Military Engineer Services Tender

View complete overview of Chandigarh MES Tender

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date9 Feb 2024
Closing Date7 Mar 2024
Tender Amount₹ 41,50,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply only constant current LED driver 45 Watts IP 65 of following specifications:- (a) Operating voltage Range- V (in) 187 to 280 Volts AC. (b) Frequency- 50/ 60 Hz. (c) PF- 0.98. (d) V out- 30 to 42 V DC. (e) I out- 250 mA.

25

-

-

... More
Supply only constant current LED driver 60 watts IP 65 of following specifications:- (a) Operating voltage Range- V (in) 100 to 265 Volts AC. (b) Frequency- 50/ 60 Hz. (c) PF- 0.98. (d) V out- 30 to 42 V DC. (e) I out- 350 mA.

60

-

-

... More
Supply only constant current LED driver 90 watts IP 65 of following specifications:- (a) Operating voltage Range- V (in) 120 to 277 Volts AC. (b) Frequency- 50/ 60 Hz. (c) PF- 0.98. (d) V out- 64 to 143 V DC. (e) I out- 700 mA.

60

-

-

... More
Supply only constant current LED driver 120/ 150 watts IP 65 of following specifications:- (a) Operating voltage Range- V (in) 120 to 277 Volts AC. (b) Frequency- 50/ 60 Hz. (c) PF- 0.98. (d) V out- 64 to 140 V DC. (e) I out- 1050 mA.

60

-

-

... More
Supply only constant current LED driver 200 watts IP 65 of following specifications:- (a) Operating voltage Range- V (in) 198 to 264 Volts AC. (b) Frequency- 50/ 60 Hz. (c) PF- 0.98. (d) V out- 71 to 21 V DC. (e) I out- 2800 mA.

50

-

-

... More
Supply only constant current LED driver 250 watts IP 65 of following specifications:- (a) Operating voltage Range- V (in) 198 to 264 Volts AC. (b) Frequency- 50/ 60 Hz. (c) PF- 0.98. (d) V out- 71 to 21 V DC. (e) I out- 2800 mA.

30

-

-

... More
Supply and fixing in repairs LED surge protection device having maximum discharge surge current (Imax)- 10kA (8/20 µs), Nominal discharge surge current (In)- 5kA (8/20 µs) and protection level (Up) upto 5KV upto 200 watt security light/ flood light fitting complete all as specified and directed.

100

-

-

... More
Supply & replacement of energy saving LED street light 90 watt capacity high pressure die cast aluminium housing with seal toughened glass cover, light source should be multi LED SMD array with individual secondary lenses, colour temperature 9000K, 500(±) system efficiency should be minimum 100 lumen/ watt and minimum system lumen package of 9900 lumen as LM 79 operating voltage range 120-180 volts IP-66 THD less than 10%, surge protection minimum 5 KV with flash indication, driver should be potted/ CE certified/ R certified and driver efficiency 85% including making connection complete all as specified and directed.

30

-

-

... More
Supply & replacement of energy saving LED flood light 50 watt capacity high pressure die cast aluminium housing with seal toughened glass cover, light source should be multi LED SMD array with individual secondary lenses, colour temperature 4900K, 500(±) system efficiency should be minimum 98 lumen/ watt and minimum system lumen package of 6000 lumen as LM 79 operating voltage range 120-180 volts IP-66 THD less than 10%, surge protection minimum 5 KV with flash indication, driver should be potted/ CE certified/ R certified and driver efficiency 85% including making connection complete all as specified and directed.

10

-

-

... More
Supply & replacement of energy saving LED flood light 200 watt capacity high pressure die cast aluminium housing with seal toughened glass cover, light source should be multi LED SMD array with individual secondary lenses, colour temperature 6500K, 500(±) system efficiency should be minimum 120 lumen/ watt and minimum system lumen package of 6000 lumen as LM 79 operating voltage range 120-180 volts IP-66 THD less than 10%, surge protection minimum 5 KV with flash indication, driver should be potted/ CE certified/ R certified and driver efficiency 85% including making connection complete all as specified and directed.

