply and fixing silica jel breather with new silica gel suitable for distribution transformer up to capacity 2000 KVA including taking out unserviceable complete all as specified and as directed.
2
-
-
Supply and fix inlet and outlet brass gate valve 32mm / 40mm heavy duty complete all as specified and as directed.
2
-
-
Disconnecting the transformer HT / LT cables earthing leads / strips complete 11 / 0.433 KV any type and capacity lifting transporting the same upto work shop for repair and dismantling (both side) the complete transformer accessories for repair/replacement to make the transformer serviceable including testing of transformer on load at site after repair complete all as specified and as directed.
NOTE: (i) Spares / accessories measured and paid separately under relevant items including refixing the transformer on platform and commissioning of transformer at site as directed.
(ii) The transformer shall be repaired in authorized workshop of manufacturer and original bill of the same will be submitted by the contractor as proof.
1
-
-
Material and labour for winding of transformer with supper enameled copper wire of existing gauge of retrieved winding for transformer HV side suitable for 11 / 0.433 KV step down distribution type any capacity complete all as specified and as directed.
500
-
-
Material and labour for winding of transformer with supper enameled copper wire of existing gauge of retrieved winding for transformer LV side suitable for 11 / 0.433 KV step down distribution type any capacity complete all as specified and as directed.
300
-
-
Material and labour for taking out trolley of LT ACBs up to 3200 Amps capacity after disconnecting power supply for carrying out servicing and maintenance of operating mechanism, latch assembly, spring mechanism, checking of electrical control wiring of ACB and checking for proper functioning of trip coil, lubricating of all moving parts and checking / cleaning of alignment of moving contacts with fixed contact assembly for proper functioning of operation. Re- assembling of bottom trolley fixed in its original position and testing commissioning for smooth functioning complete all as specified and as directed.
20
-
-
Supply and fix in repairs fixed arching contacts 3 pole suitable for the existing ACBs upto 3200 Amps capacity complete all as specified and as directed.
2
-
-
Supply and fix in repairs moving arching contacts 3 pole suitable for the existing ACBs upto 3200 Amps capacity complete all as specified and as directed.
2
-
-
Supply and fix in repair Arc chute set of three suitable for the existing ACBs upto 3200 Amps capacity complete all as specified and as directed.
2
-
-
Supply and fix in repairs shunt trip coil suitable for ACBs upto 3200 Amps capacity complete all as specified and as directed.
2
-
-
Material and labour for cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sq.mm complete all as specified and as directed.
3
-
-
Material and labour for cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sq.mm complete all as specified and as directed.
3
-
-
Material and labour for cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sq.mm complete all as specified and as directed.
3
-
-
Material and labour for cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sq.mm complete all as specified and as directed.
3
-
-
Material and labour for replacement of existing unserviceable steel tubular swaged pole 11 mtr long with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55, including painting with anti corrosive paint internally complete and externally complete with two coats of synthetic enamel aluminium paint over a coat of red oxide primer and preparation of surface including marking of pole Nos with black paint complete all as specified and as directed.
4
-
-
Dismantling of old unserviceable lightening arrester, supply and fix new lightening arrester non liner type confirming to IS No 3070 part I complete with all fittings, transmission class discharge capacity 65 KA suitable for 11 KV including making connections with over head line with ACSR conductor on poles complete all as specified and as directed.
1
-
-
Material and labour for replacement of existing unserviceable cross arms, bracings, supports, clamps and back plates fabricated from rolled mild steel sections including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and as directed.
1
-
-
Material and labour for replacement of existing unserviceable disc type insulator porcelain vitreous 145 mm height and 225 mm dia ball and socket type white, brown or green with tension clamp for conductor working pressure 11000 volts grade complete all as specified and as directed.
3
-
-
Material and labour for replacement of existing unserviceable pin type insulator porcelain vitreous white, brown or green insulator including one galvanised spindle, two galvanized washers and one galvanized nut 150mm height and 150mm dia for working pressure 11000 volts grade complete all as specified and as directed.
3
-
-
Material and labour for Plain Cement Concrete, (1:4:8), type D2 using 40mm graded stone aggregate for foundation filling of poles as mass concrete complete all as specified and as directed.
2
-
-
Material and labour for Plain Cement Concrete, (1:2:4), type B-1, using 20mm graded crushed stone aggregate as in coping of poles / stays etc complete all as specified and as directed.
1
-
-
Material and labour for cutting, removing the vegetation growth and surface dressing all around the installation yard / transformer / LT panel board areas external only to keep always installation clean and tidy complete all as directed.
NOTE :-
All the installation yards / area shall be kept clean through out contract period by repeatedly removing the grass / shrubs as many times as required depending on the growth of grass, measurement will be measured and paid only once throughout the contract period.
3000
-
-
Material and labour for cutting / trimming tree branches along the over head HT / LT lines up to 3.0 mtr from electric line on both sides of the span and disposing of the cut tree / branches at places complete all as specified and as directed.
100
-
-
Laying only, jointing and testing XLPE insulated, armoured heavy duty under ground electric cable with stranded aluminium conductor 1100 voltage grade including taking out/down old existing unserviceable cable of sizes 16 sq.mm to 240 sq.mm complete all as specified and as directed. NOTE :-
(i) Excavation, sand cushioning and bricks shall be measured and paid separately under respective items of BOQ.
(ii) Cable will be issued under Schedule 'B' free for laying only.
250
-
-