Delhi Jal Board Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Delhi Jal Board - DJB Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date27 Jul 2024
Closing Date3 Aug 2024
Tender AmountRefer Documents
Costs
EMD
₹ 8,200Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_DJB_260173_2Bid Award Id
ViewTender No
NIT NO. 08(M-6)Tender Authority
Delhi Jal Board ViewPurchaser Address
-Website
http://govtprocurement.delhi.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
S/o Moulded Case Circuit Breaker (MCCB) of rating 125 Amp, Triple pole, 415 V, AC of breaking capacity of 36 KA or more. Make:-L&T/Schneider/BCH/C&S
2
-
-
S/O Motor protection Relay MPR 300 32-88 AMP Make:-L&T/Schneider/BCH/C&S
2
-
-
S/o overload Relay for 30 to 40 HP, 40 – 60 Amp MN 5 Make:-L&T/Schneider/BCH/C&S
2
-
-
S/o Single Phase Preventer Make:-L&T/Schneider/BCH/C&S
2
-
-
S/o Ampere Meter Digital type. Make:-L&T/Schneider/AE
3
-
-
S/o Volt Meter Digital type. Make:-L&T/Schneider/AE
1
-
-
S/o Ampere Meter selector switch. Make:-L&T/Schneider/BCH/C&S
3
-
-
S/o Volt meter selector switch. Make:-L&T/Schneider/BCH/C&S
1
-
-
S/o Indicating Lamp, Led type Make:-L&T/Schneider/BCH/C&S
9
-
-
S/o MCB, 63 Amps, TP, ‘C’ Curve. Make:-L&T/Schneider/BCH/C&S
2
-
-
S/o Current Transformer 100/5 ampere. Make:-AE/ Kuppa / Matrix
6
-
-
S/o Current Transformer 200/5 ampere. Make:-AE/ Kuppa / Matrix
3
-
-
Other material required like insulators, heat shrinkable sleeve, bakelite, nuts & bolts, aluminum thimbles, ferrules, rubber packing etc. as required.
1
-
-
Supply of Manually operated oil immersed sheet steel clad wall mounting star – Auto Transformer starter fitted with 1 No. Under voltage release, 3 Nos. Magnatic Overload Release with Oil Dashpot time lags, stop leaver, plain enteries for PVC cables suitable for Squirrel case induction motor 415 V, 3 Phase, 50 Hz, 30-40 HP Heavy Duty Make: - Advance, Bentax or any approved in DJB
2
-
-
Fixing of new base frame at the site with the help of fasteners / welding and grouting of nut bolts and including all other work as per site requirements and Fixing the new L T Panel at the newly fixed base frame by lifting the panel board and placing it at the base frame properly and fixing it to the frame by nut bolts as requirement. Fabrication and supply of base frame made out of Angle Iron of suitable size for fixing the above Panel and suitable for making outgoing /incoming cable entries in the panel. It should be duly painted and ready with provisions for installing at the site.
1
-
-
Making the incoming connections to the Panel by connecting the existing cables after proper thimbling etc. including providing & fixing of consumables as per requirement. Making the outgoing connections of starters by Connecting outgoing starters to their respective pumps etc. Through existing cables as per site requirement after relaying of the cables as required, proper thimbling and tapping etc. including providing & fixing of material as per requirement. Making the outgoing connections of lighting DB by Connecting outgoing MCBs to the DBs etc. through the existing cables as per site requirement after relaying of the cables as required, proper thimbling and tapping etc. including providing & fixing of material as per site requirement.
1
-
-
Testing and Commissioning of the Panel Board first at NO LOAD and then at ON LOAD and Operations as per the satisfaction of engineer in charge. Loading, Unloading, Cartage and Transportation charges for the above Panel up to the site including charges of heavy labour etc.