25

-

-

... More
Supplying and fixing 10sqmm flat twin core heavy duty cable 1100 volts grade PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire including taking down existing cable complete all as specified and directed.

200

-

-

... More
Supplying and fixing 6sqmm flat twin core heavy duty cable 1100 volts grade PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire including taking down existing cable complete all as specified and directed.

200

-

-

... More
Supplying, laying in trenches/ passing through tubing/ pipes or laid under floors or through walls/ ducts etc., jointing and testing, 1100 volts grade XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, LT electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 95 sqmm 3½ core, including both sides connection with and including cable lugs etc., including taking out existing unserviceable cable, complete all as specified and directed.

250

-

-

... More
Supplying, laying in trenches/ passing through tubing/ pipes or laid under floors or through walls/ ducts etc., jointing and testing, 1100 volts grade XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, LT electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 70 sqmm 3½ core, including both sides connection with and including cable lugs etc., including taking out existing unserviceable cable, complete all as specified and directed.

310

-

-

... More
Supplying, laying in trenches/ passing through tubing/ pipes or laid under floors or through walls/ ducts etc., jointing and testing, 1100 volts grade XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, LT electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 35 sqmm 3½ core, including both sides connection with and including cable lugs etc., including taking out existing unserviceable cable, complete all as specified and directed.

600

-

-

... More
Supplying, laying in trenches/ passing through tubing/ pipes or laid under floors or through walls/ ducts etc., jointing and testing, 1100 volts grade XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, LT electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 25 sqmm 4 core, including both sides connection with and including cable lugs etc., including taking out existing unserviceable cable, complete all as specified and directed.

500

-

-

... More
Supplying, laying in trenches/ passing through tubing/ pipes or laid under floors or through walls/ ducts etc., jointing and testing, 1100 volts grade XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, LT electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 16 sqmm 4 core, including both sides connection with and including cable lugs etc., including taking out existing unserviceable cable, complete all as specified and directed. Note for item No. 15.00 to 17.00: Excavation & earthwork, sand cushioning & brick protection shall be measured and paid for separately.

200

-

-

... More
Supply and laying in replacement 40mm bore GI tubing light grade pipe with all fitting laid in trenches, fixed to well etc. complete all as specified and directed.

20

-

-

... More
Supply and laying in replacement 50mm bore GI tubing light grade pipe with all fitting laid in trenches, fixed to well etc. complete all as specified and directed.

45

-

-

... More
Supply and laying in replacement 80mm bore GI tubing light grade pipe with all fitting laid in trenches, fixed to well etc. complete all as specified and directed.

20

-

-

... More
Supply and fix in repairs water proof ABS electric distribution box, weather proof IP-65 protection suitable for outdoor use, pole mounted, factory made of size 300mm x 250mm x 150mm comprising one No. MCB SP 6 Amps, 240 volts TPN bus bar not less than 25mm x 5mm aluminium strip and fixing clamps of size 25mm x 5mm two nos including necessary nuts, bolts and locking arrangement with lock, pressure type, four Nos connection holes in each bus bar with nuts, bolts and washers made of galvanized iron and connection thimble etc. complete all as specified and directed.

50

-

-

... More
M&L for boring of holes under road, pavement, hard standing etc. by any means for inserting GI/ CI/ HDPE pipe upto 150mm bore complete all as specified and directed.

50

-

-

... More
Excavation in trenches in any type of soil n. exc. 1.5m deep and n. exc. 1.5m in width and getting out including forming bottom surface to required slope/ gradient for laying cables/ pipes etc. complete all as specified and directed. Notes: (i) Excavation shall be done carefully to avoid damage of existing cables and protection covers. (ii) Excavation work may be got carried out in short lengths for locating fault in underground cables at different locations.

