Military Engineer Services Tender
View complete overview of Goa MES Tender
Costs
EMD
₹ 1,03,500Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_668054_3Tender No
85675/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Total amount of Sch 'A' Part-IV (EXTERNAL SERVICES) brought forward from Serial Page No.33
1
-
-
Total amount of Sch 'A' Part-V (DEMOLITION/DISMANTLING) brought forward from Serial Page No 34
1
-
-
Sch 'A' Part- VI - MISCELLANEOUS ITEMS (Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.)
-
-
-
BUILDINGS & STRUCTURES
-
-
-
Preparation of new steel surfaces and applying two coats of epoxy anti corrossive paint over a coat of zinc primer all as directed and as specified.
60
-
-
EXTERNAL SERVICES
-
-
-
Design supply, install, testing & commissioning passenger MRL (Machine room less) lift electrically operated Microprocessor controlled (6 Person) 408 Kg , speed 1 metre/sec, including with single speed motor 415 volts, 3 phase, AC 50 Hz supply conforming to IS-14665, suitable to serve upto 4 floors (G+3 floors) upper floors with AC Variable Voltage & Variable Frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set complete all as specified.
1
-
-
(a ) Capacity (kgs) :- 408 Kg, 06 persons
(b) Speed (mps) :- 1 mps ( c) Rise (m) :- 15 m (d) Stops :- 4 Stops (all opning on the same side) (e) Controller Type :-ACD5-MRL
(f) Drive :- VF Regenerative (Closed Loop) (g) Power Supply :- 400/415 Volts (3 Phase AC) (h) Operation :- Full collective operation (j) Car group :- One car (simplex)
(k) Machine :- PM Gearless (Located in shaft on top of guide rails)
-
-
-
(l) Traction media :- Flat Coated Steel Belt (m) Car Finish :- (i) Rear Mid Panel = Stainless steel (finish-SS-304) (ii) Rear Corner Panels = Stainless steel (finish-SS-304) (iii) Side Mid Panels = Stainless steel (finish-SS-304) (iv) Side Corner Panels = Stainless steel (Hairline) (v) Front Panels = Stainless steel (Hairline
-
-
-
(n) False ceiling type :- CD-41
-
-
-
(O) False ceiling finish :-Stainless Steel (Hairline)
-
-
-
(p ) Ventillation :- Cross flow fan
-
-
-
(q) Hand Rails :- Stainless Steel Mirror Finish Handrails on rear car panels (side LH, side RH&Rear)
-
-
-
(r) Flooring :- GRNITE
-
-
-
(s) Car door finish :- Stainless steel (finish-SS-304)
-
-
-
(t) Landin door finish :- Stainless steel (finish-SS-304)
-
-
-
(u) Fire rated doors :- Fire rating-60mins
-
-
-
(v) Pit depth :- 1350
-
-
-
(w) Overhead :- OVERHEAD 4000 mm
-
-
-
(x) Hoistway dimensions (W x D – mm) :- 1600 mm W x 1500 mm D
-
-
-
(y) Car dimensions (W x D x H - mm) :- 1000 mm W x 1100 mm D x 2200 mm D
-
-
-
(z) Car & hoistway door type :- Telescopic 2 speed doors
-
-
-
(aa) Door openign (W x H - mm) :- 800 mm W x 2000 mm H
-
-
-
(ab) Door operator :- DC Door Operator
-
-
-
(ac) Cop[ :- COP for stops = 12 (950mm) in Stainless Steel (Hairline)
-
-
-
(ad) Car position indicator :- Monochrome LCD-Blue Background & Blue font
-
-
-
(ae) Hall fixtures :- O2000
-
-
-
(af) Hall fixture face plate :- Stainless Steel (Hairline)
-
-
-
(ag) Hall button Arrangement :- LCD MONOCROME TYPE
-
-
-
(ah) Standard Features :- Anti-nuisance Car Call Protection Independent Service (for Duplex only), Overload, Device, Nudging, Emergency Firemen’s Service Emergency Car Light Unit Infrared Curtain Door Protection, Door Time Protection, Emergency Alarm Button, Extra Door Time of Lobby & Parking, Door Open/Close Button, Manual Rescue Operation, Belt Inspection Drive, Auto Fan Cut Off
-
-
-
(aj) Options Included :- Automatic Rescue Operation Intercom
-
-
-
(ak) Provision of emergency key opening at all landings.
-
-
-
(al) PVC insulated, multistranded sheathes flexible 1100V grade copper conductor cable suitable for 3 phase, 415 V multi core cable from ground floor to lift machine room for lift controller and gear motor and single phase 240V copper conductor cable from ground floor to lift machine room for car heihts, hoist way light, machine room light complete with including switch gear items and RCBO/MCBs etc in suitable sheet steel eclosure.
-
-
-
Note :- The following works are deemed to be included in rate quited by the contractor.
(i) Any accessories/items/safty devices required to be installed and not coverd in schedule are to be provided by contractor without extra cost.
(ii) Testing shall be done by any state Govt licenced Lift Inspector (Goa State) and necessary certificate to be obtained by the contractor and produced to the Garrison Engineer.
-
-
-
Supply, laying, testing and commissioning multistranded copper conductor cable of cross sectional area 6 sqmm; 4 core conforming to IS:7098 part-I, making cable connections by providing suitable aluminium lugs with proper crimping and steel glands and laid in trenches / ducts / floors / roofs or through pipes etc complete all as specified and directed .
150
-
-
Supply, laying, testing and commissioning multistranded copper conductor cable of cross sectional area 2.5 sqmm; 2 core conforming to IS:7098 part-I, making cable connections by providing suitable aluminium lugs with proper crimping and steel glands and laid in trenches / ducts / floors / roofs or through pipes with saddles and fixing screws etc complete all as specified and directed .
