GAIL India Limited Tender
Search for the latest Gujarat tenders online related to civil works, road & transport, pipelines and more easily here on BidAssist. Here you can get any and every tender that is posted on the eProcurement Gujarat website, minus the clutter. No need for a tender ID, as on BidAssist, you can view any Gujarat tender by merely typing Gujarat in the search box.
Costs
EMD
₹ 1,00,500Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Supply, Installation, Testing And Commissioning Of Surge And Lighting Protection System
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_GAIL_203616_1Bid Award Id
ViewTender No
GAIL/CNP/JPR23SD249/2023-24Tender Authority
GAIL India Limited ViewPurchaser Address
-Website
http://etenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Supply & installation of single spike air terminals of 10/16 mm dia. & 1500 mm length as required and as per site conditions. The air terminal shall be manufactured with aluminium & shall be as per IEC 62561-2. The air terminal shall be fixed on metal shed stand mounted on clamps. For further connection with round conductor provision of connecting clamp shall be given.
1
-
-
Supply & installation of Angled Air Terminal of 10 mm dia. 500 mm above solar PV module. An Air Terminal Rod shall be manufactured with Aluminium material for solar protection, complying IS/IEC 62305 & IEC 62561-2. An Air terminal shall be provided with the two saddle clamp suitable for mounting on MMS as per site conditions and to withstand high wind loads.
9
-
-
Supply & installation of 8 mm dia aluminium round conductor for air termination network. It shall meet the requirement of IEC 62561-2.
1285
-
-
Supply & installation of 8 mm dia aluminium round conductor for mesh. It shall meet the requirement of IEC 62561-2.
263
-
-
Supply & installation of Parapet Conductor holder mounted on plastic base for holding of 8 mm dia. round conductor (for RCC). The conductor holder should be installed at every 1 mtr & as per IEC 62561-4.
887
-
-
Supply & installation of Mesh Conductor holder along with concrete block for holding of 8 mm dia. round conductor (for RCC). The conductor holder should be installed at every 1 mtr & as per IEC 62561-4.
208
-
-
Supply & installation of Adhesive-type Conductor holder for metal roof. The conductor holder should be installed at every 1 mtr & as per IEC 62561-4.
453
-
-
Supply & installation of 16sq.mm. copper cable along with lugs, having 500mm length & as per IEC 62561-1 so as to connect air termination rod with any metallic structure on the roof
28
-
-
Supply & installation of Straight and T - Connector for making Straight/Tee joint of 8 mm aluminium Conductor to 8 mm dia aluminium conductor on parapet wall, roof and vertical facade of mesonary / glass / metalic work & as per IEC 62561-1
145
-
-
Supply & installation of X - Connector for making Cross joint of 8 mm aluminium Conductor to 8 mm dia aluminium conductor on parapet wall, roof and vertical facade of mesonery / glass / metalic work & as per IEC 62561-1
27
-
-
Supply & installation of 8 mm dia aluminium round conductor as down conductor. It shall meet the requirement of IEC 62561-2.
383
-
-
Supply & installation of Down Conductor holder mounted on plastic base for holding of 8 mm dia. round conductor (for RCC). The conductor holder should be installed at every 1 mtr & as per IEC 62561-4.
338
-
-
Supply & installation of adhesive type conductor holder for metallic platform, to be installed at every 1 mtr and shall be as per IEC 62561-4.
45
-
-
Supply & installation of Test Clamp to disconnect the down conductor from the earth termination network for regular checks of the earth termination resistance value & shall be as per IEC 62561-2. (with enclosure)
46
-
-
Supply & installation of Expansion piece made of 8mm dia. Aluminium & as per IEC 62561-2 along with suitable connecting accessory. It shall be installed at every 20 mtr to maintain the flexibility to the conductor due to heat.
79
-
-
Supply & installation of Lightening Strike Counter for counting the number of lightning strikes without any power supply. The Lightning Counter should be IP65 rated metallic enclosure suitablefor external application & shall be as per IEC 62561-6
19
-
-
Supply & installation of Earthing termination made of copper-bonded rod of 10 feet length,14.2 mm dia. (Minimum copper bonding shall be 0.25mm) with exothermically welded busbar, Earth enhancement material (quantity ≥35KG, especially designed for rocky terrain), Pit Cover and other accessories as required and as per specification and other applicable codes.
47
-
-
Supply & installation of min. 8 mm Copper Bonded Steel Conductor as per IEC 62561-2 along with fixtures, laid at 600mm below the ground for interconnection of the earthing, as required and as per specification and code of practice.
1936
-
-
Supply & installation of Class B/Type I Three Phase Surge Protection Devices as per IEC 62305-4 and tested according to IEC 61643 – 11, DIN Rail mountable with Maximum Continuous Operating Voltage of 320 V and Voltage Protection Level of 2.5 kV (L-N). Response Time should be less than 100 ns (L-N & N-PE). The maximum impulse test current should be 50 kA (10/350 µs) per pole and 100 kA (10/350 µs) neutral to protective earth. The surge protection devices shall be enclosed in polycarbonate enclosure of IP 65 rating.
15
-
-
Supply & installation of Class C/Type II Three Phase Surge Protection Devices as per IEC 62305-4 and tested according to IEC 61643 – 11, DIN Rail mountable with Maximum Continuous Operating Voltage of 320 V and Voltage Protection Level of 1.5 kV (L-N). Response Time should be less than 25 ns (L-N & N-PE). The nominal current should be 20 kA (8/20 µs) per pole and maximum current shold be 40 kA (8/20 µs). The surge protection devices shall be enclosed in polycarbonate enclosure of IP 65 rating.
1
-
-
Supply & installation of 48V AC/DC Surge Protection Device
2
-
-
Supply & installation of 24V AC/DC Surge Protection Device.
2
-
-
Supply & installation of 110V AC/DC Surge Protection Device.
1
-
-
Supply & installation of Surge arrester at main power supply (3ɸ, 440VAC) board in the control room
12
-
-
Supply & installation of Surge arrester at the output to AC/DC converter and DC/DC converters
36
-
-
Supply & installation of Surge arrester at 24Vdc input to HPU at field junction box
12
-
-
Supply & installation of Surge arrester for Pressure transmitter and RTD’s
48
-
-
Supply & installation of Surge arrester at RTU end across TIC in the control room
60
-
-