493

-

-

... More
Returning filling in excavated soil including spreading, levelling, watering and well ramming in layers, each layer not exceeding 25mm thick in soft/ loose soil complete all as specified and directed.

159

-

-

... More
Removing excavated spoil n. exc. 50m and depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified and directed.

334

-

-

... More
M&L for sand cushioning to cables with a layer of sand 8cm thick before laying the cable and 15cm thick punned down after laying and stretching of cable) complete all as specified. (Punned thickness (overall 18cm) shall be measured & paid).

118

-

-

... More
M&L old size sub class ‘B’ bricks for protection to cable laid flat abutting each other perpendicular to direction of cable direction complete all specified and directed.

10.89

-

-

... More
M&L for preparation old painted surfaces of LT steel poles 9.00m long and painting applying one coat of synthetic enamel paint in 30cm wide strips alternate in black and yellow colour upto 1.5 mtr height above muff and the remaining portion with one coat of aluminium paint and writing pole no on pole with white paint complete all as directed at site all as specified and directed.

100

-

-

... More
Supply and fix aluminium cable lugs suitable for 10 Sqmm to 25 Sqmm size cable all specified and directed.

100

-

-

... More
Supply and fix aluminium cable lugs suitable for 35 Sqmm to 50 Sqmm size cable all specified and directed.

100

-

-

... More
Supply, fix, connecting and testing MCCB four pole, 63 Amps, 415 volts, 16kA breaking capacity with adjustable thermal setting having Ics= 100% Icu including taking down the existing one complete all as specified and directed.

2

-

-

... More
Supply, fix, connecting and testing MCCB four pole, 100 Amps, 415 volts, 25kA breaking capacity with adjustable thermal setting having Ics= 75% Icu including taking down the existing one complete all as specified and directed.

2

-

-

... More
S&F in replacement of MCCB, 4 pole, 125 Amps, 25 KA, 50Hz, 415 volts with Ics= 75% of Icu complete with adjustable thermal & adjustable magnetic type relays complete all specified and directed.

4

-

-

... More
S&F in replacement of MCCB, 4 pole, 160 Amps, 25 KA, 50Hz, 415 volts with Ics= 70% of Icu complete with adjustable thermal & adjustable magnetic type relays complete all specified and directed.

4

-

-

... More
S&F in replacement of MCCB, 4 pole, 250 Amps, 25 KA, 50Hz, 415 volts with Ics= 75% of Icu complete with adjustable thermal & adjustable magnetic type relays complete all specified and directed.

2

-

-

... More
S&F in replacement of MCCB, 4 pole, 200 Amps, 25 KA, 50Hz, 415 volts with Ics= 75% of Icu complete with adjustable thermal & adjustable magnetic type relays complete all specified and directed.

2

-

-

... More
S&F in replacement MCB, SPN, 230V, 6 Amps AC, 10 KA, 'C' series and 50Hz complete all as specified and directed.

20

-

-

... More
M&L repair to door hinges and door locks of LT panel board/ feeder pillar box of any size any description including scrubbing/ scratching of old rusted paint by burning through blow lamps and painting the complete of LT panel board/ feeder pillar box externally and internally with 02 coats of approved colour superior quality synthetic enamel paint over a coat of red oxide primer complete al as specified and as directed.

10

-

-

... More
Site clearance including cutting of grass/ trimming of all bushes/ small trees upto a height of 10 feet in surrounding areas of perimeter security lights, E/M installations, panels, bus bar chambers etc. including sprinkling of herbicide solution as per manufacturer's instructions complete all as specified and directed.