300
-
-
Excavation in trenches by cutting of road/concrete/bituminous/PCC hard standing getting out and levelling of bottom surface to required level for laying of UG cable/pipe all as directed.
6
-
-
Supply and fix MCCB 100 amps 4 Pole , 25 KA , 50 Hz 415 Volts to be fixed in existing panel board after making addition alteration and making bus bar extension with necessary of suitable size all as specified and directed.
2
-
-
M & L for Earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below normal ground level connected to copper strip size 20 x 3 mm thick by mean of nuts/bolts, check nuts and washers of brass as shown in electrical plate No. 5 of SSR part-I including necessary excavation and earth work, GI Pipe 15 mm bore light grade for watering with Funnel, wire mesh and protection to earthing strip shall be provided with GI pipe light grade 32 mm dia up to 7.5 mtr from the earth plate electrode and refilling of soil including adequate quantity of charcoal dust and common salt etc & earth work in any strata, PCC pit chamber in cement mortar 1:3:6 type C-2 with 40 mm thick Precast RCC cover slab 1:2:4 type B with 8 mm dia TMT bar and handle with lifting hooks including testing any type complete all as specified and as directed.
4
-
-
M & L for Earthing complete with Galvanised earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanised earth wire 4 mm dia by mean of nuts/bolts, check nuts and washers of brass as shown in electrical plate No. 5 of SSR part-I including necessary excavation and earth work, GI Pipe 15 mm bore light grade for watering with Funnel, wire mesh and protection to earth lead shall be provided with GI pipe light grade 20 mm dia up to 7.5 mtr from the earth plate electrode and refilling of soil including adequate quantity of charcoal dust and common salt etc & earth work in any strata, PCC pit chamber in cement mortar 1:3:6 type C-2 with 40 mm thick Precast RCC cover slab 1:2:4 type B with 8 mm dia TMT bar and handle with lifting hooks including testing any type complete all as specified and as directed.
1
-
-
S&F vertical type MCCB DB VTPN 8 way, 415 volts, double door, factory made sheet metal enclosure with 200 amps rated copper bus bar, neutral bar, earth bar painted with epoxy based powder coated suitable for mounting MCCB FP 100 amps as incomer and MCB TP/SP as outgoings complete with IP-43 protection and concealed in wall including making incoming and outgoing cable/wire connections complete all as specified and directed. Note:- MCCB/MCBs will be measured & paid seperately
1
-
-
S & F MCB TPN 63 amps 415 volts C curve, 50 HZ AC 10 KA including lugs complete all as specified and as directed
2
-
-
S & F 6 to 32 amp rating 240 V, 10 KA "C" curve miniature circuit breaker (MCB) of following poles and current carrying in the DB complete with connection testing and commissiooning all as specified and as directed
4
-
-
S & F MCB TP 40-63 amps 415 volts C curve, 50 HZ AC 10 KA complete all as specified and as directed
1
-
-
S & F MCB SPN 06 -32 amps 230 volts C curve, 50 HZ AC 10 KA complete all as specified and as directed
2
-
-
supply, installation, testing and commissinoning LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC, 50Hz indoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 2 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening,locking arrangement, cable alleys, bus bar chamber and switch gear compartment, hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, copper bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length, incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate ) in foundation design subject to approved of GE to sent the site requirement complete all as specified and directed including comprising of following :-
1
-
-
(a) MCCB 100 Amps, FP, 25 KA, 415 volts, 50Hz- 01 No
-
-
-
(b) MCB 40 Amps, DP, 10 KA, 415 volts, 50Hz- 02 Nos
-
-
-
(C) Digital voltmeter, with VSS - 01 set
-
-
-
(d) Digital Ammeter with CTs & ASS- 01 set
-
-
-
() LED phase indication lamps RYB- 01 set
-
-
-
(h) Copper bus bar TPN 200 Amps rating - 01 set
-
-
-
Sch 'A' Part- VII COMPREHENSIVE MAINTENANCE
-
-
-
First year Comprehensive maintenance after expiry of defects liability period.Repair & routine maintenance of lift including carrying out daily check and periodical services and attending lift in case of emergency for a period of 12 months. The lift is fully electrically operated Microprocessor controlled (6 Person) 408 Kg, speed 1 metre/sec, including with single speed motor 415 volts, 3 phase, AC 50 Hz supply conforming to IS-14665, suitable to serve upto 4 floors (G+3 floors) upper floors with AC Variable Voltage & Variable Frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set complete all as specified.
1
-
-
Note :- (a)After DLP period all minor/major equipments i.e. main control card, door drive. Main WVF drive, wiring, digital display, sensor, door spring, door roller, LOP, etc should be replaced to make serviceable of the lift. (b) All major worn out / defective part while executing the work shall be provided by the contractor at free of cost. (c) Contractor should submit copy of MOU with the OEM to GE. The MOU shall be submitted atleast 6 months prior to the issue of completion certificate of the main contract. (d) Contractor has to submit monthly maintenenace report for every month to the department.
(e) Carrying out lift inspection by Goa State Authorized Agency/Lift Inspector at site & submit report to the department for the 6 passenger (408 kg) capacity lift (f) If the operation of Lift become unserviceable for more than 24 hrs the Penalty will be imposed. Penalty amount will be apx Rs 5000/ as incovenient Charge.
-
-
-
Same as Item No. 21.10 after completion of BOQ Item No 21.10 here in before.
1
-
-
Same as Item No. 21.10 after completion of BOQ Item No 21.20 here in before.
1
-
-
Same as Item No. 21.10 after completion of BOQ Item No 21.30 here in before.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%