1000

-

-

... More
M&L for dismantling old earthing and providing new earthing complete with galvanised steel earth plate electrode 600mmx 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level connected to galvanised iron strip of size 25mm x 4mm by means of bolts, nut check nuts and washers earth strip protected by galvanized steel pipe 40mm bore (light grade) connected to test point all as shown in electrical plate No. 3 of SSR 2009 (Part-I) and including necessary excavation and earth work in any type of soil, 20mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, pit cover of precast RCC (1;2:4), type B-1 reinforced XPM of weight not less than 4 Kg/ Sqm and MS frame etc. complete & connected to earthing test point all as specified or indicated including brazing/ testing on completion complete all as specified and directed. Notes:- (i) The unit rate includes galvanised Iron strip and protection pipe upto (maximum 7.5m from earth plate) earth point/ test point. (ii) The complete earth system shall be guaranteed to give result less than 5 ohm resistance.

23

-

-

... More
Supply, install, test & commissioning factory made LT feeder pillar box of size 75cm x 75cm x 60cm with set of 4 strip copper bus bar 200 Amp, 1100 volt grade, 60cm long duly sleeved with relevant colored sleeved cubical outdoor type, weather proof, fabricated out 14 SWG MS sheet, welded on 40mm x 40mm x 6mm angle iron frame & having four Nos 120cm long legs made out of 50mm x 50mm x 6mm angle iron below frame grouted on ground in concrete block of size 80cm x 80cm x 20cm built in PCC (1:2:4) of suitable size with front & rear openable door having locking arrangements, bottom space for cable entry with duly internally and externally painted with two coats of dark grey synthetic enamel paint over a coat of red oxide primer including dismantling and taking down existing feeder pillar box complete all as specified and directed.

6

-

-

... More
Supply, installation, testing and commissioning in replacement LT cubical panel (CPRI Approved) of size 1000mm x 750mm x 550mm with set of 400 Amp, 4 strip bus bars duly sleeved with relevant colored insulation heavy duly mounted on insulators; factory made, compartment type, dust and vermin proof (IP-55) duly powder coated outdoor type suitable for 1100 volts grade, 3 phase, 4 wire supply, floor mounted fabricated out 3.15 mm MS Sheet on 50mm x 50mm x 6mm angle iron frame, 120cm long angle iron legs for grouting in floor with cement concrete PCC foundation of suitable size in (1:2:4) and front & rear double door type inclusive locking arrangement with provision of all incoming/ outgoing cable entries alongwith suitable size of double compression type cable gland for incoming & out going cable duly internally and externally painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and comprising the following:-

2

-

-

... More
Incoming: (a) Digital MCCB AC, 4 pole, 200 Amps, 25 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 75% of ICu)- 01 No. Outgoing: (b) Digital MCCB AC, 4 pole, 100 Amps, 16 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 100% of ICu)- 01 Nos. (c) Digital MCCB AC, 4 pole, 63 Amps, 10 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 100% of ICu)- 02 No. (d) Digital LED Amps meter with CT’s 400/ 5 amps and selector switch- 01 No. (e) Digital LED Voltmeter 0-500 volts with selector switch- 1 No. (f) Phase indicator lamps RYB- 01 Set. (g) Internal connections with colour code copper cable multistranded of suitable size copper thimbles etc. as per manufacturers design and specifications. (h) Danger notice plate 440 V with conventional skull and bones in red signal colour- 01 No. (j) Spare space for mounting 01 No. MCCB.

-

-

-

... More
S&F steel tubular swaged pole type 410 SP-31 (9.00 metre long) complete with MS base plate not less than 8mm thickness and painting the pole internally through out and externally upto the planting depth with two coats of black bitumouns paint and remaining external portion upto 1.50m height above PCC with two coats of synthetic enamel paint in alternate layer of black & yellow colour of 30cm height each and the remaining portion of pole including swan neck with two coats of aluminium paint over a coat of red oxide primer including dismantling of existing steel poles including foundation concrete complete all as specified and directed.

10

-

-

... More
M&L for plain cement concrete (1:3:6) type C-1 using 20mm graded crushed stone aggregate for coping of poles including provision of necessary form work and finishing the exposed surface even and smooth in cement mortar (1:3) and applying two coats of white wash to the portion of PCC muffs above ground level weathering, slightly rounded or chamfered angles and throating complete all as specified and directed.

0.8

-

-

... More
M&L for cement concrete (1:4:8) type D-2 using 40mm graded crushed stone aggregate in foundation filling & mass concrete for poles/ struts/ stays assembly complete all as specified and directed.

2

-

-

... More
S&F in replacement light sensitve control unit for street light control panel as pole/wall mounted enclouser consisting of natural switch power contractor rating of 40 Amps (AC3) and 63 Amps MCB and terminal blocks. The enclosure comes complete with mounting bracket on wall /pole with clamps, openable door with lock and key. The enclousure shall be made of UV stablized FR grade special moulding compound to provide a rust proof, electric shock proof, termite proof outdoor mountable electrically insulating body capable of enduring solar radiation in the outdoor. Specification of light sensitive control unit shall be as under: (i) Operating Voltage : 230 Volt 50 Hz + 20% (ii) Switching Endurance : Minium 5000 Cycles (iii) Operating illuminume levels : (a) For switching ON - 60 Lux for 30Sec (b) For Switching OFF - 10 Lux for 30 Sec (iv) Auto voltage Trip levels : (a) High Volatge Trip /Auto reset : 285 VAC,270 VAC (b) Low Voltage Trip /Auto reset : 150 VAC,165 VAC (v) Oprating state indication : Through LED (vi) Duration based Switch OFF option : 04 to 08 Hrs With a resolution of ½ hour (vii) Over ride option : Control ON and Control OFF Make SWADEEP Model SWADEEP-02EC12kW3P or equivalent in performance in make L&T/ GE Lighting / Indoasian as approved by GE.

4

-

-

... More
M&L for maintenance of 16m to 30m high mast pole structure accessories by removing any debris, greasing to gears and transitional yoke and other moving parts including lift cable operation, repair to light control box, gear pulley, steel wire rope, mobile rungs, adjustment of head frame and fixture mounting ring including replacement of spare required in the maintenance schedule like power cable, steel wire rope and filling of gear oil complete all as directed.

27

-

-

... More
M&L for taking out unserviceable 2/3HP, 3 phase induction motor from existing high mast alongwith mounting pulley after taking out the gear assembly, transporting the motor to workshop and rewinding the same with super enameled copper wire of standard gauge, bringing back to site and refixing the same after carrying the other work like fixing of connector, connecting strip etc. complete all as specified and directed. Note: No credit against old winding will be deducted in credit schedule and quoted rate shall be deemed to be after accounting credit of copper.

11

-

-

... More
M&L for replacement of 24 hour analog time switch comfort and save energy capable of switching loads automatically as per real time and replacement of contactor MNX 32 Amps, MNX A2 amps complete all as specified and directed.

11

-

-

... More
S&F in replacement MCB, TPN, 230V, 63 Amps AC, 10 KA, 'C' series and 50Hz complete all as specified and directed.

6

-

-

... More
Supply and fixing in replacement 250 watt LED flood light fittings made up of pressure die cast aluminium housing with toughened glass and high power LED's and secondary lenses with IP 66 protection; system efficiency 110/ 125/ 135 LPW, 10 KV SPD all as specified and directed.

12

-

-

... More
M&L PVC insulated with three runs of 2.5 Sqmm single core, multistranded, FR PVC insulated unsheathed cable 1100 volts grade with copper conductor from main control board of high mast pole of LED light fixed on the pole wound with PVC ring of suitable size to hold the cable inside the high mast including making connection to lights and panel including taking down existing wiring complete all as specified and directed. Note: Three runs of cable shall be considered as one unit length.

170

-

-

... More
S&F indoor/ outdoor type heat shrinkable type cable jointing kit for LT 1100 volts grade cable for straight through joint complete with accessories suitable for 3½/ 4 core XLPE armoured aluminium conductor cable of size 25 to 50 sqmm complete all as specified and directed.

5

-

-

... More
All as per item No. 56.00 above but for cable of size 70 to 95 Sqmm.

6

-

-

... More
All as per item No. 56.00 above but for cable of size 120 to 150 Sqmm.

5

-

-

... More
M&L for isolating the main supply from the DG set of capacity 63 KVA to 125 KVA, dismantling the complete engine by taking out head, sump piston assembly, water sleeves, connecting rod, big end bearing, main end bearing, tapped assembly, inlet and outlet valves etc. including drainage out engine oil and keeping in container, Reassembly of engine after replacement of required accessories and testing the engine after making connection with alternator on load to the satisfaction of Engineers-in-Charge. Labour charges for replacement of new parts shall be deemed to be included in this item. However, supply of items required to be replaced will be paid separately. Parts where grinding, calibration or lapping is required at workshop will be measured and paid separately. Accessories required for overhauling of DG set shall be measured and paid separately.

2

-

-

... More
M&L for decarbonisation of valve heads of DG of capacity 125 KVA and job making the surface free from carbon contents and lapping of inlet and outlet valve 12 No’s complete all as directed.

2

-

-

... More
M&L for complete overhauling of fuel injecting pump of DG set of capacity 125 KVA and replacement of plungers, delivery valve and spring washer, cam shaft, pump, rack & pinion and testing the same after carrying out the job work from authorized workshop complete as specified and directed by Engineer-in-charge.

2

-

-

... More
M&L for repair of injector nozzle of DG set of capacity 125 KVA and testing the injector assembly- 6 No. for proper delivery of the fuel including replacement of any parts like spring washers, plunger and barrel spring required complete as specified and directed by Engineer-in-charge.

2

-

-

... More
Supply only the following parts for DG set of capacity 125 KVA:-

-

-

-

... More
Piston assembly

12

-

-

... More
Liner assembly

12

-

-

... More
Piston ring set

12

-

-

... More
Connecting rod

4

-

-

... More
Gasket set complete for lower and upper parts

2

-

-

... More
Water pump assembly

2

-

-

... More
Thermo-state

2

-

-

... More
Turbo charger repair kit

2

-

-

... More
Fan belt

2

-

-

... More
AVR

2

-

-

... More
Diode assembly

2

-

-

... More
Main Bearing (Set of seven)

2

-

-

... More
Large End Bearing (Set of 12)

2

-

-

... More
Air Filter

2

-

-

... More
Fuel filter

2

-

-

... More
Oil filter

5

-

-

... More
Engine Oil

40

-

-

... More
Hose pipe set

2

-

-

... More
Supply and fixing automatic transfer switch (ATS), 4 pole, 415 volts with inbuilt time delay with enclosures of rating 160 Amp including taking down old complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB

2

-

-

... More
Supply and fixing automatic transfer switch (ATS), 4 pole, 415 volts with inbuilt time delay with enclosures of rating 200 Amp including taking down old complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB

3

-

-

... More
S&F in replacement for power contactor 4 pole type 80/ 100 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB

3

-

-

... More
S&F in replacement for power contactor 4 pole type 160 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB

3

-

-

... More
S&F in replacement for power contactor 4 pole type 200/ 250 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB

3

-

-

... More
S&F in replacement for power contactor 4 pole type 400 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB

2

-

-

... More
Supply, fixing, testing and commissioning in replacement of Air Circuit Breaker (ACB) 1000 Amps, 4 pole with microprocessor release IPR 1+ ,50 kA, 415 Volt, manual drawout type conforms to IS/IEC:60947-2 in existing place including removing of LT connection to old ACB and jointing of LT connection to new ACB complete all as specified and directed. Make: Havells Model Titania E series IPR E+ or equivalent in performance in L&T/ Siemens/ ABB as approved by GE. Note: Mentioned work will be carried out by manufacturer's representative only to the entire satisfaction of Engineer-in-charge.

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.